Professional Documents
Culture Documents
1g Roof Dainage and Design
1g Roof Dainage and Design
Damp Penetration:
There are many reasons why a building suffers from
damp penetration. The main reasons are faulty
rainwater goods such as gutters and down pipes.
Gutters.
(Carry the rainwater)
A gutter should be laid with a slight fall towards the outlet.
Gutters fixed with a fall have a greater carrying capacity than
when fixed level.
Experiments by the Building Research Establishment have
shown that an eaves gutter with a fall of 1 in 600 will carry up
to 40 % more water than when fixed level.
600
Roof Drainage and Design.
Example:
Roof Drainage and Design.
The rate of run-off from a roof may be found from the following
formula:
Q = 2.5 litre/sec
Roof Drainage and Design.
Example 3
10 m
20 m
Roof Drainage and Design.
Rate of run-off:
Q = roof area (m2) x rainfall (m/hour) x 1000 (l/sec)
3600
The area to be drained to each gutter is 10m x 10m so
Q = (10 x 10) x (0.075) x 1000
3600
Q = 2.083 litre/sec
From Table 15, one 150mm gutter and one 89mm downpipe
could cope with a flow capacity of 2.16 litre/sec from a maximum
effective roof area of 103m2.
This will be fine in this situation as the roof area to be drained is 100m2
and our flow capacity is 2.08 litre/sec.
From Table 15, one 115mm gutter and one 63mm downpipe
could cope with a flow capacity of 1.11 litre/sec from a maximum
effective roof area of 53m2.
This will work as the roof area to be drained is 40m2 and our rate of
run-off is 0.833 litre/sec.
Roof Drainage and Design.
Example 5
Size the gutters and downpipes for a roof of dimensions 20m x 10m
with a pitch of 30.
Plan area of roof is 20m x 10m.The gutter is to be placed along the
10m length.
Roof Drainage and Design.
To calculate the effective area, the plan area for each half of the roof,
and therefore each gutter, would be 10m x 10m.
From Table 14, with a pitch of 30, the effective area is plan area x
1.15.
Rate of run-off:
Q = 2.396 litre/sec
Looking at Table 15, there is no one gutter and downpipe which can
cope with a flow capacity of approximately 2.4 litres/sec. So in this
case, we need to use more than one downpipe.
From Table 15, a 125mm gutter and 75mm downpipe could cope with a
flow capacity of 1.37 litre/sec from a maximum effective roof area of 65m2.
This will work as the roof area to be drained is 57.5m2 and our rate of run-off
is 1.198 litre/sec.
The downpipes could be placed at either end of the guttering, but placing
them in from the end would give a more efficient system.
Roof Drainage and Design.
Example 6
Size the gutters and downpipes for a roof of dimensions 35m x 20m
with a pitch of 32. Plan area of roof is 35m x 20m.
The gutter is to be placed along the 20m length.
35 m
20 m
Roof Drainage and Design.
To calculate the effective area, the plan area for each half of the roof,
and therefore each gutter, would be 17.5m x 20m.
Rate of run-off:
Q = roof area (m2) x rainfall (m/hour) x 1000 (l/sec)
3600
Roof Drainage and Design.
Q = (490) x (0.075) x 1000
3600
Q = 10.21 litre/sec
Looking at Table 15, there is no one gutter and downpipe which can
cope with a flow capacity of over 10 litres/sec. So in this case, we need
to use more than one downpipe.
The flow capacity and effective areas calculated for this roof are almost
5 times the maximum values quoted in Table 15. This suggests that 5
downpipes are needed, one every 4 metres along the length.
Roof Drainage and Design.
The effective area = 490 m2
So using 5 downpipes,
new effective area = 98 m2
From Table 15, a 150mm gutter and one 89mm downpipe could cope with
a flow capacity of 2.16 litre/sec from a maximum effective roof area of 103m2.
This will work as the roof area to be drained is 98m2 and our rate of run-off is
2.04 litre/sec. i.e. 5 downpipes, 1 every 4 metres.
NOTE:
The largest sized guttering available from most suppliers is 150mm ..
But larger ones are available.
Roof Drainage and Design.
Example 7
Size the gutters and downpipes for the pitch roof building 10m x 8m
with a pitch of 30. Note: the wall bounding the roof.
Roof Drainage and Design.
Solution;
Assume a rainfall intensity of 75 mm/hour.
The plan area of the roof is 10m x 4m = 40m2
From Table 14, to calculate the effective area of a roof with a pitch up to
30, the plan area must be multiplied by 1.15
But consideration must be made for the wall draining onto the roof.
The effective area of this must be calculated and added to give an overall
effective area.
The effective area of a wall draining onto a roof is half the area of the
wall section affecting the roof.
Roof Drainage and Design.
So effective area = ½ (6 x 2) = ½ (12) = 6
= 1.083 litre/sec
Roof Drainage and Design.
From Table 15, a 115 mm gutter and one 63mm downpipe could cope with
1.08 litres/sec draining a roof 52 m2.
Next check if this size gutter will work for both sides of the Building.
Opposite roof side has no wall draining onto it so;
Total Effective Area = 46 m2
From Table 15, a 150mm gutter and 89mm downpipe could cope with a
flow capacity of 1.8 litre/sec (we need 4 outlets)
NOTE: If the gutter had been selected based on the max effective area values
from Table 15 then only two downpipes would have been used. This would not
work for the rainfall intensity of 150 mm/hour.
The flow rate takes precedence.
Roof Drainage and Design.
Building B
The plan area of the roof is 8m x 5m = 40m2
From Table 14, to calculate the effective area of a roof with a pitch
of to 20, the plan area must be multiplied by 1.15
But consideration must be made for the wall draining onto the
roof.
Roof Drainage and Design.
The effective area of this must be calculated and added to give an overall
effective area.
The effective area of a wall draining onto a roof is half the area of the wall
section affecting the roof.
So effective area = ½ (8 x 2) = ½ (16) = 8
Then, Total Effective Area = 46 + 8 = 54 m2
= 2.25 litre/sec
Roof Drainage and Design.
Looking at Table 15, there is no one gutter and downpipe which can cope with a
flow capacity of approximately 2.25 litres/sec. So we need to use more than one
downpipe.
But the calculated flow capacity value is just over the flow capacity value for the
largest gutter given in Table 15, so we will only need to use 2 downpipes in total.
But there is no need to select the largest gutter size available. A 125 mm
gutter and 75 mm downpipe (2) could cope with half the flow capacity, 1.125
litre/sec.
NOTE: If the guttering and downpipes had been sized solely based on the max
effective area values from Table 1 only one downpipe would have been used, and
so the system would be undersized.
The flow rate takes precedence.
Roof Drainage and Design.
Next check if this size gutter will work for both sides of Building B.
Opposite roof side has no wall draining onto it so;
Total Effective Area = 46 m2
END
Any Questions.