PUMP STATION

Inlet pump stations must be installed after primary screens to protect the pumps from
being dmaged or clogged.The pump station is necessary to lift wastewater to a higher point for
treatment, to provide consistent inlet flows to the treatment system,and to prevent overflow of
raw wastewater. For safety, good ventilation and lighting are necessary. Either floats or
ultrasonic level controller may be used for the start-stop levels pumps,the ultrasonic level control
is recommended due to its clog-free.

There are two types of station:

a) Dry-well
b) Wet-well

SECONDARY SCREEN

After the inlet pump station,further screening is required to reduce the remaining floating
matter (plastic,paper,cloth and particles) and finer particles in the wastewater that will disrupt the
treatment process downstream. It is also installed to minimize blockages in sludge handling and
treatment facilities.
DESCRIPTION UNIT MANUALLY RAKED MECHANICALLY
RAKED
Design flow m³/s Qpeak or pump flow Qpeak or pump flow
whichever is higher whichever is higher
Maximum clear spacing mm 12 12
Slope to the vertical 30-45 15-45
Maximum approach velocity m/s 1.0 1.0
at the feed channel
Maximum flow through m/s 1.0 1.0
velocity velocity at the
screen face
Minimum freeboard mm 150* 150
Screenings skip storage day 7 7
capacity
Minimum channel width mm 500 500
Minimum channel depth mm 500 500
RC staircase 1 unit Anti-skid and non- Anti-skid and non-
corrosive corrosive