Warehouse Foam System: - 1 X 200 Gallon Vertical Style Bladder Tank
Warehouse Foam System: - 1 X 200 Gallon Vertical Style Bladder Tank
It is often necessary to install a fixed foam fire MAJOR FOAM SYSTEM COMPONENTS
protection system to protect warehouse facilities
where flammable liquids are stored or used during a • 1 x 200 Gallon vertical style bladder tank
manufacturing process. Listed below are two
different methods of supplying fire protection: • 1 x 4" between flange style ratio controller (Flow
range with AR-AFFF type concentrate is 400 -
1. Foam-Water Sprinkler System 1,500 gpm)
• Closed Head
• Open Head/Deluge The above design criteria could also apply to any
system designed in accordance with NFPA 16.
2. High Expansion Foam System
However, many times with a closed head foam
Design of the foam-water sprinkler system generally sprinkler system, the “Authority Having Jurisdiction”
falls under one or more of the following: over the system approval will require an application
rate in excess of .16 gpm per sq. ft. over a specific
NFPA 13: Installation of Sprinkler Systems area. Application densities ranging from .20 to .40
NFPA 16: Installation of Deluge Foam-Water gpm per sq. ft. are often used. Before the final
Sprinkler and Foam-Water Spray sizing of the foam system, establish with the
Systems “Authority” on what design density will be required
over what area. For example, an insurance carrier
NFPA 30: Flammable and Combustible Liquids might require an application rate of .30 gpm per sq.
Code ft. over 1,500 sq. ft. depending on the sprinkler
AHJ: Authority Having Jurisdiction. head used. NFPA 30 requires a similar application
Some authorities have their design rate over 1,500 sq. ft. when using high temperature
criteria for both closed head and sprinkler heads or .30 gpm per sq. ft. over 2,550 sq.
deluge type systems. ft. when using ordinary temperature sprinkler
heads.
Design Example:
DISCHARGE APPLICATION AREA
Type System: Deluge
Design Standard: NFPA 16 The area to be protected must be determined for
Dimensions: 80' x 50' correct sizing of the foam system. The area can
Stored Product: Assortment of Polar Solvent and vary according to which NFPA standard or
Hydrocarbon based liquids “Authority Having Jurisdiction” guideline the system
Foam Concentrate: 3% AR-AFFF (suitable for use is designed. NFPA 16 requires that the system be
on both Hydrocarbons and Polar Solvents) designed to flow foam over the entire risk area.
Warehouse Area: 80 x 50= 4,000 sq. ft. NFPA 16 requires the system demand area to be
Application Rate: .16 gpm per sq. ft. based on 5,000 sq. ft. unless occupancy standards
The application rate may be higher specify a different demand area. NFPA 30 requires
depending on types of polar solvent liquids the system design to be based on 2,000 sq. ft.
stored. when used to cover solid pile or palletized storage
Flow in GPM of foam solution: .16 x 4,000=640 of flammable liquids. If the system is to include an
Discharge Duration: 10 minutes 640 x 10 = 6,400 in-rack foam-water sprinkler system, the overhead
gallons of foam solution may be based on 1,500 sq. ft. for high temperature
Foam Concentrate: 6,400 x .03 = 192 gallons heads and 2,550 sq. ft. if ordinary temperature
Number of sprinkler heads: 40 (extra hazard sprinkler heads are used. The in-rack system is
occupancies, approx. 100 sq. ft. per based on three sprinkler heads per level being
sprinkler) discharged multiplied by the number of levels high.
CHEMGUARD
204 S. 6th Ave • Mansfield, Tx 76063 • (817) 473-9964 • FAX (817) 473-0606
www.chemguard.com
DATA SHEET #D10D03150
REVISION: 09/2005
DISCHARGE DURATION
water at the ratio controller; therefore, it is “forced”
NFPA 16 requires discharge duration of 10 minutes.
into the water stream even at low flow rates through
NFPA 30 requires discharge duration of 15 minutes.
the ratio controller. If using a 3% concentrate, the
Many “Authorities Having Jurisdiction” may require
ratio mix may be 4-6% at low flows.
discharge duration of 20 minutes.