Professional Documents
Culture Documents
SHOOTING
DATA: 02/09/2007
CONTINUITY TEST
SET THE MULTIMETER IN
OHM AND BUZZER
CONFIGURATION
or DC
ALARM n° 4
1. Please control that all the power supply cable are not
disconnected from the power connector (The power supply
connection depending by the crane installer, we produce the
crane and the electrical system of this part)..
3. By Digital Multimeter set in ohm and buzzer configuration please
check the cable continuity between the power connection wire to
pin 43 of the 56 pin plug (see the sketch).
If there is not continuity in this line the internal wire of
the harness is broke.
Replace the main wiring of the crane and contact the after sales department
ALARM n°
5 - Faulty block output on
6 - Faulty block output off
Due to:
diode
+ -
Resistor LED
Remove the Diode from the connector and reconnect the electrical
part in to the solenoid.
Press RESET button in to the Load Limiting Device do delay the
alarm and verify if the alarm disappear.
Replace the diode.
Please contact the after services department
2. Unscrew and remove the 90° Connector from the Emergency valve.
By the multimeter in ohm setting, check if the solenoid is not in short
circuit.
The value of impedance depending by the voltage of the system.
Voltage Ohm
12V 7,3Ω
24V 28,8Ω
7,3
Emergency valve
OL
1
YVH1
2
If the multimeter show the short circuit valve the reason is in to the
cable that could be damage somewhere.
Please contact the after services department
4. If the test above have a positive result the problem is related
to the Load limiting device.
Press enter button (long time, three seconds) in to the load limiting
device. The display will show
CHECK MENU
INPUTS MENU
Inputs
KEY - KEY +
Outputs
OUT1: ON/OFF
KEY - KEY +
Outputs
YELLOW LAMP:ON/OFF
KEY - KEY +
Outputs
INDEX
KEY RED LAMP: ON/OFF
LONG
KEY - KEY +
Outputs
RADIO S1: ON/OFF
KEY - KEY +
Outputs
RADIO S2: ON/OFF
KEY - KEY +
Outputs
BUZZER: ON/OFF
KEY - KEY +
Outputs KEY +
MX POWER: ON/OFF
Main
part
Wiring
extension
Step 1 wiring test
The wiring related with the pressure transducer line is
XS2 see sketch above could it be damage or interrupt
somewhere.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
29 42 43 56
1 14 15 28
The multimeter must show the vale O.L that means no short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS2 connection and move to test like
following sketch:
Main wiring short circuit test
Main
part
Wiring
extension
Wiring
extension
Step 1 wiring test
The wiring related with the pressure transducer line is
XS10 see sketch above could it be damage or interrupt
somewhere.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
29 42 43 56
1 14 15 28
The multimeter must show the vale O.L that means no short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS10 connection and move to test like
following sketch:
Main wiring short circuit test
The wiring related with the WINCH line is XS7 see sketch
above could it be damage or interrupt somewhere.
29 42 43 56
1 14 15 28
- Multimeter
Extensometer DINAMIC OIL sensor test
Trouble shooting material necessary
- Multimeter
TEST PROCEDURE
Power on the system.
Open the aluminum box close to the winch.
Step 1: No load on the winch
By the multimeter check the voltage between the
extensometer wires YELLOW and WHITE
Step 2: Max winch capacity (depend by the model)
By the multimeter check the voltage between the
extensometer wires YELLOW and WHITE
The voltage different between step 1 and step 2 must
be included from 2mV to 7mV.
Please pay attention at the voltage range that the
display show ( normally the mV range is on the
right top of display)
If the test result is different from the above value the
extensometer is in fault.
Please contact after sales department to have a spare
part information.
Step test
Multimeter in ohm configuration
1 TEST PIN 1 e PIN 2
2 TEST PIN 2 e PIN 3
3 TEST PIN 2 e PIN 4
4 TEST PIN 2 e PIN 5
Step test
Multimeter in ohm configuration
1 TEST PIN 1 e PIN 2
2 TEST PIN 2 e PIN 3
3 TEST PIN 2 e PIN 4
4 TEST PIN 2 e PIN 5
TEST
PIN 1 and PIN 2
THE VALUE MUST BE CLOSE TO MEGA ohm
PIN 2 and PIN 5
THE VALUE MUST BE CLOSE TO KILO ohm
PIN 2 and PIN 3
THE VALUE MUST BE CLOSE TO KILO ohm
PIN 2 and PIN 4
THE VALUE MUST BE CLOSE TO KILO ohm
TEST
PIN 1 and PIN 2
THE VALUE MUST BE CLOSE TO MEGA ohm
PIN 2 and PIN 5
THE VALUE MUST BE CLOSE TO KILO ohm
PIN 2 and PIN 3
THE VALUE MUST BE CLOSE TO KILO ohm
PIN 2 and PIN 4
THE VALUE MUST BE CLOSE TO KILO ohm
If short circuit is present in one of this test you must replace
the wire in trouble with a new one.
Please contact after sales department to have a spare part
information.
After cable replacement start the crane operation.
Otherwise move to the step 2
29 42 43 56
1 14 15 28
1 2
Due to:
1. Cable damage in short circuit
2. Load limiting device fault
3. Bubble sensor broken in short circuit
See the wiring structure in to the alarm 50
description
Step 1 wiring test
The wiring related with the bubble sensor line is XS3
see sketch above could it be damage and in short circuit
some where.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
The multimeter must show the vale O.L that means no short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS10 connection and move to test like
following sketch:
Main wiring short circuit test
29 42 43 56
1 14 15 28
Extension wiring
continuity test Pin 1 and pin 1
Than
Pin 2 and pin2
Pin3 and pin 3
Pin 4 and pin 4
If continuity is not present in one of this three tests you must
replace the wire in trouble.
Please contact after sales department to have a spare part
information.
After cable replacement start the crane operation.
1 2
Due to:
1. Cable damage in short circuit
2. Load limiting device fault
3. Bubble sensor broken in short circuit
See the wiring structure in to the alarm 52
chapter
Step 1 wiring test
The wiring related with the bubble sensor line is XS11
see sketch above could it be damage and in short circuit
some where.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
The multimeter must show the vale O.L that means no short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS11 connection and move to test like
following sketch:
Main wiring short circuit test
29 42 43 56
1 14 15 28
Go to the step n 3
Power supply bubble sensor line test
If the two step 1 and step 2 resulting OK the component that make the
alarm on is the bubble sensor and must be replaced.
The bubble sensor located in the second boom of the crane .
Replace the sensor and repositioning the new one in the same position of
the old one to avoid any safety problem during the overload
situation.
Due to:
1. Cable damage in short circuit
2. Load limiting device fault
3. Bubble sensor broken in short circuit
See the wiring structure in to the alarm 54
chapter
Step 1 wiring test
The wiring related with the bubble sensor line is XS3
see sketch above could it be damage and in short circuit
some where.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
The multimeter must show the vale O.L that means NO short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS 3 connection and move to test like
following sketch:
Main wiring short circuit test
Go to the step n 3
Step 3 bubble sensor
29 42 43 56
1 14 15 28
Go to the step n 3
Power supply bubble sensor line test
Due to:
1. Cable damage in short circuit
2. Load limiting device fault
3. Bubble sensor broken in short circuit
See the wiring structure in to the alarm 56
chapter
Step 1 wiring test
The wiring related with the bubble sensor line is XS11
see sketch above could it be damage and in short circuit
some where.
Trouble shooting material necessary to solve the
problem:
- Digital multimeter
The multimeter must show the vale O.L that means NO short
circuit in to the wiring line, than move to step number two.
Otherwise disconnect XS 11 connection and move to test like
following sketch:
Main wiring short circuit test
Go to the step n 3
Step 3 bubble sensor
DANFOSS COMPONENT
Electro-Hydraulic
actuator
ELECTRICAL CONNECTION
HAWE COMPONENT
Electro-Hydraulic
actuator
ELECTRICAL CONNECTION
Keyboard
Feeder
Due to:
1. Cable damage in open circuit
2. No power supply
3. Load limiting device fault
4 .Electro Hydraulic actuator broken
1. TAKE OFF FROM THE BLACK PROTECTION FROM THE LOAD
LIMITING DEVICE SIDE
ELECTRICAL CONNECTION IN TO
THE CONTROL VALVE
Load limiting
device
Alarm n. : 60
% 0
M01
1
M02
USING A SREWDRIVER AS THE PICTURE LIFT UP THE PURPLE
LOCKING2 AND PULL OUT THE CONNECTOR
M01
2
M02
1
PIN4
CHASSIS
-CHECK THE POWER SUPPLY IN TO THE CONNECTOR PIN4
KEPP PRESSED THE LOAD LIMITING DEVICE RESET BUTTON (DUE
TO THE ALARM LOAD LIMITING DEVICE CUT OFF THE POWER
SUPPLY TO THE ELECTRO HYDRAULIC ACTUATOR) SEE THE
SHETCH ABOWE PART 1 THE MULTIMETER MUS SHOW THE VALUE
LIKE A BATTERY VOTAGE IF POWER IS PRESENT
-CHECK THE NEGATIVE IN TO THE CONNECTOR PIN3
CONNECT THE MULTIMETER IN VOLT CONFIGURATION RED TEST PIN IN TO
PIN 4 AND BLACK TEST PIN IN TO THE PIN 3.
KEPP PRESSED THE RESET BUTTON IN TO THE LOAD LIMITING DEVICE
THE MULTIMETER SHOW THE VALUE LIKE A BATTERY VOTAGE IF
NEGATIVE IS PRESENT
-CHECK THE CONTINUITY LINE IN TO THE WIRING
SEE THE SHETCH ABOVE PART 2 AND FOLLOWING THE STEP
2 44 3 CHASSIS
SIMPLE CRANE
MEANS
DUE TO
->0<-
25%
ENTER KEY
LONG
CHECK MENU
INPUT
ENTER KEY
SHORT
• CHECK MENU INPUT
• IN THIS AREA ALL THE INPUT ARE
MONITORIZED IN REAL TIME
• M = MOVEMENT
• 1 = MOVEMENT NUMBER
• A = DIRECTION LEVER
• B = DIRECTION LEVER
DIR B
DIR A
PRESS THE LOAD LIMITING DEVICE RESET KEY BUTTON
AND KEEP PRESSED DURING FOLLOWING OPERATION.
USE KEY + AND – TO SCROLL DOWN ALL THE INPUT AND
CHECK WHICH ONE IS NOT IN ON STATUS.
KEY - KEY +
Inputs Inputs
M1 A: ON M5 A: ON
Inputs Inputs
M1 B: ON M5 B: ON
KEY - KEY +
Inputs Inputs
M2 A: ON M6 A: ON
KEY - KEY +
KEY - KEY +
Inputs Inputs
M2 B: ON M6 B: ON
Inputs Inputs
M3 A: ON M7 A: ON
Inputs Inputs
M3 B: ON M7 B: ON
KEY - KEY + KEY - KEY +
Inputs Inputs
M4 A: ON M8 A: ON
Inputs Inputs
M4 B: ON M8 B: ON
KEY - KEY +
REFERT TO THE FOLLOWING CHART CONTROLL IN
TO THE CHECK INPUT MENU THE STATUS OF THE
INPUT.
INPUT STATUS ON OK
INPUT STATUS OFF FAULT
DEPENDING BY THE CRANE CONFIGURATION YOU
WILL FIND ONE OR MORE OF THE INPUT IN OFF
STATUS
1. TAKE OFF FROM THE BLACK PROTECTION FROM THE LOAD
LIMITING DEVICE SIDE
ELECTRICAL CONNECTION IN TO
THE CONTROL VALVE
Load limiting
device
M01
USING A SREWDRIVER
1 AS THE PICTURE LIFT UP THE PURPLE
LOCKING AND PULL OUT THE CONNECTOR
M02
2
PRESS RESET BUTTON AND MOVE THE CRANE BY RADIO
REMOTE CONTROL UNTILL THE ALARM COME ON AGAIN
THAN REPEAT THE CHECK INPUT CONTROLL OPERATION
AS BEFORE AND VERIFY :
1.IF INPUT IN OFF IS THE SAME THAN BEFORE THE
PROBLEM IS IN TO THE CABLE:
BROKEN CABLE BEETWEN THE CONNECTOR TO LOAD
LIMITING DEVICE PIN (SEE THE DIAGAM AND CHEK THE
CONTINUITY BY MULTIMETER SEE CHAPTER ALARM 60)
POSITIVE AND NEGATIVE JUNCTION ARE LOCATED IN TO THE
INTERNAL WIRING POSITION, AND TO REPARE IT MEANS OPEN
ALL THE WIRING COVER (TERMO HETERING) AND IS NOT
POSSIBLE REPLACE WITH A NEW ONE.
REPLACE THE WIRING IS THE FASTER AND SAFETY SOLUTION.