Micrologic
Control units
5.0 P, 6.0 P and 7.0 P
User manual
09/2009
Micrologic control units Contents
5.0 P, 6.0 P and 7.0 P
Discovering Micrologic P 4
Identification 4
Presentation 5
Setting procedure 6
Setting Micrologic 5.0 P using the dials 8
Setting Micrologic 6.0 P using the dials 9
Setting Micrologic 7.0 Pusing the dials 10
Selecting the type of neutral protection 11
Main menus 12
Metering 14
History, maintenance and setup 16
Protection 18
Overview of functions 20
Current protection 20
Voltage protection 26
Other protection 27
Load shedding and reconnection 28
Measurements 29
Alarms 31
Optional M2C and M6C contacts 32
Event histories 33
Leds and display screens 34
COM communications option 36
Setup 38
Setting up the optional M2C / M6C contacts 38
Setting up the Micrologic control unit 40
Setting up the metering functions 43
Setting up the COM communications option 46
Protection settings 48
Fine adjustment of the long-time I2t, short-time and
Instantaneous settings using the keypad 48
Fine adjustment of the long-time Idmtl, short-time and
instantaneous settings using the keypad 49
Fine adjustment of the ground-fault and earth-leakage
protection setting using the keypad 50
Setting the neutral protection 51
Setting the I t , I unbal, I max, U min, U max, U unbal, rP max,
F min, F max, and phase-rotation protection functions
using the keypad 52
Setting load shedding / reconnection 54
Metering 56
Current measurements 56
Voltage measurements 59
Power measurements 61
Energy measurements 63
Frequency measurements 64
Maintenance 66
Resetting fault indications 66
Viewing the event histories 67
Operation counter and contact-wear indicator 68
Checking/replacing the battery 69
Tests 70
04443726AA - 09/2009
Micrologic control units Contents
5.0 P, 6.0 P and 7.0 P
Technical appendix 72
Tripping curves 72
Voltage measurements 74
Zone selective interlocking (ZSI) 76
Power supply 77
Changing the long-time rating plug 79
Thermal memory 80
Data available via the COM communications option 81
Threshold and time-delay settings 82
Other settings 85
Measurement setting ranges and accuracy 86
Power factor sign conventions 87
Index 88
04443726AA - 09/2009
04443726AA - 09/2009
Discovering Micrologic P Identification
E60230A
DB119909
Micrologic 5.0 P
0 Ir Isd Ii I
Selective protection + Idmtl
long time
Ir .8 tr 8
alarm
.7 .9 (s) 4 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
Micrologic 5.0 P
E60483A
Micrologic 6.0 P
Selective protection + Idmtl + ground-fault protection,
power measurements and additional protection
X t t
E60232A
DB119909
DB119911
Micrologic 6.0 P
Y 4260A
N 1 2 3
Idmtl
2
I t on
Z
100
2
50 I t off
0
X: type of protection
b 2 for basic protection 0 Ir Isd Ii I 0 Ig I
b 5 for selective protection
Ground-fault protection
long time
Y: version number
A J .1 2
0
on I t off
ground fault
Micrologic 7.0 P
Z: type of measurement Selective protection + Idmtl + earth-leakage protection,
b A for "ammeter" power measurements and additional protection
b P for "power meter"
t
E60234A
DB119913
DB119909
50
0 Ir Isd Ii I 0 I∆n I
Ir
.6
.7
long time
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm
Selective protection Earth-leakage protection
+ Idmtl
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
earth leakage
04443726AA - 09/2009
Discovering Micrologic P Presentation
1 top fastener
E60236A
E60235B
1
2 terminal block for external connections
3 housing for battery 2
4 screw for long-time rating plug 5.0P
logic
5 long-time rating plug Micro
alarm
time 8 12
Indications
long tr
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 6 Ir
.5 1 at
.4 x In
8
12 LED indicating long-time tripping 4
13 LED indicating short-time or
instantaneous tripping 7 5
14 LED indicating ground-fault or 10
6
earth-leakage tripping 11
15 LED indicating additional-protection or
auto-protection tripping
E60237A
E60238A
16 graphics display Micrologic 5.0 P 18 19 20
17 button for reset of fault-trip LED reset 12 17
and battery test
13
14
Navigation 15 4260A
N 1 2 3
18 access button to the "Metering" menu (1) 16
19 access button to the "History, maintenance 21 22 23
100
and setup" menu (1)
20 access button to the "Protection" menu (1)
21 button used to scroll down or reduce 50
the displayed value
22 button used to scroll up or increase
the displayed value 0
23 button used to select or confirm a choice
E60240A
4 .4 .4 .3 6 8 10 4 (s) .4 .4 .3 6 8 10
28 instantaneous pickup Ii
(s) 3 5
3 5
2.5 .3 .2 2.5 6 .3 .2 4 12
26
6 4 12
28 26 .2 .1 28
29 ground-fault pickup Ig 2
1.5 10
8 .2
.1 2
0
.1 3
2
15
off
2
1.5 10
8
.1 2
0
3
2
15
off
30 ground-fault tripping delay tg 27 x Ir on I t off x In 27 x Ir on I t off x In
setting delay setting delay
test 34
31 earth-leakage pickup I∆n Ig
E
tg
(s) .4 .4 .3
D F
32 earth-leakage tripping delay ∆t 29
C G .3 .2
earth-leakage protection
35 test connector
I∆n
setting
∆t
delay
test 34
(A) 5 (ms)
3 7 230 350
2 10
31 1 20
140
35
.5 30 60 800
32 earth leakage
04443726AA - 09/2009
Discovering Micrologic P Setting procedure
DB119915
DB119914
circuits, ground faults and earth leakage.
b If the set thresholds are overrun, these protection Micro
logic
5.0
Micro
logic
5.0
b Open the protective b Make the necessary settings using the dials
cover. b The screen automatically displays the relevant curve
b Check the set value on the screen, in absolute value
in amperes (A) and in seconds (s).
È60252B
used for fine adjustments of the settings made using
leakage. The value previously set using a dial the dials.
automatically becomes the maximum value for the b All the settings not available via the dials are made in Micro
logic
5.0
04443726AA - 09/2009
Discovering Micrologic P Setting procedure
With the protective cover closed, it is not possible to set View the settings and measurements
the protection functions. However, it is possible to set
DB119916
E60254B
metering functions and alarms, as well as view all
measurements, settings and histories. 5.0
logic logic
5.0
Micro Micro
Caution!
DB119917
04443726AA - 09/2009
Discovering Micrologic P Setting Micrologic 5.0 P
using the dials
DB119919
long time
Ir .8
.6
.7 .9
.95
Ir = 0.5 x 2000 = 1000 A
.5 .98
.4 1
Isd = 2 x 1000 = 2000 A
x In
short time instantaneous Ii = 2 x 2000 = 4000 A
Isd Ii
3
4
5 6 8 10
2.5 6 4 12
2 8 3 15
1 1.5 10 2 off
x Ir x In
setting
In 2000 A
A
2000
In =
See pages 22 and 24 for selection of the setting Set the time delays
ranges.
tr = 1 s
DB119910
long time
tr 8
(s) 4 12
2 16
1 20
.5 24
tsd = 0.2 s
@ 6 Ir
short time
tsd
(s) .4 .4 .3
.3 .2
.2 .1
.1 2 0
on I t off
delay
DB119921
DB119922
DB119923
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
04443726AA - 09/2009
Discovering Micrologic P Setting Micrologic 6.0 P
using the dials
DB119924
long time
DB119918
Ir .8
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
Isd
short time
Ii
instantaneous
Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3
1.5 10 2
15
off
Ii = 2 x 2000 = 4000 A
1 x Ir x In
setting
Ig
E
B Ig = 640 A
D F
In 2000 A C G
A
B H
2000
In =
A J
ground fault
See pages 22 to 26 for selection of the setting ranges. Set the time delays
DB119925
long time tr = 1 s
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
short time
tsd
tsd = 0.2 s
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay tg = 0.2 s
tg
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
ground fault
DB119921
DB119922
DB119923
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
t t
DB119926
t t
DB119927
DB119928
DB119929
Ig Ig
tg tg
0 I 0 I 0 I 0 I
Ig: ground-fault pickup tg: ground-fault tripping delay
04443726AA - 09/2009
Discovering Micrologic P Setting Micrologic 7.0 P
using the dials
DB119930
long time
DB119918
Ir .8
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
Isd
short time
Ii
instantaneous
Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3
1.5 10 2
15
off
Ii = 2 x 2000 = 4000 A
1 x Ir x In
setting
I∆n
(A) 5
I∆n = 1 A
3 7
2 10
In 2000 A 1 20
In =
2000
A
.5 30
earth leakage
See pages 22 to 26 for selection of the setting ranges. Set the time delays
tr = 1 s
DB119931
long time
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
tsd = 0.2 s
E60153A
short time
tsd
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay ∆t = 140 ms
∆t
(ms)
230 350
140
60 800
earth leakage
t t t
DB119921
DB119923
DB119922
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
t t
DB119932
DB119933
I∆n
∆t
0 I 0 I
I∆n: earth-leakage pickup ∆t: earth-leakage tripping
delay
10 04443726AA - 09/2009
Discovering Micrologic P Selecting the type of neutral
protection
3D+N
/2 On four-pole circuit breakers, it is possible to select the type of neutral protection for
4P 4D
4P 3D
the fourth pole using the three-position dial on the circuit breaker:
b no neutral protection 4P 3D
b half neutral protection 3D + N/2
b full neutral protection 4P 4D
Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.
04443726AA - 09/2009 11
Discovering Micrologic P Main menus
The Micrologic P control unit offers access to the main screen and three menus:
b the main screen displaying the continuous measurement of the phase currents (I1,
I2, I3) and the neutral current (IN), if it exists
b the "Metering" menu
b the "History, maintenance and setup" menu
b the "Protection" menu.
Main screen
As long as no functions are activated, Micrologic P
E60101A
4260A control units display in real time the current on the most
heavily loaded phase.
The number for that phase is presented in a square.
1 2 3
The current in the neutral is displayed if the neutral CT
is set as internal or external (see "Ineutral (A)" settings
100 in the "Current protection" menu).
50
When a menu button is pressed, a presentation screen "Metering", "History, maintenance and setup" and
is displayed and the green LED on the button goes ON.
"Protection" menus
b "Metering" menu
I (A) screen
U
screen
(V) b whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
P (kW)
few minutes
b the LED goes OFF on exiting the menu.
E (kWh)
F (Hz)
12 04443726AA - 09/2009
Discovering Micrologic P Main menus
E71711A
Event screen
history
v press the button to return to the previous
Contacts screen
M2C / M6C v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Micrologic few minutes
setup v the LED goes OFF on exiting the menu.
Metering
setup
Com.
setup
b "Protection" menu
Current screen
protection
v press the button to return to the previous
Voltage screen
protection v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Other few minutes
protection v the LED goes OFF on exiting the menu.
Load
shedding I
Load
shedding P
b Saving settings
When a setting is made in any of the three menus, the
E71657A
no
yes
04443726AA - 09/2009 13
Discovering Micrologic P Metering
Current measurements
E60105A
I (A)
I (A)
access to the following sections:
U (V)
Instant.
P (kW) I1, I2, I3, IN currents
I1, I2, I3, IN (depending on the type of
E (kWh) system)
Demand
Voltage measurements
E60391A
I (A)
U (V)
access to the following sections:
Phase sequence.
Phase
rotation
14 04443726AA - 09/2009
Discovering Micrologic P Metering
Power measurements
E60392A
Power factor PF
Power
F (Hz) factor
Demand
Energy measurements
E60393A
Frequency measurement
E60394A
P (kW)
E (kWh)
F (Hz)
04443726AA - 09/2009 15
Discovering Micrologic P History, maintenance
and setup
Press the button to select the "History, maintenance and setup" menu.
Event history
E71711A
Micrologic history
setup
The last ten alarms recorded
Metering Alarm
setup history
Number of operations (opening or closing)
Com. Operation
setup counter
Wear of the circuit-breaker main contacts
Contact
wear
16 04443726AA - 09/2009
Discovering Micrologic P History, maintenance
and setup
Micrologic setup
E71714A
Metering setup
E71715A
Event
history access to the following sections:
Metering
Contacts setup
M2C / M6C b 3 phases, 3 wires, 3 CTs: method using
System
Micrologic type
two wattmeters
setup b 3 phases, 4 wires, 3 CTs: method using
three wattmeters
Metering b 3 phases, 4 wires, 4 CTs: method using
setup three wattmeters with measurement
of the neutral current.
Com. Current Selection of the calculation method and setting
setup demand
of the time interval for the calculation
Event
access to the following sections:
history Com.
setup
Contacts
M2C / M6C Setting of parameters for the COM communications
Com. option (address, baud rate, parity)
Micrologic parameter
setup
Authorisation of access to settings via
Metering Remote the COM communications option.
setup settings
04443726AA - 09/2009 17
Discovering Micrologic P Protection
Current protection
E71712A
Current
protection access to the following sections:
Current
Voltage protection
protection
Fine settings of the long-time I2t, short-time and
Other
protection I (A) instantaneous protection functions
Load
shedding P Fine settings of the:
I (A) b ground-fault (Micrologic 6.0 P)
b earth-leakage (Micrologic 7.0 P) protection functions
18 04443726AA - 09/2009
Discovering Micrologic P Protection
Voltage protection
E71719A
Other protection
E71720A
Current
access to the following sections:
protection Other
protection
Voltage
protection Setting of the reverse-power protection rP max
Other rPmax (W)
protection
Setting of the minimum-frequency protection F min
Load
shedding I Fmin (Hz)
Current rotation
protection
Voltage Load shedding depending on current
protection Load Access to load shedding and reconnection
protection
Load
shedding I
Load
shedding P
Current
Access to load shedding and reconnection
protection Load
Voltage
shedding P depending on power
protection
Other
protection
Load
shedding I
Load
shedding P
04443726AA - 09/2009 19
Overview of functions Current protection
I2t long-time protection
For the default values, the setting ranges, increment The long-time protection function protects cables against overloads. This function is
steps and setting accuracies, see the technical based on true rms measurements.
appendix. It is possible to select either I2t long-time protection or Idmtl long-time protection.
Thermal memory
b The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise in the cables.
b The thermal memory assumes a cable cooling time of approximately 15 minutes.
20 04443726AA - 09/2009
Overview of functions Current protection
Idmtl long-time protection
Idmtl Protection
Long-time current setting Ir and Idmtl tripping delay tr
Micrologic control unit Accuracy 5.0 P, 6.0 P and 7.0 P
Current setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
tripping between 1.05 and 1.20 Ir other ranges or disable by changing rating plug
Time setting 0.5 1 2 4 8 12 16 20 24
DT
Time delay (s) tr at 1.5 x Ir 0 to -20% 0.53 1 2 4 8 12 16 20 24
tr at 6 x Ir 0 to -20% 0.53 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.53 1 2 4 8 12 16 20 24
tr at 10 x Ir 0 to -20% 0.53 1 2 4 8 12 16 20 24
SIT
Time delay (s) tr at 1.5 x Ir 0 to -30% 1.9 3.8 7.6 15.2 30.4 45.5 60.7 75.8 91
tr at 6 x Ir 0 to -20% 0.5 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.7 (1) 0.88 1.77 3.54 7.08 10.6 14.16 17.7 21.2
tr at 10 x Ir 0 to -20% 0.7 (2) 0.8 1.43 2.86 5.73 8.59 11.46 14.33 17.19
VIT
Time delay (s) tr at 1.5 x Ir 0 to -30% 3.6 7.2 14.4 28.8 57.7 86.5 115.4 144.2 173.1
tr at 6 x Ir 0 to -20% 0.5 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.7 (1) 0.81 1.63 3.26 6.52 9.8 13.1 16.34 19.61
tr at 10 x Ir 0 to -20% 0.7 (2) 0.75 1.14 2.28 4.57 6.86 9.13 11.42 13.70
EIT
Time delay (s) tr at 1.5 x Ir 0 to -30% 12.5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0 to -20% 0.7 (1) 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
tr at 10 x Ir 0 to -20% 0.7 (2) 0.7 (1) 0.7 (1) 1.41 2.82 4.24 5.45 7.06 8.48
HVF
Time delay (s) tr at 1.5 x Ir 0 to -30% 164.5 329 658 1316 2632 3950 5265 6581 7900
tr at 6 x Ir 0 to -20% 0.7 (1) 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.7 (2) 0.7 (1) 1.1 (1) 1.42 3.85 5.78 7.71 9.64 11.57
tr at 10 x Ir 0 to -20% 0.7 (2) 0.7 (2) 0.7 (1) 0.7 (1) 1.02 1.53 2.04 2.56 3.07
04443726AA - 09/2009 21
Overview of functions Current protection
Short-time and instantaneous protection
For the default values, the setting ranges, increment Short-time protection
steps and setting accuracies, see the technical b The short-time protection function protects the distribution system against
appendix. impedant short-circuits
b The short-time tripping delay and the I2t ON and I2t OFF options can be used to
ensure discrimination with a downstream circuit breaker
b This function carries out true rms measurements.
For the characteristics and external wiring of the zone b Zone selective interlocking (ZSI)
selective interlocking function, see the technical The short-time and ground-fault protection functions enable time discrimination by
appendix on "Zone selective interlocking". delaying the upstream devices to provide the downstream devices the time required
to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.
b Intermittent faults are taken into account by Micrologic P and may lead to shorter
tripping times than those set.
If the "without long-time protection" plug is used and the long-time protection function
is disabled, the short-time pickup Isd is automatically multiplied by In instead of Ir as
is the standard case.
Instantaneous protection
b The instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable. The tripping order is sent to the circuit
breaker as soon as current exceeds the set value, with a fixed time delay of 20
milliseconds.
b This function carries out true rms measurements.
Instantaneous pickup Ii
22 04443726AA - 09/2009
Overview of functions Current protection
Neutral protection
For the default values, the setting ranges, increment Three-pole circuit breakers
steps and setting accuracies, see the technical Protection of the neutral is possible on a three-pole circuit breaker by connecting an
appendix. external sensor.
Settings are made using the and buttons on the control unit.
The and buttons on the control unit may then be used for a more precise
setting. The dial setting constitutes the upper limit for adjustments using the keypad.
04443726AA - 09/2009 23
Overview of functions Current protection
Ground-fault and earth-leakage
protection
For the default values, the setting ranges, increment Ground-fault protection on Micrologic 6.0 P
steps and setting accuracies, see the technical b An ground fault in the protection conductors can provoke local temperature rise at
appendix. the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
b There are two types of ground-fault protection.
Type Description
Residual b The function determines the zero-phase sequence current, i.
e. the vector sum of the phase and neutral currents (depending
on the type of installation)
Source Ground Return b Using a special external sensor, this function directly
measures the fault current returning to the transformer via the
earth cable
b It detects faults both upstream and downstream of the circuit
breaker
b The maximum distance between the sensor and the circuit
breaker is ten metres.
24 04443726AA - 09/2009
Overview of functions Current protection
I t Alarm, current unbalance, maximum
current
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. Protection tripped by a maximum value
DB119995
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
I t Alarm
b The alarm function is tripped by the rms value of an earth-leakage current
b This alarm signals an earth-leakage current under the pickup value and does not
produce circuit-breaker tripping.
I b From:
DB119996
E max
v I avg is the average value of the rms currents of the
I avg three phases
I avg = I1 + I2 + I3
3
v E max is the maximum difference between the
0 I1 I2 I3
current of each phase and I avg
b Micrologic P uses the two values above to calculate
the current unbalance:
E max
I unbal =
I avg
Note:
IN max protection does not take into account the neutral-protection setting (N, N/2, 1.6xN, OFF).
04443726AA - 09/2009 25
Overview of functions Voltage protection
Minimum voltage, maximum voltage,
voltage unbalance
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. protection tripped protection tripped
by a minimum value by a maximum value
t t
DB119946
DB119997
1 3
3 1
2 4
4 2
0 U min 0 U max
U unbal.
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
If the voltage protection functions are activated and the Minimum-voltage protection U min
voltage measurement inputs are still energised, it is b This function calculates the minimum rms value of the three phase-to-phase
impossible to reset and close the circuit breaker. voltages
b Protection is activated when at least one of the three phase-to-phase voltages
(U12, U23, U31) is below the threshold set by the user
b This protection function does not detect phase failure.
U b From:
DB119998
26 04443726AA - 09/2009
Overview of functions Other protection
Reverse power, min. frequency,
max. frequency, phase rotation
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. protection tripped protection tripped
by a minimum value by a maximum value
t t
DB119949
DB119950
1 3
3 1
2 4
4 2
0 F min 0 F max
rP max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
Note:
The direction of flow is set by the user in the "Power sign" section of the "Micrologic setup" menu
under "History, maintenance and settings".
b + corresponds to the normal direction of flow, i.e. from the top terminals on the circuit breaker
to the bottom terminals
b - is the opposite.
If the voltage protection functions are activated and the Minimum and maximum-frequency protection F min.
voltage measurement inputs are still energised, it is
impossible to reset and close the circuit breaker. and F max
These functions monitor the value of the frequency on the distribution system.
Phase-rotation alarm
This alarm is activated if two of the three phases are inverted.
Note:
The alarm is activated following a fixed 300-millisecond time delay. If one of the phases is
absent, the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot be activated.
04443726AA - 09/2009 27
Overview of functions Load shedding
and reconnection
For the pickup and dropout thresholds and time delays, Load shedding and reconnection depending on current
see the technical appendix. The pickup curve for load shedding and reconnection depending on current is
parallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plug is
installed, the load shedding/reconnection function based on current cannot be
activated.
b I2t protection: the neutral is taken into account
b Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarm
linked to an M2C or M6C contact (disconnection and reconnection of non-priority
loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
t
DB119999
Long-time
protection
curve
3
1
4
0 I
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
t
DB119952
3
1
4
2
0 P
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
28 04443726AA - 09/2009
Overview of functions Measurements
Current and voltage
Demand current
b Display of the demand current on phases I1, I2, I3 and the neutral IN (depending
on the type of distribution system)
b Selection of the demand calculation method
b Display of the interval over which the value is calculated
b The maximum demand values are displayed and stored in memory
b The stored maximums can be reset at any time.
Note:
The calculation method, the type of calculation window (fixed or sliding) and its duration may be
set in the "Metering setup" menu under "History, maintenance and setup".
Average voltage
Average Uavg of the instantaneous voltages between phases U12, U23 and U31.
Phase rotation
Displays the phase sequence.
04443726AA - 09/2009 29
Overview of functions Measurements
Power, energy and frequency
For the setting ranges and measurement accuracies, Instantaneous power and power factor
see the technical appendix. Micrologic P offers a number of different measurements.
b Total power measurements:
v instantaneous active power P in kW
v instantaneous reactive power Q in kvar
v instantaneous apparent power S in kVA
b Measurement of the power factor PF.
Demand power
b Display of the demand values for the active power P, reactive power Q and
apparent power S
b Selection of the demand calculation method
b Display of the interval over which the value is calculated
b The maximum demand values are displayed and stored in memory
b The stored maximums can be reset at at any time.
Note:
b the calculation method, the type of calculation window (fixed or sliding) and its duration may
be set in the "Metering setup" menu under "History, maintenance and setup".
b the synchronisation function (Synchro.Com) is available only with the COM communication
option; with this function, the demand power is determined on the basis of a signal synchronised
by the communication module.
b these settings apply to all demand powers (active power P, reactive power Q and apparent
power S). If the settings are modified, the demand values are systematically recalculated.
Energy
Micrologic P offers a number of different measurements:
b Total energy:
v total active energy E.P in kWh
v total reactive energy E.Q in kvarh
v total apparent energy E.S in kVAh
b Energy consumed (Energy in), positively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
b Energy supplied (Energy out), negatively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
b Energy values can be reset.
Note:
b the Energy in and Energy out values are incremented according to the power sign set in the
"Metering setup" menu under "History, maintenance and setup".
b as standard, the total calculated energy values are "absolute total values".
They represent the sum of the energy in and out values:
v EP = Σ EP in + Σ EP out
v EQ = Σ EQ in + Σ EQ out
b as an option (access exclusively via the COM communications option), energy can be
calculated algebraically:
v EP = Σ EP in - Σ EP out
v EQ = Σ EQ in - Σ EQ out
These values are called "signed" energies.
Frequency
The frequency of the distribution system is displayed in Hz.
30 04443726AA - 09/2009
Overview of functions Alarms
For information on the communications option and the b An alarm may be viewed using:
portable test kit, see the respective user guides. v the "Alarm history" menu
v the COM communications option
v the portable test kit.
b The commands in the "Protection" menu are used to attribute a specific operating
mode to each of the protection functions:
v OFF: protection disabled
v Alarm: the function issues an alarm, but does not trip the circuit breaker
v Trip + Alarm: the function issues an alarm and trips the circuit breaker.
b The protection functions against overloads (long time), short circuits (short time
and instantaneous) and ground faults (ground-fault and earth-leakage currents)
automatically result in tripping and cannot be deactivated (Trip mode only).
b The "I t Alarm" and phase rotation alarms can be set exclusively to OFF or Alarm
mode.
b The other protection functions for current, voltage, power and frequency may be
set to any of the three modes, OFF, Alarm or Trip + Alarm.
b The load shedding and reconnection function may be set to ON or OFF.
b The resettable alarms linked to device tripping are activated when the Ir, Isd/Ii
or I t thresholds are overrun.
The Ir alarm is reset one second after tripping. The Isd/Ii and t alarms are reset by
pressing the button.
Isd / li b
Pickup T1 It b
b Delayed alarms are activated when the pickup and dropout thresholds are overrun
and the corresponding time delays have expired.
Dropout T2
Current protection Off Alarm Trip + Alarm
I t Alarm b b
I unbal b b b
Ir, Isd, Ii, I alarms
I 1 max b b b
I 2 max b b b
Other alarms
I 3 max b b b
I N max b b b
Identical pickup and dropout thresholds Voltage protection Off Alarm Trip + Alarm
U min b b b
DB120001
U max b b b
U unbal b b b
Pickup / T1 T2
Other protection Off Alarm Trip + Alarm
Dropout
rP max b b b
F min b b b
F max b b b
Phase rotation b b
Ir, Isd, Ii, I alarms Shedding/reconnection Off On
current I b b
Other alarms
power P b b
b History logging
v Alarm mode: as soon as a given protection threshold is overrun, an alarm is
recorded in the "Alarm history"
v Trip mode: as soon as a given protection threshold is overrun, the circuit breaker
trips and the fault is recorded in the "Trip history".
b The "Protection setup" menu under "History, maintenance and setup" is used to
enable or disable the Trip mode that is displayed in the protection-setting screens.
On leaving the factory, the protection functions are set to Alarm mode.
b The "M2C / M6C contacts" menu under "History, maintenance and setup" is used
to link an M2C or M6C contact to an alarm. M2C and M6C contacts may not be used
together. They require a 24 V external power supply.
b The COM communications module can be used to transmit alarms to a supervisor.
04443726AA - 09/2009 31
Overview of functions Optional M2C and M6C contacts
An alarm is issued if the Alarm or the Trip + Alarm mode b Available types of contacts:
was set for the given protection function. v M2C: up to two contacts maximum, S1 and S2
v M6C: up to six contacts maximum, S1 to S6.
Caution!
b Current protection: b Voltage protection: b Other protection:
The M2C and M6C contacts require an auxiliary power
v Ir v U min v F min
supply. See the "Power supply" section in the technical
v Isd v U max v F max
appendix.
v Ii v U unbal. v rP max
v It v phase rotation.
v I t Alarm
v I unbal
v I1 max
v I2 max
Wiring diagram for M2C contacts.
v I3 max
v IN max.
E60492A
474
484
Ir threshold T1 tr delay
Wiring diagram for M6C contacts
T2 = 1 sec
11
17
19
21
23
25
1
5
7
9
E60491C
Ir LED Press
Internal alarm
12
14
16
18
20
22
24
2
6
8
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after pressing
Pickup
Dropout
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after T2
32 04443726AA - 09/2009
Overview of functions Event histories
Alarm history
b The alarm history is the means to display at any time the parameters measured
during the last ten alarms.
b For each alarm, the following parameters are recorded:
v alarm cause
v alarm threshold
v date
v time (hours, minutes and seconds).
Operation counter
This function is available only via the COM communications option.
b Micrologic P:
v stores and displays the total number of operations (incremented each time the
circuit breaker opens) since the initial installation of the circuit breaker
v stores and displays the total number of operations since the last reset.
Note:
If the control unit is changed, the circuit breaker must be defined again. In this case, see "Breaker
selection" in the "Micrologic setup" menu under "History, maintenance and setup".
04443726AA - 09/2009 33
Overview of functions Leds and display screens
E60444A
E60495A
Micrologic 5.0 P
Alarm
4260A
off
N 1 2 3
100
50
E71600B
Trip
22/11/1999
02:04:04
Umin 100V
Reset
by test/reset
button
34 04443726AA - 09/2009
Overview of functions Leds and display screens
b Fault-trip LEDs
b The LEDs indicate the type of fault that tripped the circuit breaker
b The LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n and
Ap LEDs)
b When activated, a LED remains ON until it is locally reset.
E60337B
E60338B
Micrologic 5.0 P Micrologic 5.0 P
E60340B
Micrologic 5.0 P Micrologic 5.0 P
self-protection built into the device) trips the circuit
breaker and turns the Ap LED on.
04443726AA - 09/2009 35
Overview of functions COM communications option
Communication options
E71748A
Digipact and ModBus are the indispensable elements when integrating Micrologic P
Chassis
in the Digivision and SMS Powerlogic installation-management systems which
communicate via the BatiBus and ModBus protocols.
External gateways are available for communication over other networks, including
COM module on ProfiBus, Ethernet, etc.
chassis (optional)
The communications option makes possible the following remote functions:
b Device identification:
v address
v device type
v control-unit type
v type of long-time rating plug
Circuit breaker
b Measurement values:
v currents
Micrologic P v voltages, frequencies, power, etc.
control unit
b Fault values:
v fault type
v interrupted current.
b Indicators:
v contact wear, counters, etc.
v maintenance register.
36 04443726AA - 09/2009
04443726AA - 09/2009 37
Setup Setting up the optional
M2C / M6C contacts
E71601A
E60146A
E60226A
type
type S2 S2
S1
S2 Ir Ir
then then
Select a contact. Select an alarm. Confirm.
E71603A
E71604A
M2C / M6C S2 S2
Setup
S1 Mode Mode
S2 latching latching
contact contact
then then
Select a contact. Select a latching mode: Confirm.
b non-latching
b latching
b time-delay
b locked to 1
b locked to 0.
38 04443726AA - 09/2009
Setup Setting up the optional
M2C / M6C contacts
S2 S2 S2
E71605A
E71606A
E71607A
Mode Mode Mode
time delay time delay time delay
then
Select the time delay. Adjust. Confirm.
Select the command Reset the contacts to 0
M2C / M6C
E60442A
Reset (- / +) Reset (- / +)
then
Reset the contacts to 0… or cancel the reset,
then confirm.
04443726AA - 09/2009 39
Setup Setting up the Micrologic
control unit
E71938B
setup
Language
Select. Confirm.
To return to English
1. Return to the main 2. Select the "History, 4. Select the "Language"
screen by pressing any of maintenance and setup" menu by moving the
the three buttons menu by pressing cursor up on the first
menu.
Confirm by pressing
or press the button 3. Select the "Micrologic
setup" menu by moving
the cursor up on the first
followed by any of the menu. Move the cursor
three buttons down on the third menu
and confirm
by pressing
E71611B
E71612B
18 : 30 : 03 18 : 30 : 03 18 : 30 : 03
40 04443726AA - 09/2009
Setup Setting up the Micrologic
control unit
E71613B
E71614B
If time is not synchronised by the supervisor via the
Date Date
communication module, a drift of up to one hour per
year may be observed.
01 / 01 / 2000 01 / 01 / 2000
Time Time
18 : 30 : 03 18 : 30 : 03
then then
Enter the year. Set the time in the same
manner.
E89322A
E89323A
setup
Breaker selection selection selection
selection Standard Standard Standard
UL IEC IEC
The circuit-breaker code is required to identify the
device and activate the contact-wear counter. Circuit breaker Circuit breaker Circuit breaker
Masterpact Masterpact Masterpact
Note this code if the control unit must be changed type type type
(example 03E7).
NT08N NT H1 NT H1
Enter this code when setting up a new control
unit on the circuit breaker.
03E7 03E7 03E7
For a new device, the code is set to zero. P Logicxxxxxx P Logicxxxxxx P Logicxxxxxx
When the main circuit-breaker contacts are replaced, then then then
this code must be reset to zero.
Select the standard. Choose and confirm. Select the circuit breaker.
E89325A
E89326A
04443726AA - 09/2009 41
Setup Setting up the Micrologic
control unit
E71642B
E71643B
E71644B
setup Power Power Power
Power
sign
sign sign sign
By default, Micrologic P uses P+ for the power flowing
from top to bottom terminals. The selected direction of
P- P+ P+
flow is valid for:
b measurement of power and the power factor
b measurement of energy
b load shedding and reconnection depending on
power.
E71625A
E71626A
setup
VT ratio
Primary Primary Primary
If the supply voltage for the control unit exceeds 690 V, 690V 690V 690V
an external voltage transformer must be installed. Secondary Secondary Secondary
To display the true voltage values, enter the 690V 690V 690V
transformation ratio between the primary and
secondary voltages of the transformer.
then then
Select either the: Enter the voltage. Go on to the next setting.
b primary voltage
b secondary voltage.
E71628A
E71629A
42 04443726AA - 09/2009
Setup Setting up the metering
functions
E71631A
E71632A
type type type
3Φ 4w 3Φ 3w 3Φ 3w
3CT 3CT 3CT
E89200C
E89201C
setup
Current
demand
demand demand demand
Calculation Calculation Calculation
Thermal method based in I2t calculation. method method
method
block
block block
thermal interval
interval interval
Window type Window type Window type
sliding sliding sliding
Interval Interval Interval
15 min 15 min 15 min
04443726AA - 09/2009 43
Setup Setting up the metering
functions
E89213C
E89214C
E89215C
Current Current Current
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
sliding sliding sliding
Interval Interval Interval
15 min 20 min 20 min
Select the command Select the calculation method for demand power
Metering
Power Power Power
E89216C
E89217C
E89218C
setup
Power demand demand demand
demand
Calculation Calculation Calculation
The synchronisation function "Synchro.Com" is method method method
available only with the COM communication option. block block
With this function, the demand power is determined on thermal block
interval interval interva
the basis of a signal synchronised by the
communication module. Window type Window type Window type
sliding sliding sliding
Thermal method based on I2t calculation.
Interval Interval Interval
Sliding window:
power demand is refreshed every 15 secondes. 15 min 15 min 15 min
Fixed window:
power demand is refreshed at the end of the time
Select. Choose between: Confirm.
interval.
b thermal
b block interval
b sync. to comms
E89220C
E89221C
44 04443726AA - 09/2009
Setup Setting up the metering
functions
Power Power
E98320A
E89222C
E89223C
Power
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
fixed fixed fixed
Interval Interval Interval
15 min 20 min 20 min
E89226B
E89227B
setup Sign Sign Sign
Sign convention convention convention
convention
See page 87 for the description of power factor sign
conventions.
04443726AA - 09/2009 45
Setup Setting up the COM
communications option
Select the command When a COM communications option is used, it is necessary to:
b set up the COM communications option
Com. b authorise remote setting of the Micrologic control unit
setup b authorise remote control of the circuit breaker.
Com.
parameter View and set up the communications option
E71723A
E71724A
Modbus Modbus
E71725A
As soon as the Digipact or ModBus communications
Modbus
option is connected, the control unit recognises it and Com Com Com
displays the type of module on the graphic screen. Address Address Address
Automatic time updates are possible only with the
ModBus system. 47 45 45
Baud-rate Baud-rate Baud-rate
9600 9600 9600
Parity Parity Parity
None None None
then
Select an existing Adjust. Confirm.
parameter.
Adjust all the other parameters for the communications option in the same manner.
DIGIPACT MODBUS
(read only) (read and set up)
Address 1 - 255 1 - 47
Baud rate 9 600 bauds
19 200 bauds
Parity Even
None
E71728A
then
Select existing setting. Choose. Confirm.
46 04443726AA - 09/2009
Setup Setting up the COM
communications option
E71729A
E71730A
E71731A
the default access code is 0000 and is requested by Remote Remote Remote
the supervisor. settings settings settings
Access Access Access
permit permit permit
Yes Yes Yes
Select the existing access Enter the first digit. Confirm and proceed in
code setting. the same manner for the
other digits.
Select the command Authorise remote control of the circuit breaker
Com.
E71732A
E71733A
E71734A
setup
Remote Remote Remote
control control control
Remote
control
04443726AA - 09/2009 47
Protection settings Fine adjustment of the long-time
I2t, short-time and Instantaneous
settings using the keypad
Select the command.
E71738A
Current I(A)
protection Trip
E60276A
E60275A
E60149A
I(A) I(A) I(A)
Trip Trip Trip
1000 A 998 A 998 A
1.0 s 1.0 s 1.0 s
then
Select a setting. Adjust the value. Confirm.
E60277A
then
Adjust the other settings Quit the setting screen. Confirm.
and confirm.
48 04443726AA - 09/2009
Protection settings Fine adjustment of the long-time
Idmtl, short-time and instantaneous
settings using the keypad
Select the command
E71739A
Current Idmtl (A)
protection
Trip
Idmtl (A) 1000 A long-time current setting Ir
long-time tripping delay tr
1.0 s
EIT Idmtl protection:
DT, SIT, VIT, EIT, HVF
2000 A short-time pickup Isd
0.2 s short-time tripping delay tsd
4000 A instantaneous pickup Ii
Idmtl (A)
E60151A
E71718A
E60278A
Idmtl (A) Idmtl (A)
Trip Trip
1000 A 1000 A
Change I(A)
1.0 s 1.0 s
settings with
Idmtl(A)? EIT VIT
2000 A 2000 A
0.2 s 0.2 s
No 4000 A 4000 A
Yes
then then
Select yes. Select a setting. Change the setting.
E71657A
E60279A
E60280A
then
Confirm. Adjust the other settings. Confirm.
04443726AA - 09/2009 49
Protection settings Fine adjustment of the ground-
fault and earth-leakage protection
setting using the keypad
Select the command
DB120019
DB120020
Current I (A) I (A)
protection
Trip Trip
I (A)
1200A threshold 1200A
then
Select a setting.
DB120023
DB120021
DB120022
I (A) I (A) I (A)
Trip Trip Trip
then
Adjust the value. Confirm. Go to the next setting.
DB120025
DB120025
50 04443726AA - 09/2009
Protection settings Setting the neutral protection
E89237B
E89238B
E89239B
protection Ineutral (A) Ineutral (A) Ineutral (A)
Ineutral (A) Neutral CT Neutral CT Neutral CT
then
Select. Choose between: Confirm.
b internal
b external
b none.
E89242B
Ineutral (A)
E89241B
Ineutral (A)
E89240B
breaker
Four-pole OFF: no neutral protection
N / 2: half neutral protection
N: full neutral protection
Neutral CT Neutral CT Neutral CT
Three-pole OFF: no neutral protection
N / 2: half neutral protection External External External
N: full neutral protection
1.6 x N: oversized neutral protection
then
Select. Choose. Confirm.
E71657A
E89242B
Ineutral (A)
Neutral CT
Do you want
External to save new
settings?
Protection no
N/2 yes
Note:
On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dial setting.
04443726AA - 09/2009 51
Setting the I , I unbal, I max, U min,
I
Protection settings
U max, U unbal, rP max, F min, F max,
and phase-rotation protection
functions using the keypad
Select the corresponding menu
E71661B
type of protection
Current
protection
operating mode
I Alarm Pick up
(Off, Alarm or Trip)
I unbal (%)
pickup threshold
pickup time delay
I1 max (A) Drop out
dropout threshold
I2 max (A) dropout time delay
E60171B
E60293B
Umin (V) Umax (V) Umax (V) Umax (V)
Umax (V) Off Alarm Alarm
Pick up Pick up Pick up
Uunbal (%) 690V 690V 690V
5.00s 5.00s 5.00s
Other
protection Drop out Drop out Drop out
690V 690V 690V
rPmax (W) 0.50s 0.50s 0.50s
Fmin (Hz)
then
Select the first setting. Choose Off or Alarm. Confirm.
Fmax (Hz)
E60292B
E89294B
Phase
rotation Umax (V) Umax (V)
Off Trip
Pick up Pick up
690V 690V
5.00s 5.00s
In trip mode, the dropout threshold is equal to the
pickup threshold. Drop out
The dropout time delay is fixed and equal to 1 second.
690V
0.50s
then
Select the first setting. Choose Trip.
52 04443726AA - 09/2009
Protection settings Setting the I , I unbal, I max, U min,
I
U max, U unbal, rP max, F min, F max,
and phase-rotation protection
functions using the keypad
E89293B
E89295B
Umax (V) Umax (V)
Trip
Do you want Pick up
to set the
690V
protection to
Trip mode? 5.00s
no
yes
then
Confirm.
For protection tripped by a maximum value, the dropout b Set the pickup and dropout thresholds and time delays
threshold is always less than or equal to the pickup
Umax (V) Umax (V) Umax (V)
E71665A
E71666A
E71667A
threshold.
then
Select the existing Adjust. Confirm.
dropout threshold setting
When all the settings have been made, quit the screen
E71668A
E71668A
E71657A
then
Set the other parameters. Quit the setting screen. Confirm
04443726AA - 09/2009 53
Protection settings Setting load
shedding / reconnection
E71673B
Load type of shedding (I or P)
Load shedding
shedding I
operating mode (On, Off)
Load
shedding P Pick up
pickup threshold
pickup time delay
Drop out
dropout threshold
dropout time delay
54 04443726AA - 09/2009
Protection settings Setting load
shedding / reconnection
E71670A
E71671A
E71672A
shedding P shedding P shedding P
Off On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
1000kW 1000kW 1000kW
10s 10s 10s
then
Select the first setting. Select: Confirm.
b Off: load shedding
disabled
b On: load shedding
enabled.
E71674A
E71675A
E71676A
Load Load Load
shedding P shedding P shedding P
On On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
980kW 985kW 985kW
10s 10s 10s
then
Select the existing Adjust. Confirm.
dropout threshold.
When all the settings have been made, quit the screen
E71677A
E71677A
E71657A
Load Load
by pressing one of the menu-access buttons.
This saves the new values. shedding P shedding P
On On
Pick up Pick up Do you want
to save new
1000kW 1000kW
settings?
3600s 3600s
Drop out Drop out
985kW 985kW
no
10s 10s yes
then
Set the other parameters. Quit the setting screen. Confim.
04443726AA - 09/2009 55
Metering Current measurements
Only the measurements for the phase (1, 2, 3) and Continuous current measurement
neutral currents are displayed on the main screen. The bargraph displays the value in amperes of the most heavily loaded phase.
E60184A
E60185A
E60187A
The neutral current is displayed if the neutral CT is set
to internal or external (see "Ineutral (A)" settings in the
"Current protection" menu).
4260A 3850A 3410A
1 2 3 1 2 3 1 2 3
100 100 100
50 50 50
0 0 0
The and buttons may be used to display the currents on the three phases.
If the operator no longer uses the buttons for a few seconds, the bargraph returns to
the display of the most heavily loaded phase.
E60189A
Instant.
I1, I2, I3, IN
I1 = 3410 A
Max I2 = 4260 A
I3 = 3850 A
IN = 200 A
I = 13 A
then
Select. View.
I inst. Imax
E60190A
E60191A
Reset ( - / + )
then
Select. View.
56 04443726AA - 09/2009
Metering Current measurements
Imax Imax
E60192A
E60191A
instant. instant.
I1 = 0A I1 = 5600 A
I2 = 0A I2 = 4800 A
I3 = 0A I3 = 4700 A
IN = 0A IN = 800 A
I = 0A I = 28 A
Reset ( - / + ) Reset ( - / + )
E71679A
Demand.
I1, I2, I3, IN 13min
I1 = 3950 A
Max I2 = 4270 A
I3 = 3890 A
IN = 340 A
then
Select. View.
04443726AA - 09/2009 57
Metering Current measurements
Demand
E71681A
E71680A
Imax
Demand
I1, I2, I3, IN
15min
I1 = 4020 A
Max
I2 = 4450 A
I3 = 4300 A
IN = 600 A
Reset ( - / +)
then
Select. View.
E71683A
Imax Imax
Demand Demand
15min 15min
I1 = 0A I1 = 4020 A
I2 = 0A I2 = 4450 A
I3 = 0A I3 = 4300 A
IN = 0A IN = 600 A
Reset ( - / +) Reset ( - / +)
58 04443726AA - 09/2009
Metering Voltage measurements
E60193A
E89257B
U (V) Uinst.
Instant.
The phase-to-neutral voltages are displayed if the U12 = 400 V
selected system type is 3-phase, 4-wire (see page 43).
Average 3Φ U23 = 404 V
U31 = 401 V
Unbal 3Φ
Phase U1N = 230 V
rotation U2N = 229 V
U3N = 233 V
then
Select. View.
Uavg.
E89258B
U (V)
Instant. 3Φ
Average 3Φ
402 V
Unbal 3Φ
Phase
rotation
then
Select. View.
U (V)
Instant.
3Φ
Average 3Φ
1%
Unbal 3Φ
Phase
rotation
then
Select. View.
04443726AA - 09/2009 59
Metering Voltage measurements
E89260A
E89261A
U (V) Phase
rotation
Instant.
Average 3Φ
Unbal 3Φ
∆Φ : 1, 2, 3
Phase
rotation
then
Select. View.
60 04443726AA - 09/2009
Metering Power measurements
E60199B
E71690A
Pinst.
Instant. P, Q, S
P (kW)
To ensure reliable power and power-factor
Power 2180
measurements, the "Power sign" and "Sign factor
convention" parameters must be set. Q (kvar)
-650
S (kVA)
2280
then
Select. View.
E71692A
Pinst. factor
P, Q, S
Power
factor 1.00
then
Select. View.
Demand
P, Q, S P (kW)
2350
Max
Q (kvar)
-820
S (kVA)
2640
then
Select. View.
04443726AA - 09/2009 61
Metering Power measurements
Pmax
E71695A
Demand
E71696B
Demand
P, Q, S P (kW)
2450
Max
Q (kvar)
-800
S (kVA)
2700
Reset (- / +)
then
Select. View.
Pmax Pmax
E71697B
E71698B
Demand Demand
P (kW) P (kW)
0 2450
Q (kvar) Q (kvar)
0 -800
S (kVA) S (kVA)
0 2700
Reset (- / +) Reset (- / +)
62 04443726AA - 09/2009
Metering Energy measurements
E71699A
E (kWh) b total energy
b energy in (positive component in the total energy)
To ensure reliable energy measurements, the "Power b energy out (negative component in the total energy).
E total
sign" and "Sign convention" parameters must be set.
E in
E out
Reset
energy
then
Select.
E total E in E out
E71700B
E71701B
E71702B
E.P (kWh) E.P (kWh) E.P (kWh)
20168 +21320 168
E.S (kVAh)
22926
View the total energy View the energy View the energy
values. in values. out values.
E71705A
E71703A
E (kWh) Reset
E total Energy To reset
energy
E in press
Are you enter
sure ?
E out
Reset
Energy No
Yes
then then
Select. Select yes or no. If yes, confirm.
04443726AA - 09/2009 63
Metering Frequency measurements
E60110A
F (Hz)
60.0
View.
64 04443726AA - 09/2009
04443726AA - 09/2009 65
Maintenance Resetting fault indications
Caution! The fault indication is maintained until it is reset on the control panel.
If the circuit breaker remains closed and the Ap LED Press the reset button.
remains ON after the reset, open the circuit breaker
E60306B
and contact the after-sales support department. Micrologic 7.0 P
Fault
22/11/1999
02:04:04
Umin 100V
Reset
by test/reset
button
66 04443726AA - 09/2009
Maintenance Viewing the event histories
E71706A
E71707A
history Trip
history 22/11/1999
Trip
history 02:04:04
U min Umin 160V
27/01/1999
Ir
27/06/1998
Ir
18/02/1998
then
Select a fault. View.
E71709A
history Alarm
history
Alarm 27/01/1999
history 13:06:09
I2 max I2 max 3400A
27/01/1999
In max
23/03/1998
U max
12/02/1998
then
Select an alarm. View.
04443726AA - 09/2009 67
Maintenance Operation counter and
contact-wear indicator
E71736A
E71737A
E71735A
history Number of Number of Number of
operations operations operations
Operation
counter Total Total Total
17824 17824 17824
Operations Operations Operations
since last since last since last
reset reset reset
6923 0 6923
then
Reset… … or cancel the reset,
then confirm.
history Contact
wear
Contact
wear
59
should be inspected every time the counter reaches a
multiple of 100.
68 04443726AA - 09/2009
Maintenance Checking/replacing the battery
E60307A
Micrologic 7.0 P
1 2 3
Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
E71751A
If the battery needs to be changed, order a new battery Replacing the control-unit battery
with the Schneider Electric catalogue number 33593.
1. remove 2. remove the battery
b Lithium battery
the battery cover
b 1.2 AA, 3.6 V, 800 mA/h
DB119959
DB119960
+
DB119961
DB119962
04443726AA - 09/2009 69
Maintenance Tests
DB119963
5.0 P
logic
Micro
If the circuit breaker does not trip, contact the after-sales support department.
Refer to the manual that comes with the test kits. Mini test kit and portable test kit
The test connector is used to connect the mini or the portable test kit to check that
the control unit is operating correctly.
DB119964
DB119965
5.0 P 5.0 P
logic logic
Micro Micro
70 04443726AA - 09/2009
04443726AA - 09/2009 71
Technical appendix Tripping curves
E71753A
72 04443726AA - 09/2009
Technical appendix Tripping curves
E46266A
04443726AA - 09/2009 73
Technical appendix Voltage measurements
Micrologic P is equipped with a three-phase voltage power supply that, with respect
to the distribution system, may be considered a delta load. The three-phase power
supply reinjects voltage on an open phase.
The voltage-protection functions react as indicated below.
Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit reinjects
voltage on the failed phase and measures a phase-to-phase voltage higher than the
actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit reinjects
voltage on the failed phase and measures a phase-to-phase voltage higher than the
actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage and
voltage-unbalance protection functions.
The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for the
three phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).
74 04443726AA - 09/2009
Technical appendix Voltage measurements
b Diagram 1
Contactor
DB120006
Fuses
Motor
Open
b Diagram 2
Contactor
DB120007
Fuses
Motor
Open
b Diagram 3
Contactor
DB120008
Motor
Open
Fuses
b Diagram 4
DB120009
Load
Fuses
Other
measurement
and protection
systems
04443726AA - 09/2009 75
Technical appendix Zone selective interlocking (ZSI)
Operating principle
E60450B
Note:
On device no. 1, the tsd and tg tripping delays must not be set to zero because this would make
discrimination impossible.
2
A
Connections between control units
A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
b Micrologic 5.0 A, 6.0 A, 7.0 A
b Micrologic 5.0 P, 6.0 P, 7.0 P
b Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.
Caution!
Wiring
b Maximum impedance: 2.7 ý / 300 metres
lf the protection function is not used on circuit breakers
b Capacity of connectors: 0.4 to 2.5 mm2
equipped for ZSI protection, a jumper must be installed
b Wires: single or multicore
to short terminals Z3, Z4 and Z5. If the jumper is not b Maximum length: 3000 metres
installed, the short-time and ground-fault tripping b Limits to device interconnection:
delays are set to zero, whatever the position of the v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to a
adjustment dial. maximum of ten inputs
v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and to
an input ZSI - IN CR (Z4) or GF (Z5).
point B
2 Z1
Z2
Z3 tsd = 0. 2
Z4
Z5
point A
Z1 downstream Z1
Z2 circuit-breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
76 04443726AA - 09/2009
Technical appendix Power supply
Battery module
Use of a BAT battery module, mounted in series with the AD power-supply module,
ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.
Wiring diagrams
b Reliable or backed-up auxiliary system
E60449A
L4
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
F2
F1 +
-
L4 H4
L3 Input H3 InputC +
220V
AC
- 24VD
0V t
OutpuC + 24V
t
OutpuC
-
AD 22 – 24VD
G2 BAT + 24VD
H1
G1 H2
F2
F1 +
-
2 Q3
Q1 Q
25
21 23
17 19
L4
M6C
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
04443726AA - 09/2009 77
Technical appendix Power supply
b If the 24 V DC external power supply (AD module) is used, the maximum cable
length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed
10 metres.
b The communications bus requires its own 24 V DC power source (E1, E2).
This source is not the same as the 24 V DC external power-supply module
(F1-, F2+).
When the PTE option is implemented, the supply circuit of the voltage-measurement
input must be protected against short-circuits. Installed as close
as possible to the busbars, this protection function is ensured by a P25M circuit
breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
78 04443726AA - 09/2009
Technical appendix Changing the long-time
rating plug
DB119975
5.0 H 5.0 H
logic logic
Micro Micro
Caution! 4. snap out the rating plug 5. clip in the new rating plug
If no long-time rating plug is installed, the control unit
DB119976
5.0 H
logic
Micro
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
04443726AA - 09/2009 79
Technical appendix Thermal memory
Thermal memory
The thermal memory is the means to take into account temperature rise and cooling
caused by changes in the flow of current in the conductors.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
b For all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.
b For long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping curves.
80 04443726AA - 09/2009
Technical appendix Data available via the COM
communications option
Setup / Maintenance
b Setting of the control-unit date and time
b Password for the measurement module
b Control-unit ID code
b Control-unit ID name
b Selection of the measurement calculation algorithm
b Sign convention for the active power
b Total-energy measurement mode
b Interval for the demand-current calculation window
b Power quality indication
b Demand-power calculation mode
b Interval for the demand-power calculation window
b Battery-charge indication
b Trip and alarm histories
b Operation counter and contact-wear indicator
b Assignment and setup of programmable contacts
b Event log and maintenance register.
Protection
b Circuit-breaker rated current
b Type of neutral protection
b Long-time I2t protection settings
b Long-time Idmtl protection settings
b Short-time protection settings
b Instantaneous-protection settings
b Ground-fault protection settings
b Earth-leakage protection settings
b Current-unbalance, It alarm and maximum-current protection settings
b Voltage-protection settings
b Setting for other protection functions.
04443726AA - 09/2009 81
Technical appendix Threshold and time-delay
settings
Short-time protection
Type Range Factory setting Step Accuracy
Isd pickup 1.5 to 10 Ir maximum 10 A ± 10 %
tsd tripping delay 0 - 0.1 - 0.2 - 0.3 - 0.4 s maximum 0.1 s
Instantaneous protection
Type Range Factory setting Step Accuracy
Ii pickup 2 to 15 In or off maximum 10 A ± 10 %
Neutral protection
Type Range Factory setting
Three-pole device Off, N/2, N, 1.6xN off
Four-pole device Off, N/2, N N/2
82 04443726AA - 09/2009
Technical appendix Threshold and time-delay
settings
Current protection
Type Range Factory setting Step Accuracy
Current unbalance I unbal
Pickup threshold 5 % to 60 % 60 % 1% -10 %, +0 %
Dropout threshold 5 % of pickup threshold pickup threshold 1% -10 %, +0 %
Pickup time delay 1 s to 40 s 40 s 1s -20 %, +0 %
Dropout time delay 10 s to 360 s 10 s 1s -20 %, +0 %
Ground-fault I t alarm
Pickup threshold 20 A to 1200 A 120 A 1A +/- 15 %
Dropout threshold 20 A to pickup threshold pickup threshold 1A +/- 15 %
Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %
Dropout time delay 1 s to 10 s 1s 0.1 s -20 %, +0 %
Earth-leakage I t alarm
Pickup threshold 0.5 A to 30 A 30 A 0.1 A -20 %, +0 %
Dropout threshold 0.5 A to pickup threshold pickup threshold 0.1 A -20 %, +0 %
Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %
Dropout time delay 1 s to 10 s 1s 0.1 s -20 %, +0 %
Maximum current I1 max, I2 max, I3 max, IN max
Pickup threshold 0.2 In to In In 1A ± 6.6%
Dropout threshold 0.2 In to pickup threshold pickup threshold 1A ± 6.6%
Pickup time delay 15 s to 1500 s 1500 s 1s -20 %, +0 %
Dropout time delay 15 s to 3000 s 15 s 1s -20 %, +0 %
Voltage protection
Type Range Factory setting Step Accuracy
Minimum voltage U min
Pickup threshold 100 V to U max pickup threshold 100 V 5V -5 %, +0 %
Dropout threshold pickup threshold to U max pickup threshold 5V -5 %, +0 %
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
Maximum voltage U max
Pickup threshold U min pickup threshold to 1200 V 725 V 5V -0 %, +5 %
Dropout threshold 100 V to pickup threshold pickup threshold 5V -0 %, +5 %
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
Voltage unbalance U unbal
Pickup threshold 2 % to 30 % 30 % 1% -20 %, +0 %
Dropout threshold 2 % to pickup threshold pickup threshold 1% -20 %, +0 %
Pickup time delay 1 s to 40 s 40 s 1s -20 %, +0 %
Dropout time delay 10 s to 360 s 10 s 1s -20 %, +0 %
04443726AA - 09/2009 83
Technical appendix Threshold and time-delay
settings
Other protection
Type Range Factory setting Step Accuracy
Reverse power rP max
Pickup threshold 5 to 500 kW 500 kW 5 kW ± 2.5%
Dropout threshold 5 kW to pickup threshold pickup threshold 5 kW ± 2.5%
Pickup time delay 0.2 s to 20 s 20 s 0.1 s -0 %, +20 % (1)
Dropout time delay 1 s to 360 s 1s 0.1 s -0 %, +20 %
Maximum frequency F max
Pickup threshold F min pickup threshold to 440 Hz 65 Hz 0.5 Hz ± 0.5 Hz
Dropout threshold 45 Hz to pickup threshold pickup threshold 0.5 Hz ± 0.5 Hz
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
Minimum frequency F min
Pickup threshold 45 Hz to F max pickup threshold 45 Hz 0.5 Hz ± 0.5 Hz
Dropout threshold pickup threshold to F max pickup threshold 0.5 Hz ± 0.5 Hz
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
Phase rotation
Pickup threshold Ph1, Ph2, Ph3 or Ph1, Ph3, Ph2 Ph1, Ph2, Ph3 none none
Dropout threshold pickup threshold pickup threshold none none
Pickup time delay 0.3 s 0.3 s none - 0 %, + 50 %
Dropout time delay 0.3 s 0.3 s none - 0 %, + 50 %
(1) + 30 % on dial 0.2 s
(2) + 30 % up to 1.5 s
84 04443726AA - 09/2009
Technical appendix Other settings
Micrologic setup
Type Range Factory setting Step
Language German English UK
English US
English UK
Italian
French
Spanish
Chinese
Date / time 1s
Circuit-breaker "no def"
selection
Neutral TC no TC
VT ratio
primary voltage min. 100 V, max. 1150 V 690 V 1v
secondary voltage min. 100 V, max. 690 V 690 V 1v
System 50/60 Hz 50/60 Hz
frequency or
400 Hz
Measurement setup
Type Range Factory setting Step
System type 3 Φ, 3 w, 3 CT 3 Φ, 4 w, 4 CT
3 Φ, 4 w, 3 CT
3 Φ, 4 w, 4 CT
Demand-current
calculation method thermal or block interval
block interval
type of window fixed or sliding sliding
calculation interval 5 to 60 minutes 15 minutes 1 minute
Demand-power
calculation method thermal or block interval
block interval or
sync. to comms
type of window fixed or sliding sliding
calculation interval 5 to 60 minutes 15 minutes 1 minute
Power sign P+ P+
P- (flow from top to
bottom)
Sign convention IEEE IEEE
IEEE alternate
IEC
Communication setup
Type Range Factory setting
Com parameter MODBUS
adress 1-47 47
baud rate 9600 19200 bauds
to 19200 bauds
parity even even
none
Remote settings
access authorisation yes / no yes
access code 0000 to 9999 0000
Remote control manual automatic
automatic
Protection setup
Type Range Factory setting
Current protection alarm / trip / OFF OFF
voltage protection
other protection
04443726AA - 09/2009 85
Technical appendix Measurement setting ranges
and accuracy
b The accuracy of the current measurements depends Measurement setting ranges and accuracy
on both the value displayed (or transmitted) and the
circuit-breaker rating, where: Type Range Accuracy at 25 °C
Accuracy = 0.5 % In + 1.5 % reading Instantaneous current
I1, I2, I3 0.05 x In to 20 x In ±1.5 %
Example: IN 0.05 x In to 20 x In ±1.5 %
For a circuit breaker with a 4000 A rating and a current I t ground 0.05 x In to In ±10 %
displayed on Micrologic of 49 A, the accuracy is: I t earth leakage 0 to 30 A ±1.5 %
0.5 % x 4000 + 1.5 % x 49 = ±21 A I1 max, I2 max, I3 max 0.05 x In to 20 x In ±1.5 %
IN max 0.05 x In to 20 x In ±1.5 %
I t max ground 0.05 x In to In ±10 %
I t max earth leakage 0 to 30 A ±1.5 %
Demand current
I1, I2, I3 0.05 x In to 20 x In ±1.5 %
IN 0.05 x In to 20 x In ±1.5 %
I1 max, I2 max, I3 max 0.05 x In to 20 x In ±1.5 %
IN max 0.05 x In to 20 x In ±1.5 %
Phase-to-phase voltages
U12 170 to 1150 V ±0.5 %
U23 170 to 1150 V ±0.5 %
U31 170 to 1150 V ±0.5 %
Phase-to-neutral voltages
V1N 100 to 1150 V ±0.5 %
V2N 100 to 1150 V ±0.5 %
V3N 100 to 1150 V ±0.5 %
Average voltage
U avg 170 to 1150 V ±0.5 %
Voltage unbalance
U unbal 0 to 100 % ±0.5 %
Instantaneous power
P 0.015 to 184 MW ±2 %
Q 0.015 to 184 Mvar ±2 %
S 0.015 to 184 MVA ±2 %
Power factor
PF -1 to +1 ±2 %
Demand power
P 0.015 to 184 MW ±2 %
Q 0.015 to 184 Mvar ±2 %
S 0.015 to 184 MVA ±2 %
P max 0.015 to 184 MW ±2 %
Q max 0.015 to 184 Mvar ±2 %
S max 0.015 to 184 MVA ±2 %
Total energy
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
E.S -1010 GVAh to +1010 GVAh ±2 %
Total energy in
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
Total energy out
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
Frequency
F 45 Hz to 440 Hz ±0.1 %
86 04443726AA - 09/2009
Technical appendix Power factor sign conventions
DB120011
Flow of active and
reactive power Q
DB119979
DB119980
DB119981
04443726AA - 09/2009 87
Index
A
Activation 25, 26, 27, 28, 31
Active, reactive, apparent energy 30, 63
Active, reactive, apparent power 30
AD power-supply module 77
Address 36
Alarm 31
Alarm history 33, 67
B
Baud rate 46
Buttons 5, 6
C
Circuit-breaker selection 41
COM communication option 36, 46, 81
Contact 32, 38
Contact wear 68
Control unit identification 4
Control-unit battery 5, 69
Current demand calculation 29, 43
D
Date and time 40
Demand current 29, 57
Demand power 30, 61
Digipact 46
Dropout 25, 26, 27, 28, 31
DT 21, 49
E
Earth-leakage protection 24
Earth-leakage protection tripping delay ∆ 24
EIT 21, 49
F
F max 30, 52
F min 30, 52
Fault 66
Frequency 30, 64
Full neutral protection 23, 51
Graphic display 5
Ground-fault / Earth-leakage fault protection test 70
Ground-fault protection 24
H
Half neutral protection 23, 51
History, setup and maintenance menu 13, 16
HVF 21, 49
I
I t 50
I t Alarm 25, 52
I avg 25
I max 25, 52
I unbal 25, 52
I∆n pickup 24
I2t 20, 48
Idmtl 21, 49
Ig pickup 24
Ii pickup 22
Infrared link 5
Instantaneous current 29, 56
Instantaneous protection 22
Ir current setting 20, 21
Isd pickup 22
88 04443726AA - 09/2009
Index
L
Language 40
Latching 32
Lead seal for cover 5
LEDs 5, 34, 69
Load shedding / reconnection 28, 54
Long-time I2t protection 20
Long-time Idmtl protection 21
Long-time plug 5, 79
M
M2C / M6C 32, 38
Main screen 12, 56
Maximum demand current 29, 58
Maximum demand power 30, 62
Maximum instantaneous current 29, 56
Metering menu 13, 14
ModBus 46
N
Negatively incremented energy 30, 63
Neutral CT 51
Neutral protection 11, 23
Neutral protection setting 11, 51
No neutral protection 23, 51
O
Operation counter 68
Oversized neutral protection 23, 51
P
Parity 46
Phase rotation 27, 52
Phase sequence 27
Phase-to-neutral and phase-to-phase voltage 29, 59
Portable test kit 70
Positively incremented energy 30, 63
Power demand calculation 30, 44
Power factor 61
Power sign 42
Power supply 77
Protection menu 13, 18
R
Remote control 47
Remote settings 46
Resetting the alarms and fault indications 66
Resetting the contacts 32, 38
Resetting the energy values 63
Resetting the maximum demand current values 58
Resetting the maximum demand power values 62
Resetting the maximum instantaneous current values 57
Resetting the operation counter 68
rP max 27, 52
S
Self-protection 35
Setting dials 5, 6
Short-time protection 22
Sign convention 87
SIT 21, 49
System frequency 42
System type 43
04443726AA - 09/2009 89
Index
T
Tab 7
Temperature 35
Test connector 5, 70
tg tripping delay 24
Thermal memory 20, 80
tr tripping delay 20, 21
Transformation ratio 42
Trip 4
Trip history 33, 67
Tripping curves 72
tsd tripping delay 22
U
U max 26, 52
U min 26, 52
U unbal 26, 52, 59
V
VIT 21, 49
Voltage U avg 26, 29, 59
Z
Zone selective interlocking 76
90 04443726AA - 09/2009
Notes
04443726AA - 09/2009 91
Notes
92 04443726AA - 09/2009