Small General Frequency Converter

Operating Instructions

220V 0.75KW – 5.5KW

400V 0.75KW – 15KW

■ Please read the instruction carefully and understand the contents

so that it can be installed and used correctly. 。

■ Please hand in the instructions to the end user and keep it

properly.
■ Technical specifications of this product may change without prior
notice.
2RI20140401-2.0 VersionA
English

Start date : May 1, 2014

Data number: XM-H0123 V3.0

STATEMENT
Thanks to the use of frequency converter, before use, be sure to

read the instructions carefully, please be familiar with the product

safety precautions.
Safety precautions:
1、Before the connection, please confirm whether the input power is
in the power down state.
2、Connection work, please professional electrical engineering

personnel to carry on.


3、Ground terminal, please be sure to ground.
4、After the emergency stop circuit connection is completed, please

be sure to check if the action is valid.


5、Inverter output line is not connected to the shell, the output line is
not short circuit.
6、Please confirm whether the voltage of the AC main circuit power

supply is consistent with the rated voltage of the inverter.

7、Do not carry on the voltage test to the frequency changer.

8、Please connect the brake resistance according to the wiring

diagram.
1 / 26
9、Do not receive the power cord to the output U, V, W terminal
10、Do not access the contactor output circuit.
11、Electricity before installing protective cover. Remove the cover,

please be sure to disconnect the power supply.

12、Select reset to try the function of the inverter, please do not close

to the mechanical equipment, because the alarm will suddenly start

again when the stop.

13、After confirming the operation signal is cut off, the alarm can be

reset, and the frequency converter is likely to start suddenly.


14、Do not touch the inverter terminal, the terminal has a high
voltage, very dangerous.
15、In the power, please do not change the connection and terminal
assembly and disassembly.
16、Cut off the main circuit power supply, can be checked,

maintenance.
17、Do not transform the inverter.

2 / 26
1、Technical Data
Converter Rated Data
Output Physical Size
Version Power Input
A ① A ② sizedimension
Long*wide*high
0.75G1-220V 0.75KW 4 3.7 ((mm)
150*115*150
single phase
1.5G1-220V 1.5KW 7 6.4 150*115*150
A.C.
2.2G1-220V 2.2KW 9.5 8.7 150*115*150
220V-240V
4.0G1-220V 4.0KW 15 14 210*118*180
50Hz/60Hz
5.5G1-220V 5.5KW 20 18 210*118*180
0.75G3-380V 0.75KW 2.5 2.3 150*115*150
1.5G3-380V 1.5KW 4.1 3.8 150*115*150
2.2G3-380V 2.2KW 5.8 5.3 150*115*150
three-phase
4.0G3-380V 4.0KW 9.4 8.6 210*118*180
A.C.
5.5G3-380V 5.5KW 12.6 11.6 210*118*180
370V-440V
7.5G3-380V 7.5KW 16.1 14.8 210*118*180
50Hz/60Hz
11G-380V 11KW 24 22 322*208*192
15G3-380V 15KW 32 30 322*208*192
18.5G3-380V 18.5KW 37 34 322*208*192
Remarks:① At rated voltage, the carrier frequency is 4,6,8kHz

② At rated voltage, the carrier frequency is10kHz

Brake Resistance Type Selection


Version Power Input Resistance power Resistance
0.75G1 0.75KW 100 W 200 Ω
single phase
1.5G1 1.5KW 300 W 100 Ω
A.C.
2.2G1 2.2KW 300 W 100 Ω
220V-240V
4.0G1 4.0KW 50Hz/60Hz 500 W 75 Ω
5.5G1 5.5KW 1000 W 75 Ω
0.75G3 0.75KW 100 W 750 Ω
1.5G3 1.5KW three-phase 300 W 400 Ω
2.2G3 2.2KW A.C. 300 W 250 Ω
4.0G3 4.0KW 370V-440V 500 W 150 Ω
5.5G3 5.5KW 50Hz/60Hz 800 W 100 Ω
7.5G3 7.5KW 1000 W 75 Ω
3 / 26
2、Installation And Wiring
 AC220V AC380V Brake resistance
input input

R S R S T P B
+10V
+12V
ACM
AVI

CE1
CE2
CE3
STP U V W PE

AO
DO

RA
RB
RC
ON

to fault indication)
Analog output

Relay output (factory set


Digital output terminal
Digital input 1
Digital input 2
Digital input 3
Start signal
ACM
AVI

potentiometer M
3~
0-20mA 5KΩ
4-20mA

Terminal use instructions


Terminal Purpose Setting And Description
Inverter input power front should use air
AC power input (single /3 switch as the over-current protection device,
phase) if there is leakage protection switch, in order
R、S、T
Single phase power supply to prevent the leakage switch malfunction,
connected to R, S please choose a sense more than 200mA,
action time more than 100ms equipment.
In order to reduce the leakage current, the
Inverter output, connecting
U、V、W motor connection line should not be more
motor
than 50 meters.
According to the brake resistance selection
P、B Connecting brake resistance
table to select the brake resistance.

4 / 26
PE ground connection Frequency converter to be a good grounding

Terminal Purpose Setting And Description


Zero potential of digital signal and analog
ACM Signal common
signal
Factory set to 0-10V, input impedance: >50k,
AVI Analog signal input can also be connected to the current signal:
4-20mA (modify parameters C34)
Frequency setting
+10V +10V, Max 10mA
potentiometer power supply
Digital input internal DC
+12V +12V, Max 20mA
power supply
Connected to the ON, the inverter can start,
disconnect free parking.
ON Digital input ON/OFF signal Can also be used as a start preparation, after
the switch on display STP, and then CE1 as a
positive turn signal.
By setting the parameter CE1, the factory
CE1 Digital input CE1.
defaults to positive transfer.
By setting the parameter CE2, the factory
CE2 Digital input CE2
defaults to reverse.

By setting the parameter CE3, the factory


CE3 Digital input CE3
defaults to Multi velocity 1

Three wire system start When the three wire system is used to start
STP the frequency converter, the signal is
stop connected with the terminal.

DO Digital output signal By parameter F17 setting

AO Analog output signal By parameter F11, F08 setting

By parameter C08 setting


RA、RB、RC Relay output Contact capacity: AC 250V/3A
DC 24V/2A

5 / 26
3、Debugging And Running
① Operation Panel And Operation Method

Run key
Press the running key, and
the converter starts to run

Numeric change key Stop key


Can be used to increase or
Press the stop button
decrease the value when
to stop the operation.
setting values RUN
Governor potentiometer Parameter setting key
Used to read and modify the parameters of
STOP each group. After pressing can enter the
parameter group or display the parameter
value.
Note: inverter power on the rear panel display STP (short connected to start
preparing) or OFF (not short connect to start preparation).

Press the yellow button

n
utto
ow b
yell
s the
Pres

Pres
s th
e ye
llo w bu
tto n
After setting the parameters, return to
the original interface method:

1、Power off, power up again 2、40 seconds automatic return


3、Select F61 parameters, and then
press the Yellow button


6 / 26
② Frequency Setting Mode Selection
The frequency setting mode of frequency converter is set by the parameter C01. C01=0, the
operating frequency is set by the potentiometer or multi speed setting; C01=1, the operating
frequency is set by the parameter F40.
(1) C01=0, potentiometer setting:
Potentiometer setting panel potentiometer or terminals of an external potentiometer, selected
by the terminal in the upper left corner of the toggle switch B1 (to the left of the toggle switch),
to dial selection panel potentiometer, pulled downward to the terminal of an external
potentiometer.

Panel Panel start stop


potentiometer control

External Terminal stop


potentiometer control
given frequency
B1 B2

(2) C01=0, multi speed given:


The machine can be set up more than 3 speeds, respectively, set in the parameters of C37,
C38, C39, can be through the digital
P input CE1, CE2, CE3 parameter settings to choose.
Such as: set CE3=2, CE2=1, when the CE2 is connected to the operation of multi speed 1,
when the CE3 is running on the multi speed 2, while the CE2 and CE3, it runs more than 3
speed.
(3) C01=1 when the parameter F40 given frequency:
The operating frequency value is set in the parameter F40, the frequency of the frequency
converter in accordance with this value。

7 / 26
③ Frequency converter start mode setting
There are several ways to start the frequency converter: panel control start stop, terminal
forward (FWD) reverse (REV) start, terminal rotation direction control, three wire system start
and stop control. The following are introduced:
panel control start and stop: (factory set to panel start stop)
To use the panel to control the start and stop frequency converter, the toggle switch B2
(pictured on the right side of the switch to dial up wave). Connect 12V and ON after (must be
connected to boot), press the green button on the panel to start, red button down. Note: the
use of panels to control the start and stop, must be parameters CE1=6.

(1) Terminal forward (FWD), reverse (REV) start:


(Toggle switch B2 pull down) Parameter settings: CE2=7, CE1=6 (factory default)

+12V Start ready signal to


变 ON switch on
频 CE1
Is turning FWD, turn on the positive
turn to start, off after the shutdown.
器 CE2 Reverse REV, switch on and off,
disconnect and stop
(2)terminal start, select terminal direction of rotation:

(toggle switch B2 pull down) Parameter setting: CE1=6, CE2=4

(4) outside the green button to start, red button down (three wire system start
stop):

Green button is normally open or compound switch, the red button is often closed, that

is, double button.

Parameter setting: CE1=6


+12V
Start ready signal to switch on
变 ON Frequency converter start, switch on
频 CE1
Keep the start up after the break.
Normally open self - reset button.
器 STP Inverter down, often closed since
8 / 26
the complex button
④ Motor brake
(1) brake resistance brake:
If the load inertia is too large, it will cause the load drive motor to generate power, which will

cause the frequency converter bus voltage rise, the inverter will report dEC alarm or OU fault.

This situation requires the installation of brake resistance. General deceleration time required

within 5 seconds of the equipment, it is recommended to install the brake resistance.

Brake resistance and power according to the selection table selection. The brake resistor

ends, connected to the terminal P and terminal B (regardless of direction).

(2) DC pressure braking:


DC braking is to apply a DC voltage to the motor, so that the motor can be quickly shut

down.

Step for starting DC braking:

The first step: in the parameter C36 set DC brake pressure, the specific value according to

the equipment adjustment.

The second step: setting parameters CE3=3.

The third step: in the inverter deceleration, on 12V and CE3, it will be applied to DC brake.

DC brake stop after disconnection

4、Parameter Table
Factory Setting
NO. name notes
value range
Only when the password
Login
C00 0 0-999 function is valid can be seen
password
(see C94)
0:AVI analog Can be selected by the wave
input.C37,C38, switch B1, set by the panel
C39 multi potentiometer or by the
Frequency
C01 0 speed input terminal AVI。
command
1: parameter The frequency command is
F40 setting set by the value of the
frequency parameter F40.

9 / 26
0: restore If the original C02=1, first
completed changed to 0, and then
C02 factory reset 0 changed to 1, you can reset.
1: restore the
(to remove the 12V and ON
factory value
between the short connection)
1: uses multi At the same time, the multi
speed 1, C37 segment speed 1 and the
2: uses multi multi speed 2 signals are
speed 2, C38 switched on, and the
3: start DC frequency is operated in
DC brake voltage
accordance setmulti
with the by C36
brake
section speed 3.
4: rotation Disconnect: forward turn; turn
direction on: reverse
selection
5: frequency On: start up operation;
converter start disconnect: deceleration stop;
Digital input operation
6: positive Choose 6 when the switch is
CE1 6
CE1 transfer option turned on.
(FWD)
7: reverse Choose 7 when the switch is
selection (REV) turned on, the reverse start,
8:UP (ramp
generator) UP off, DOWN off, slow down
9:DOWN (ramp stop.
generator)
10: external Disconnect the trigger fault
fault shutdown (normally closed signal)

11: fault reset Switch on fault reset,see:F70

Factory
NO. name Setting range notes
value

Digital input (same as


CE2 7
CE2 above)

Digital input (same as


CE3 1
CE3 above)
Operation relay for frequency
Relay output 0:Ready to run
converter
C08 function 1
Frequency converter fault time
selection 1: inverter fault
action relay

10 / 26
2: motor
Motor operated relay
operation
3: the motor is Motor relay with positive
turning rotation
4: motor
Motor reversing action relay
reverse
The frequency converter
5: the output
output frequency is 0 when the
frequency is 0
action relay
6: the Output frequency to reach a
frequency to given value (AVI given or
reach a given given by F40)
7: the
value The output frequency reaches
frequency of
the value of the C17 set.
arrival
8: reach the The output current reaches
current limit the limit value of C22

Minimum The output frequency is


C10 output 0.0 0.0-500 Hz simulated at a given value of
frequency 0%.
Maximum
Running frequency does not
C11 output 50.0 7.5-500 Hz
exceed this frequency
frequency
Output frequency from 0 up to
Acceleration
C12 10.0 0.0-999 s the maximum output
time
frequency of the required time
The output frequency is
Deceleration
C13 10.0 0.0-999 s reduced from the maximum
time
output frequency to 0
Factory
NO. name Setting range notes
value

V/F:Standard application
0: with automatic
V/F two party: applied to
voltage to
C14 control mode 2 the fan pump class
enhance the V/F
curve

11 / 26
1: with automatic
voltage to
enhance the V/F
two square curve

2: with a constant
voltage to
enhance the V/F
C15: according to the rated
curve
frequency of the motor
3: with a constant nameplate on the set
voltage to C16: this setting is mainly
enhance the V/F used to improve the torque at
two square curve low speed
V/F rated
C15 50.0 25.0-500 Hz
frequency

Constant lifting
C16 4.0 0-40 %
voltage
output C08=7, the output frequency
C17 frequency 0.0 0.0-500 Hz reaches this value, the relay
Preset value action
0: 4kHz When the operating current to
carrier 1: 6kHz the rated current of 1.2 times,
C18 2
frequency 2: 8kHz the carrier frequency will be
3: 10kHz reduced to 4kHz
Slip Adjust this parameter until the
C21 compensation 0.0 0.0-40.0 %
motor does not stall
value
When the output current
reaches the limit value, the
Output current 30-150% rated
C22 150 deceleration time becomes
limit output current
longer or the output frequency
becomes lower.

Acceleration Only at the time of


C24 0 0.0-20.0 %
torque acceleration

When C31=0, the analog input


Analog input 0: allowed
C31 0 into the dead zone, the output
dead zone 1: ban
for the 0.0Hz, or display StP.

12 / 26
Factory Setting
NO. name notes
value range

0:0…10V
1:0…5V
Signal
C34 0 2 : 0 … Set the type of AVI signal input
type
20mA
3 : 4 …
20mA
When the value of CE1, CE2 and
DC brake 0.0-50.0
C36 4.0 CE3 is equal to 3, the DC
voltage %
braking.
Multi speed 0.0-500
C37 20.0
1 Hz
By setting the value of CE1, CE2,
Multi speed 0.0-500
C38 30.0 CE3, to select multi segment
2 Hz
speed operation.
Multi speed 0.0-500
C39 40.0
3 Hz
Display
0.0-500 Displays the current frequency of
C46 frequency
Hz a given value
for a given
value
Display
0.0-500
C50 output Display current output frequency
Hz
frequency

Display DC
Shows the current DC bus
C53 bus voltage 0-255 %
voltage percentage
frequency

Display
C54 motor 0-255 % Display current motor output current

current
Automatically identifying the voltage
0:automatic
of the input power supply
Power input
C90 voltage 1 1:low Power set to low input 220V or 380V
selection
Power set for high input 240V or
2:high
450V

13 / 26
When the password is not set to 0,
User
C94 0 0-999 you must enter the password in the
password
C00 to access the parameters

Software Show current software version


C99
version number

Factory
NO. name Setting range notes
value

0.1Hz below, automatic start DC


Auto load DC braking, and keep the parameter
F06 0 0.0-999 s
braking time setting time, set to 0 when do not
start.
F08 analog Adjusting this parameter can change
F08 output ratio 50 0.0-9999 the F11 analog output to be worth
adjustment the size.
0:NO
1 : frequency
Analog output 0-10VDC Define the analog output AO signal
F11 AO signal 0 2 : frequency type, using F08 to adjust the signal
type 2-10VDC ratio
3:Voltage 0-10VDC
4:Voltage 2-10VDC
5:回馈制动
0:Ready to run Operation relay for frequency
converter
1:Inverter fault Frequency converter fault time
action relay
2:Motor running Motor operated relay

3:Motor forward Motor relay with positive rotation

Digital output 4:Motor reverse Motor reversing action relay


F17 DO function 1
5 : The output The frequency converter output
selection
frequency is 0 frequency is 0 when the action relay

6 : Frequency to a Output frequency to reach a given


given value value (AVI given or given by F40)

The output frequency reaches the


7:Frequency arrival
value of the C17 set.

14 / 26
8 : Reach current The output current reaches the limit
limit value of C22

Motor thermal 30-100%, 100% is Note: the maximum set is the motor
F20 protection 100 the rated output rated current, but can not provide full
setting current protection.

Set running
F40 frequency 50 0.0-500 Hz Only C01=1, this setting is valid
setting value

Displays the current After the boot automatically shows


F61 current state status or fault the parameter values, normal boot
information display OFF

Factory
NO. name Setting range notes
value

Display fault
F62 Final fault Only for display
information

Display fault
F63 Last fault Only for display
information

0: re on the power,
the terminal ON plus Both of these 3 methods can reset
Fault reset a low level, digital the fault
F70 0
mode input is set to 11
1: automatic fault
Automatic reset after F71
reset

Fault auto
F71 0 0.0-60.0 s Delay time of fault auto reset
reset delay

Display the total


time after the
F78 Running time 0-999h: display format is XXX
operation of the
1000-9999h: format for x.xx (x 1000)
inverter
10000-99999h: format for xx.x (x
Display the total
Inverter power 1000)
F79 time after power on
on time
the inverter
0:PID control is not
Enable PID control, by the AVI
enabled
PID mode signal as a feedback signal, can be
d38 0 1 : Enable PID
selection connected to the voltage or current
negative
signal.
feedback control

15 / 26
2 : Enable PID
positive
feedback control

Display the Display PID control, the feedback


C59 feedback Scope: F86-F87,% value of the AVI signal input, the
value of the display is a percentage.
PID control Gain value when setting PID
C70 P gain value 5.0 0.0-99.9%
control。
Set the integration time for PID
C71 I integral time 0.0 0.0-99.9 秒
control.

Set value of PID control of the set value, range


F81 0.0 F86-F87
PID control between F86 and F87.

Display the
set value of Displays the set value of the actual
F38 F86-F87
the PID PID control
control
Minimum
F86 0.0 0.0-999 Using the parameter C34 to select
feedback
the signal type of the feedback
Maximum
F87 100 0.0-999 value. Must F86 < F87
feedback

5、Fault diagnosis and elimination


state
meaning reason Elimination measures
display

inverter shutdown Terminal ON signal off Terminal 12V and ON connection

No frequency value or start Frequency given or start


inverter shutdown
command frequency converter
Terminal ON plus pulse rising
Auto start inhibit Start condition F42=0
edge

DC braking DC compression brake is F06 in the holding time after the


efficiency activated automatic return to normal

Reduce motor load, auto reset


Current limit arrival Inverter overload
(see C22)

Under voltage The main power supply Check the power supply voltage
alarm voltage is too low and parameters C90

16 / 26
Deceleration time is too If over voltage <1s, then
DC bus
short, resulting in DC bus automatic recovery; if >1s, then
overvoltage (alarm)
voltage is too high the report OU
The frequency converter
Unable to access can not modify the Disconnect the connection
parameters parameters of the between 12V and ON.
operation

Invalid parameter Modify for correct parameters


Invalid data in data
memory
data error factory reset

Data memory error Data loss or damage factory reset

CE1-CE3 is defined as the Each digital signal can only be


Parameter same digital signal used once
definition repeat Define the missing digital signal
Only use "UP" or "DOWN""
to the other terminal.

Set C34=2, but no current Modify C34, or switch on current


4-20mA signal loss
signal is switched on signal

Brake unit failure Brake resistance overheat Prolonged deceleration time

State
Meaning Reason Elimination Measures
Display
Digital input is set to 10,
External fault Exclude external faults
but not Connect

Internally generated Restore factory value or contact


internal fault
unknown fault manufacturer

Internally generated Restore factory value or contact


internal fault
unknown fault manufacturer

Internally generated Restore factory value or contact


internal fault
unknown fault manufacturer
Check the wire and the ground
insulation of the motor cable.
Short circuit or
Output short circuit Measuring the resistance of the
overload
motor, the ground insulation can
not be less than 5.MΩ

17 / 26
Cable capacitive current is Whether the motor line is too
too large long

Acceleration time (C12) is To extend the time to check the


too short specifications of the selected
frequency converter。
One phase of the motor
Earth fault Check motor cable
Ground

Motor thermal overload,


Check the actual current of the
long time current is too
Motor overheating inverter and the motor
large. Frequent start or
Check F20 parameters
long acceleration process.

Controller Inverter internal Reduce inverter load, improve


overheating overheating the cooling conditions

The main power supply Check the power supply voltage


voltage is too high and C90 settings
DC bus Deceleration time is too
Prolonged deceleration time
overvoltage short
Leakage of electric motor
Check motor cable
side

Automatic fault More than 8 times in 10 Depends on the number of


reset too much minutes. failures

Missing single phase


Single phase fault Check power supply voltage
power supply
Low power supply Voltage is lower than the Detection of power supply
voltage working voltage voltage

Dealing with common problems:


① Power up or run time display
Input power low alarm, check whether the input voltage is too low. Supply voltage 380V inverter,
shall not be less than 350V, the power supply voltage 220V inverter, shall not be less than 180V. Can
pass the parameter C53 to examine the measuring value of frequency converter.
2 Display on power up or down
Input power high alarm, check whether the input voltage is too high. Can pass the parameter C53 to
examine the measuring value of frequency converter. Measurement of more than 135, it will show the
fault.Processing method: reduce the supply voltage, extend the deceleration time, increase the braking
resistance. Also can modify the parameter C90 to 2.

③ Display on power up

18 / 26
Check CE1, CE2, CE3 parameter settings, does not allow to set the same value

④ Run display
If after the operation immediately display the fault information, first remove the motor line, and try

again. If remove the motor line also show fault is the inverter fault, if no longer display fault is output line

of the motor or motor internal short circuit.

⑤ Operating jump leakage protection switch


Inverter at run time, due to the presence of higher order harmonics, motor and motor line will be

the leakage current, resulting in leakage protection switch trip, which is determined by the principle of

the frequency converter, is inevitable, when the jump occurs leakage fault is guaranteed, take the

following measures:

First: the use of leakage protection of current leakage protection of more than 200mA.

Second: modify the carrier frequency, parameter C18=0, reduce leakage flow.

Third: increase the AC output reactor.

Fourth: as far as possible to reduce the length of the motor line, or overhead motor line.

6、 Application examples

(1) inverter constant pressure water supply control


A: electric contact pressure gauge control (the most simple control method)

The electric contact pressure gauge pressure control, only need to connect the two wires, a root from

green needles, a root from black needle, respectively, then the three binding posts of the electric

contact pressure gauge above 2 (some of the electric contact pressure gauge may be different). When

19 / 26
the water pressure is low, the black needle is below the green needle, and the frequency converter is in

an accelerating starting state. When the water pressure is high, the black needle is in the green needle.

Very simple and easy to maintain.

For this inverter, the debugging steps are as follows:

(1)2 lines from the electric contact pressure meter, a wire connected to the 12V, the other line is

connected to the CE1 (no need to distinguish between positive and negative).

(2)On the right side of the wave switch B2 dial to the bottom (to participate in the P6 page), select the

external terminal to start control.

(3)The panel on the speed control knob up to the maximum.

(4)Set the drive parameters: CE1=6, C12=80, C13=80

Automatic start up after power up. If not start, can be directly connected to the CE1 and 12V wire, to

see whether or not to start, such as can not be started, the inverter is set to explain the problem. If you

can start, that is the external electric contact table or line problems, can check whether the 2 wires on

the electrical contacts, black needle lower than the green needle should lead, black needle is higher

than the green needle should be disconnected.

B:Water supply control (see P14 page for PID parameters)


Use the built-in PID converter is controlled by adjusting the PID control function, pressure
acquisition using pressure sensor or remote pressure gauge. Debugging steps:
① B1 on the left side of the toggle switch dial below. (see page P6)② The remote pressure gauge
pressure signal connected to ACM, AVI, 10V. If the 2 wire pressure sensor is connected to the AVI,
ACM. You can see the size of the feedback value in the parameter C59.
③If the panel is started, the right toggle switch B2 dial to the top. If the terminal start control, the
right toggle switch below B2 dial. The start signal line is connected to the 12V and CE1.

④ Parameter settings: CE1=6, C12=30, C13=30d38=1,Enable PID negative feedback control;


F81, used to set the size of the water pressure, the setting range is 0-100, through this parameter
to adjust the height of the water pressure. Can be adjusted to 30, and then adjusted according to the

actual application of high or low.


⑤ PID control adjustment speed:
C70=2, P value parameter adjustment, the greater the P value, the faster the adjustment.
Recommended (1-10)

20 / 26
C71=0.2, I value parameter adjustment, the greater the I value, the slower the adjustment.

Recommended (0.1-1)

(2) Inverter Pid Control Debugging


① Set PID control mode, parameter d38.
D38=0, do not start PID control;
D38=1, enable PID negative feedback control;
D38=2, enable PID positive feedback control;
② Set PID to a given value, parameter F81.
The setting range of 0-100 is F81. (can also be changed by the parameter F87 and F86 this range,

also can view a given value through the parameter F38).


③ Set feedback value:
The feedback value is given by the terminal AVI, which can be connected with the voltage signal

and the current signal. The voltage signal is connected with the ACM, AVI and 10V. If the 2 wire
pressure sensor is connected to the AVI, ACM. You can see the size of the feedback value in the
parameter C59.

④ PID control adjustment speed:


Through the P value parameter C70 adjustment, P value is bigger, the adjustment speed is quicker.
Recommended (1-10)
Through the I value parameter C71 adjustment, I value is bigger, the adjustment speed is slower.
Recommended (0.1-1)
⑤ Start converter:
The use of PID control, the left toggle switch B1 dial down (external analog). Start-up mode such
as the use of panel and right toggle switch B2 dial to above, the starting method such as the use of an
external terminal start, right toggle switch B2 dial below, connected to 12V and CE1 can start.

(3) two kinds of speed control


Equipment requirements: the use of a potentiometer knob to speed control, the use of multi

speed when the reverse rotation.


1、The two toggle switches B1, B2 goes to the bottom.
2、Wiring: potentiometer 3 wire connected to the ACM, AVI, +10V, the positive transfer signal
connected to the 12V and CE1, the reverse signal is connected to the CE2, 12V, while CE2 and CE3
short.

21 / 26
3、Parameter setting: CE1=6, CE2=7, CE3=1, C37=10 (reverse running speed 10HZ)

(4)Point Motion Control


Need to point to the control of the device, you can use the multi speed control.
The right toggle switch below B2 dial.
Connection: the positive transfer signal is connected to 12V and CE1, while CE1 and CE3 are
short connected.
Parameter settings: CE1=6, CE3=1, C37=10 (point moving speed 10HZ)
(5) Low Speed Operation (torque is not enough)
Parameter setting C14=2, then adjust the parameter C16, ascending gradually adjusted, not

to regulate the, regulated may report OC overcurrent fault.

(6) using high speed motor


Used in woodworking machinery, engraving machine and other equipment, pay attention to
the motor rated frequency of the motor shall check. You must set the parameters of C15, C11, C15 is
the rated frequency, and to the same motor nameplate. C11 is the maximum output frequency, can be

less than or equal to C15.


(7)Motor free stop control
Inverter factory set to slow down the way, some equipment needs the motor to free down the
way, according to the following steps.
1、The connection between 12V and ON to remove the short, right below the B2 dial to toggle
switch.
2、Setting parameters CE2=2, CE1=1, CE3=4
3、When connected to the 12V and ON, the converter will be turned to start, will be free to stop
when the disconnect.

22 / 26
Parameter modification record

NO. parameter values NO. parameter values

23 / 26
Service delivery value, quality cast brilliant
Letter to the user:
Thank you for using our products, in order to ensure that you get the best
after-sales service of our company, please read the following terms, and do a
good job in the relevant matters.
1, product warranty
According to the normal use of the use of the case, the failure occurred
within the warranty.
2, product warranty period
The warranty period of this product is from the date of the factory, within
twelve months. After the warranty period, the implementation of long-term
technical support services.

24 / 26
3, non warranty scope
Any violations of the requirements of human factors, natural disasters or
water, external damage, harsh environment causes damage, and not permitted
without the transducer disassembly, modification and maintenance of behavior,
considered as a waiver of warranty service.
4, from the middle of the purchase of products
Where the dealer, agents to buy products from the user, in the product
failure, please contact the dealer or agent.
Please keep this manual in order to prepare for the use of.

Service data number: XM-H0123