Professional Documents
Culture Documents
A R T I C LE I N FO A B S T R A C T
Keywords: Intermittence from solar photovoltaic (PV) source can deteriorate overcurrent relays (OCRs) response to fault.
Accurate photovoltaic (PV) system This paper proposes a method for fault analysis with OCRs consideration to discuss relays faults currents fluc-
Battery Energy Storage System tuations in time against PV fluctuations. The simulated PV fluctuations are short time dynamic high and low
Fault analysis irradiations fluctuations and PV connection and disconnection based PV-dominated feeders. Two distribution
Photovoltaic (PV) fluctuation
systems (DSs) based accurate PV systems are modeled separately with and without Battery Energy Storage
overcurrent relay (OCR) fault current
System (BESS) for the purpose of proposed method. Series and parallels PV modules are arranged to model
accurate 6.5 kV PV farm power. Two level three-phase voltage source inverter (VSI), DC-DC boost converter and
LCL filter are applied for each PV system. Precise detailed control strategies are implemented in PSCAD software.
This paper proposed method complies with congestion which is frequently avoided in literature. The results
discussions based proposed method clarified PV fluctuations scenarios impacts on OCRs dynamic fault currents
profiles in presence and absence of BESS and clearly revealed and argued related important findings. In addition,
OCRs performance is shortly analyzed based particle swarm optimization (PSO) algorithm efficiently coded in
Matlab. The obtained results could be very profitable to power system relaying operators to handle protection
challenges with PV power fluctuations.
⁎
Corresponding author.
E-mail addresses: sergetekpeti@stu.xjtu.edu.cn, tekpetiserge@yahoo.fr (B.S. Tekpeti).
https://doi.org/10.1016/j.ijepes.2018.03.003
Received 1 December 2017; Received in revised form 18 February 2018; Accepted 1 March 2018
Available online 13 March 2018
0142-0615/ © 2018 Elsevier Ltd. All rights reserved.
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
profiles in time are clearly analyzed based comparison in an interesting ⎡id ⎤ ⎡ cos(θ) cos(θ−2π /3) cos(θ + 2π /3) ⎤ ⎡ia ⎤
way. Few relays are implemented to ease analysis when taking into ⎢ iq ⎥ = 2/3 × ⎢− sin(θ) − sin(θ−2π /3) − sin(θ + 2π /3) ⎥ × ⎢ ib ⎥
account of all the relays in time based distinct PV fluctuations scenarios. ⎢i ⎥ ⎢ ⎥ ⎢i ⎥
⎣ 0⎦ ⎣ 1/ 2 1/ 2 1/ 2 ⎦ ⎣ c⎦
Three lines to ground (3L-G) symmetrical fault which is a severe fault in
(1)
power system is applied. Usually, inaccurate models are developed,
which this work overcomes as it mainly uses self-built power conver- v ⎡ cos(θ) ⎤
sion facilities and control strategies. In fact, it is obvious that, the more ⎡ a⎤
vabc = ⎢ vb ⎥ = vm × ⎢ cos(θ−2π /3) ⎥
⎢ ⎥
accurate the system the better the results precision. The control stra- ⎣ vc ⎦ ⎣ cos(θ + 2π /3) ⎦ (2)
tegies are dq current control and voltage mode PQ control based syn-
chronous rotating frame control strategy; Incremental Conductance (IC) The grid active power (P ) and reactive power (Q) follow (3) when vq is
maximum power point tracking (MPPT); phase locked loop (PLL); pulse not null, and (4) if vq = 0 due to PLL which assures θ synchronization.
width modulation (PWM); sinusoidal pulse width modulation (SPWM) PLL is a negative feedback control, with details available in [4].
and BESS control. OCRs performance is analyzed based PSO algorithm
⎧ P = vd id + vq iq
as case study.
The remainder of this paper is organized as follows. Section 2 ex- ⎩Q = vd iq + vq id
⎨ (3)
poses PV systems modeling with control strategies details and relevant
explanations including emphasizing this work goal. In Section 3, PV ⎧ P = vd id
⎨ Q = vd iq (4)
penetrated DSs models are explained to show this paper modeling ⎩
quality. Section 4 argues solar radiation fluctuation impact on PV where vd and vq are direct and quadrature voltages components, re-
system performance in distinct manners to highlight important findings spectively.The dq current control in rotating reference frame takes dq-
with descriptive figures. Section 5 provides the proposed simulation ∗
frame voltages (vdq ), currents (idq ) and dq-frame reference currents (idq )
method details. Section 6 gives PSCAD simulations results and provides from voltage mode PQ control to produce dq-frame reference voltages
∗
convincing discussions and comments. Section 7 presents relays per- (vdq ). Voltage mode PQ control is outer control loop whereas dq current
formance analysis based PSO algorithm. All the results are provided in control is inner control loop. Joined both control loops constitutes
form of Tables and figures. Section 8 concludes this paper. synchronous rotating frame structure.
The relationship between natural (abc) and rotating (dq0) frames of 2.3. Boost converter and VSI control
injected grid current (iabc ) formulated based park transformation is in
(1). The three-phase voltage (vabc ) is in (2). θ is the grid voltage phase Fig. 3 shows boost converter PWM control. The state of difference
angle; vm the phase maximum voltage, whereas id , iq , and i 0 are direct, between PV farm voltage (vpv ) and IC MPPT output voltage (vMPPT ) in (6)
quadrature, and zero components currents, respectively. Usually, i 0 is decides control signal of switch T1 through PI 3 regulation based signals
neglected. comparator. The signal is 0 when (vMPPT ) is greater than (vpv ) and 1 else.
Point of Common
Coupling
518
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
Point of Common
Coupling
ipv L1 D1 ipv
S22
+ + Reset
Rint ibat L2
Limiter vdc
PV vpv T1 ibat ibatlim 980V Ebat
Cpv Cdc vdc S11
Farm vbat
940Ah
SOC
Buck boost switching
vpv Filter IC MPPT vMP PT control logic
PI 3 Trigger vdc ibat
ipv Filter algorithm + COM pulse
*
vdc
*
ibat COM S22
vpv PI 4 PI 5
Fig. 3. Boost converter control with MPPT.
SOC SOC & vdc S11
vdc control
The DC bus capacitor (Cdc ) and PV farm output capacitor (Cpv ) are
modeled 10 4uF . Fig. 4. BESS buck-boost converter control.
1,vpv−vMPPT > 0
T1 = ⎧
part and exponential voltage part, which are 2nd and 3rd terms of (9),
⎩ 0,vpv−vMPPT < 0
⎨ (6)
respectively.
∗
Based produced vdq from current control loops, inverse park transfor- From Fig. 4, vdc is compared to vdc ∗
and controlled through PI4 to
∗
mation is applied to obtain equivalent reference voltages signals (vabc ) in ∗ ∗
generate reference battery current ibat . ibat is further compared to ibat and
abc natural frame. Lastly, SPWM for inverter control is realized. Indeed, ∗
controlled through PI5. ibat is defined in (10), where Kpb4 and Kib4 are
∗
signals (vabc ) are compared to 10kHZ high frequency signal to avoid PI4 proportional and integral gains, respectively. Combined SOC and vdc
switching loss and give the inverter 6 IGBT control signals S1−S6. The control is inspired from [12,35]. Both PI4 and PI5 controllers generated
LCL filter at VSI output has L = 2mH , C = 30uF and L = 1mH . signal is passed to the PWM circuit and later the logic circuit is used for
decision upon charge, discharge or halt modes of operation. The switch
2.4. BESS based buck-boost converter control S11 is triggered and S22 is zero during boost mode (discharge), whereas
S22 is triggered and S11 is zero during buck mode (charge) to absorb
The BESS buck-boost converter control is in Fig. 4. Lead-acid battery power from the DC bus. However, S11 and S22 become zero when no
is applied in this paper based [12,34,35]. The battery has terminal regulation signal is needed (halt mode).
voltage (vbat ) and state of charge (SOC ) define in (7) and (8), respec-
tively, as function of battery current (ibat ). ∗ 1 ∗
ibat = ⎛Kpb4 + Kib4 × ⎞ (vdc −vdc )
⎝ s⎠ (10)
vbat = Ebat −Rint ibat (7)
As defined in (11), fluctuations originated from PV (ΔP ),load or grid can
SOC = 100 1− ( (∫ i bat dt / Qbat )) (8)
cause extra energy (ΔE ) largely influenced by Cdc.. That is, vdc regulation
should be fast enough to maintain constant voltage and minimize power
where Qbat is battery capacity and Rint battery internal resistance. The loss.
battery open circuit voltage (Ebat ) in (9) is modeled using controlled
1
voltage source as shown in Fig. 4. ΔE = ∫T s
ΔP. dt =
2
2
[Cdc (vdc 2
1−vdc 0 )]
(11)
Ebat = E0−K × [(1−SOC )/ SOC ] × Qbat + Aexp[−B (1−SOC ) Qbat ] (9) 2 2
where and
vdc1 are DC bus voltages at the end and start of the period
vdc0
where E0 is the battery constant, which value lies between the full Ts , respectively.
charged voltage and exponential voltage of battery discharge curve. K The PV farm has 9.75 MW at standard test condition, which is 1000
is the polarization voltage; A and B are exponential voltage and ex- W/m2 irradiation and 25∘C temperature. The series and parallel com-
ponential capacity, respectively. The battery model has normal voltage binations of batteries produces total BESS power of approximately 920
519
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
kWh suitable to compensate for short term deviation in DC bus voltage. whereas low irradiation results in low current.
As PV systems of Figs. 1 and 2 are determinant parts of focused DSs Due to PV2 connection, apart from normal voltage drop during fault
in this paper, we preliminary conducted simulations on them to assure from 0.3 s to 0.4 s, a slight but non-negligible voltage drop occurs at
each model works properly. However, the results are not mentioned PV1 inverter side, before and after fault, as shown in Fig. 6(d), com-
here to rather focus on this paper objective fulfillment. Unlike PV pared to normal voltage in Fig. 6(c). It could be caused by applied same
models including BESS connection and disconnection cases in same size PVs, as an extra case study justified that, PV2 with size higher than
model, this paper applies two separate similar models with and without PV1 rather induces over voltage, before and after fault, whereas a size
BESS. This seems more accurate situation as no need to connect and lower than PV1 induces more voltage drop, before and after fault. Same
disconnect BESS to evaluate its performance. This paper analysis based observations apply to PV3-PV4 separate connections at nodes 3 and 4,
PV models of Figs. 1 and 2 could be profitable for protection engineers respectively, added to only PV1 initially connected in Fig. 5, with and
to investigate overcurrent relays protection challenges against PV without BESS.In addition, BESS has regulated DC bus voltage and PV1
fluctuations, such as unpredictable irradiation fluctuation and PVs output during low irradiation profile in a robust and efficient way as
connection and disconnection in time, as discussed further. Thus, the depicted in Fig. 7. Indeed, irradiation started maintained at 1000 W/m2
analysis could be useful to address new methods to enhance relay co- and decreased to 600 W/m2 at 0.5 s and, fluctuated randomly in
ordination in DS [36–39]. The BESS performance is revealed based 200–600 W/m2 with and without BESS. PV1 6.5 kV voltage is smoothed
pertinent analyses. in Fig. 7(b) compared to Fig. 7(a) voltage under minimum acceptable
value from 0.5 s, with and without BESS, respectively. DC bus voltage is
regulated in Fig. 7(d) compared to Fig. 7(c) voltage under minimum
3. PV connected DSs models
acceptable value from 0.5 s, with and without BESS, respectively. The
batteries previously charged during PV working at high irradiation
Two DSs are considered for fault analysis in this paper, where the
around 1000 W/m2 are discharged against low irradiation to smooth
difference between them is in the PV systems models used. The two DSs
and regulate PV1 voltage and DC bus voltage, respectively. However,
have same scheme profile in Fig. 5 modeled in PSCAD. Precisely, for the
PV1 current which is 1.5 kA at 1000 W/m2,varies almost same in BESS
DS including BESS, PV1 and other PVs to be connected later at nodes
absence and presence in Fig. 7(a) and (b), respectively, but fluctuations
2–4, have separate identical PV system model of Fig. 1 with entire
instability is increased without BESS. Moreover, fault occurrence has
control strategies. On the other hand, PVs of DS without BESS have
insignificant influence on PV current and PV and DC bus voltages as
separate identical PV system of Fig. 2 with entire control strategies.
clearly noticeable in fault duration from 0.3 s to 0.4 s in Fig. 7(a)–(d).
This paper is using accurate PV systems models with satisfied high
degree of complexity, congestion, and accuracy. In fact, quality models
are usually avoided over inaccurate models, such as constant voltage
5. Proposed simulation method details
and current controlled sources full of assumptions and uncertainty.
Though connected PV systems are identical, depending on type of DS
3L-G faults of 0.3 ohm severity are applied in the middle of lines L1-
model, no common variable existed between them in implementation,
L4, simultaneously, during all fluctuation cases. PV1 irradiation is
as each of them has its own variables, with subscripts 1–4, for PV1-PV4,
varied with and without BESS, in both high and low irradiation profiles,
respectively, to comply with software requirement. The radial DS in
separately, at all simulation time, for all studied cases.For both DSs
Fig. 5 includes eight OCRs named, R1-R8, and the lines are sketched
models, first, PV1 impact is investigated to collect relays maximum
5 km and have two identical relays each. In addition, the grid is 110 kV
fault currents in time. Later, PV2-PV4 are connected to nodes 2–4, re-
with 100 MVA power rating.
spectively, at same time, which is beginning of simulation, to collect
relays fault currents. PV2-PV4 irradiation is kept constant at 1000
4. Solar radiation fluctuation impact correction W/m2 in this paper. PV2-PV4 connection is in Fig. 8(a). The case study
systems, PV2-PV3 disconnected whereas PV1 and PV4 connected; PV2
Considering Fig. 5 model, with only PV1 connected based Fig. 2 and PV4 disconnected whereas PV1 and PV3 connected; and PV3-PV4
model, low irradiation fluctuation in 200–600 W/m2 induced 1 kA low disconnected whereas PV1-PV2 in service, as shown in Fig. 8(b)–(d),
PV1 inverter current in Fig. 6(a). However, the use of BESS has cor- respectively, are further carried out to do same. LVRT capability, which
rected that current up to 2.2 kA normal amplitude in Fig. 6(b). is hot topic for PV is not applied in this paper as PVs connection and
Insignificant and high build up currents due to simultaneous 3L-G disconnection scenarios are methodically proceeded manually. Except
faults in middle of lines L1-L4 are observed in Fig. 6(a) and (b), re- PV1 which is always connected during all scenarios to dynamically
spectively. The maximum fault currents are 1.2 kA and 4.8 kA in fluctuate its irradiation it time, the other PVs are either connected or
Fig. 6(a) and (b), respectively. It is important to emphasize that irra- disconnected at time t = 0 s to simulate the expected scenario in Fig. 8.
diation fluctuations only have impact on inverter current and not on its Software limitations make long time irradiation fluctuations simu-
voltage, as high irradiation provides normal current amplitude, lation tedious. Besides, fast irradiation variations can be assessed
around an arbitrary instant in time. The faults started in 0.3 s and they
PV 1 take 0.1 s. The maximum fault currents seen by each relay is collected
0.27 kV/ following fault current evolution in time. Precisely, every 0.02 s, the
30 kV maximum fault current of the relays are plotted, representatively, in
R1 R2 R3 R4 form of charts, from 0.3 s to 0.4 s. That is, from the collected dynamic
maximum faults currents in time, each relay will have highest and
30 kV/ minimum faults currents values in time. The highest fault current is the
Ld1 Ld2
110 kV Fault Fault high amplitude fault current in time whereas the minimum fault current
Ld3 Ld4 is the low amplitude fault current in time. This method ease fault
110 kV current comparison in time. Each relay fault current is represented with
100 MVA R5 R6 R7 R8
50 Hz a unique color to ease differentiation. During the fault period, the
Grid plotted maximum fault currents correspond to maximum phase currents
Fault Fault at specified time. Based on this simple and effective method applied in
PSCAD, OCRs maximum faults currents are collected and plotted
Fig. 5. PV connected DS.
faithfully.
520
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
3.0
4.0
2.0
2.0
1.0
0.0 0.0
-1.0
-2.0
-2.0
-4.0
-3.0
-4.0 -6.0
Time(s) 0.300 Time(s) 0.300 0.310 0.320 0.330 0.340 0.350 0.360 0.370 0.380 0.390 0.400
0.310 0.320 0.330 0.340 0.350 0.360 0.370 0.380 0.390 0.400
(a) (b)
PV1 Inverter side voltage PV1 Inverter side voltage
Vabc1 Vabc1
0.250
0.200
0.20
0.150
PV1 Inverter side voltage(kV)
PV1 Inverter side voltage(kV)
0.10 0.100
0.050
0.00 0.000
-0.050
-0.10
-0.100
-0.20
-0.150
-0.200
-0.250
Time(s) 0.250 0.300 0.350 0.400 0.450 Time(s) 0.200 0.250 0.300 0.350 0.400 0.450 0.500
(c) (d)
Fig. 6. PV1 performance under random low irradiation variation in 200–600 W/m2
against 0.1 s simultaneous 0.3 ohm 3L-G faults in middle of L1-L4: (a) PV1 inverter current without
BESS (b) PV1 inverter current with BESS (c) PV1 inverter normal voltage (d) PV1 inverter voltage with PV2 added at node 2.
6. Results and relays faults currents fluctuations analysis 6.74 kA, 6.66 kA, 3.12 kA, 15.65 kA, 6.73 kA, 6.6 kA and 2.91 kA, re-
spectively, at 0.3 s for R4 and R8, whereas at 0.32 s for other relays in
Similar relays fault current profiles are observed against high and Fig. 11. However, with BESS included, R1-R8 have highest faults cur-
low irradiations fluctuations, where fluctuations in time seem to have rents of, 14.74 kA, 6.05 kA, 6.02 kA, 2.85 kA, 14.88 kA, 6.08 kA,
insignificant impact on faults currents seen by relays. However, PVs 6.01 kA, and 3.1 kA, respectively in Fig. 12, at same instants as in
connection and disconnection have very remarkable influence on faults Fig. 11.
currents seen by relays. Based on these facts, it is unnecessary to repeat In both cases, in terms of achieved highest fault currents, R4 and R8
approximately same values of fault currents for high and low irradia- have low faults currents probably due to far distance from PV1. As it is
tions fluctuations. That is, it is very useful for the purpose of this paper easily comparable, R1 and R5, R2 and R6, and R3 and R7, have very
to plot relays maximum faults currents variation in time when con- close highest faults currents, maybe due to the symmetry among relays
necting and disconnecting PVs at specific nodes, considering high and positions. Except R8, in majority, R1-R7 highest faults currents without
low irradiation fluctuations in time as a unique case. Indeed, as relays BESS are slightly greater than those with BESS. On the other hand,
faults currents profiles were almost identical against high and low ir- without BESS, R1, R3, R5 and R7 have minimum fault currents of,
radiation profiles, we choose to plot results with low irradiation profile 9.32 kA, 4.34 kA, 9.4 kA and 4.32 kA, respectively, achieved at 0.3 s for
as that profile usually gives PV systems weak performance. As a result, both R1 and R5 and at 0.4 s for both R3 and R7 in Fig. 11. However,
relays fault currents under low irradiation apply to high irradiation. with BESS, the corresponding relays mainly have limited minimum
Against high and low irradiations fluctuations in Figs. 9 and 10, fault currents of, 8.42 kA, 3.83 kA, 10.35 kA and 3.76 kA, respectively,
respectively, with separate PVs connection and disconnection cases, the at 0.3 s for R1 and at 0.4 s for the remaining relays in Fig. 12.
coming figures show relays maximum faults currents fluctuations dy-
namism in time in absence and presence of BESS. Considering the high
6.2. PV1-PV4 supplying 6.5 kV power each
6.5 kV power PVs penetration in this paper, quite high faults currents
could be observed, depending on, fault type, location and severity.
Here, PV2-PV4 are connected at time t = 0 s . Without BESS, R1-R8
have highest faults currents of, 15 kA, 12.12 kA, 12.07 kA, 15.57 kA,
6.1. PV1 supplying 6.5 kV power 12.94 kA, 15.92 kA, 5.12 kA and 15.00 kA, respectively, at 0.36 s for R6,
whereas at 0.32 s for other relays in Fig. 13. PV2-PV4 connection in-
Without BESS, relays R1-R8 have highest faults currents of, 15.6 kA, duced random faults currents and, as we can see, there are no particular
521
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
PV1 Volta
ge and Curren
t PV1 Volta
ge and Current
Vpv1 Ipv1 Vpv1 Ipv1
8.0 8.0
7.0 7.0
PV Voltage (kV) / Current (kA)
5.0 5.0
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
Time(s) Time(s) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
(a) (b)
PV1 DC bus voltage PV1 DC bus voltage
Vdc1 Vdc1
8.0 8.0
7.0 7.0
PV1 DC bus voltage (kV)
6.0 6.0
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
Time(s) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 Time(s) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
(c) (d)
Fig. 7. PV1 performance under random low irradiation fluctuation in 200–600 W/m2
against 0.1 s simultaneous 0.3 ohm 3L-G faults in middle of L1-L4: (a) PV1 current and voltage
without BESS (b) PV1 current and voltage with BESS (c) PV1 DC bus voltage without BESS (d) PV1 DC bus voltage with BESS.
currents similarities among the relays. In majority, adding PV2-PV4 10.53 kA, 16.02 kA and 10.53 kA, respectively, at 0.3 s for R4, whereas
provoked relays build up currents and, for instance, R4, R6 and R8, at 0.32 s for other relays in Fig. 16. Without BESS, R2, R4 and R6 have
with highest currents of 3.12 kA, 6.73 kA and 2.91 kA, respectively, minimum faults currents of, 5.06 kA, 0.82 kA and 9.37 kA, respectively,
when PV1 connected, suddenly present build up currents of 15.57 kA, at 0.4 s for R2, 0.32 s for R4 and 0.3 s for R6 in Fig. 15. However, using
15.92 kA and 15.00 kA, respectively. It seems that PVs connections BESS, the corresponding relays have limited minimum faults currents
induce more faults currents seen by the closest relays, which are R4, R6 of, 4.31 kA, 0.69 kA and 8.58 kA, respectively, at cited same instants in
and R8, for PV2-PV4, respectively. Fig. 16.
Moreover, with BESS, R1-R8 have slightly smoothed highest faults
currents of, 14.56 kA, 10.97 kA, 10.94 kA, 16.13 kA, 12.19 kA, 16 kA, 6.4. PV1 and PV3 supplying 6.5 kV power each
4.46 kA and 14.74 kA, respectively, at 0.34 s for R6, whereas at 0.32 s
for other relays in Fig. 14, but build up currents still present. Without Here, PV3 and PV4 are connected and disconnected, respectively, at
BESS, R5 and R7 have minimum faults currents of, 6.22 kA and 2.45 kA, time t = 0 s.. Without BESS, R1-R8 have highest fault currents of,
respectively, at 0.3 s for both relays in Fig. 13. However, with BESS, 16.78 kA, 7.23 kA, 7.15 kA, 2.79 kA, 12.66 kA, 15.77 kA, 7.54 kA, and
both relays have 5.58 kA and 2.18 kA limited currents, respectively, at 2.57 kA, respectively, at 0.3 s for both R4 and R8, whereas at 0.32 s for
same instant in Fig. 14. other relays, as shown in Fig. 17.
Relay R6, which has 6.73 kA with PV1, now sees 15.77 kA build up
6.3. PV1 and PV4 supplying 6.5 kV power each current, whereas other relays have random decrease or increase in fault
currents. The use of BESS gives R1-R8 slightly smoothed highest fault
In this case, PV2-PV3 are disconnected at time t = 0 s . Without currents of, 16.05 kA, 6.51 kA, 6.46 kA, 2.86 kA, 11.83 kA, 16.04 kA,
BESS, R1-R8 have highest faults currents of, 17.65 kA, 7.61 kA, 7.53 kA, 7.13 kA and 2.67 kA, respectively, at 0.3 s for R4, R6 and R8, whereas at
2.96 kA, 10.80 kA, 11.8 kA, 11.66 kA and 16.25 kA, respectively, at 0.32 s for other relays in Fig. 18. Without BESS, R2 and R4 have
0.3 s and 0.34 s for R4 and R8, respectively, and at 0.32 s for other minimum faults currents of, 4.89 kA and 0.89 kA, respectively, at 0.3 s
relays in Fig. 15. for R2 and 0.32 s for R4 in Fig. 17. With BESS utilization, same relays
Here also the relays faults currents seem to have random variation have limited minimum faults currents of, 2.54 kA and 0.74 kA, re-
with noticeable more build up currents compared to the case with PV1. spectively, at cited same instants as shown in Fig. 18.
Relay R8 which has 2.91 kA with PV1, now sees 16.25 kA build up
current, whereas other relays have random decrease or increase in 6.5. PV1 and PV2 supplying 6.5 kV power each
faults currents. The model with BESS offers R1-R8 slightly smoothed
highest fault currents of, 16.59 kA, 6.75 kA, 6.70 kA, 3.05 kA, 10.9 kA, Lastly, PV2 and PV3 are connected and disconnected, respectively,
522
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
PV 1 PV 2 PV 1
0.27 kV/ 0.27 kV/ 0.27 kV/
30 kV 30 kV 30 kV
R1 R2 R3 R4 R1 R2 R3 R4
Fault 0.27 kV/ Fault 0.27 kV/ Fault Fault 0.27 kV/
30 kV 30 kV 30 kV
PV 3 PV 4 PV 4
(a) (b)
PV 1
PV 1 PV 2
0.27 kV/
30 kV 0.27 kV/ 0.27 kV/
30 kV 30 kV
R1 R2 R3 R4
R1 R2 R3 R4
(c) (d)
Fig. 8. PV dominated DSs case study systems: (a) PV1-PV4 connected (b) PV1 and PV4 connected (c) PV1 and PV3 connected (d) PV1 and PV2 connected.
at time t = 0 s . With no BESS, R1-R8 have highest fault currents of, Fig. 20. Without BESS, R2, R4, R6 and R8 have minimum faults currents
10.81 kA, 11.79 kA, 11.76 kA, 16.37 kA, 17.66 kA, 7.6 kA, 7.49 kA and of, 9.38 kA, 15.71 kA, 5.04 kA and 0.78 kA, respectively, at 0.3 s for R2,
2.94 kA, respectively, at 0.3 s for R8, whereas at 0.32 s for other relays 0.4 s for both R4 and R6, and at 0.32 s for R8 as depicted in Fig. 19.
in Fig. 19. However, based BESS application, the corresponding relays have lim-
Relay R4, which has 3.12 kA with PV1, now sees 16.37 kA build up ited minimum faults currents of, 8.53 kA, 15.5 kA, 4.33 kA and 0.78 kA
current, whereas other relays have random decrease or increase in fault respectively, at 0.3 s for R2 and R4, 0.4 s for R6 and 0.32 s for R8 in
currents. With PVs having BESS, R1-R8 have slightly smoothed highest Fig. 20.
fault currents of, 10.9 kA, 10.57 kA, 10.54 kA, 15.96 kA, 16.58 kA, Investigations revealed that relays mainly have highest faults cur-
6.76 kA, 6.68 kA and 2.83 kA, respectively, at 0.3 s and 0.34 s for R8 rents achieved at 0.32 s. That is, against high and low irradiations
and R4, respectively, whereas at 0.32 s for other relays, as shown in fluctuations, relays fault currents are in majority highest within 0.02 s
0.95k
0.93k
0.90k
0.88k
0.85k
0.82k
0.80k
Time(s) 0.300 0.320 0.340 0.360 0.380 0.400
523
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
600
Solar radiation (W/m^2)
500
400
300
200
Time(s) 0.300 0.320 0.340 0.360 0.380 0.400
20
R1
R2
Currents (kA)
15
R3
10 R4
5 R5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4
R8
Time (s)
Fig. 11. Relays maximum fault currents fluctuations with PV1 without BESS.
of fault duration. In addition, though faults currents variation is It may seem that BESS combined with employed control strategies
random, in majority we can observe a slight decrease in faults currents has positive effect on system dynamism to slightly smooth the time
profiles from 0.34 s to 0.4 s. Globally, the case with PV2-PV4 added to varying fault currents to minimum. These results could be improved
existing PV1 induced high fault currents compared to other cases with a more robust BESS. However, this paper BESS which has com-
showing similar performance at some instants. Importantly, the far the prehensive limited capability with few details provided, seems suffi-
relay the less the impact on its fault current with PV2-PV4 either con- cient to improve DC bus voltage and PV farm voltage quality, through
nected or disconnected at nodes 2–4, respectively. adjustment of voltage fluctuations, such as overshoot or undershoot,
Moreover, more in-depth results analyses, with high and low irra- and voltage sags and dips. Therefore, the use of batteries storage is
diations profiles, have shown that, although the impact of irradiation capable to enhance high PV connected DS performance.
fluctuation in time is slight, there seems to be slight build up currents at Results similarities are observed when fluctuating irradiation of
some instants. However, PVs connection and disconnection scenarios each of PV2-PV4, separately, by adopting same procedure clearly de-
induce more build up currents in presence of fault and non-uniform monstrated using PV1 as an example. That is, when varying respective
irradiation fluctuation. irradiation, each of PV2-PV4 impact is carried out firstly; then other
Another separate case study, on both DSs models, with results not PVs are connected to respective nodes secondly; followed with other
plotted here, revealed that, fault resistance higher than applied 0.3 ohm cases, proceeded for PV2 as, PV1 and PV4 disconnected whereas PV2
induces low relays fault currents, however, a resistance below 0.3 ohm and PV3 connected; PV1 and PV3 disconnected whereas PV2 and PV4
induces high fault currents. Moreover, against PVs connection and connected; and PV3-PV4 disconnected whereas PV1-PV2 in service etc.
disconnection, with impact depending on PVs locations and sizes, relays We conducted all those case studies but due to space limitation and
and grid faults currents fluctuations are proportional to fault resistance resemblance of results the details are not provided.
and so is the grid and transmission lines voltages drop. Importantly, considering both DS models and both irradiation
20
R1
R2
Currents (kA)
15
R3
10 R4
5 R5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4 R8
Time (s)
Fig. 12. Relays maximum fault currents fluctuations with PV1 using BESS.
524
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
20
R1
Currents (kA)
15 R2
10
R3
R4
5 R5
R6
0
0.3 0.32 0.34 0.36 0.38 0.4 R7
R8
Time (s)
Fig. 13. Relays maximum fault currents fluctuations with PV1-PV4 without BESS.
20 R1
R2
Currents (kA)
15
R3
10 R4
5 R5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4
R8
Time(s)
Fig. 14. Relays maximum fault currents fluctuations with PV1-PV4 using BESS.
20
R1
R2
Currents (kA)
15
R3
10 R4
5 R5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4
R8
Time (s)
Fig. 15. Relays maximum fault currents fluctuations with PV1 and PV4 without BESS.
20
R1
15 R2
Currents (kA)
R3
10 R4
5 R5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4
R8
Time(s)
Fig. 16. Relays maximum fault currents fluctuations with PV1 and PV4 using BESS.
20 R1
R2
Currents (kA)
15
R3
10 R4
R5
5
R6
0 R7
0.3 0.32 0.34 0.36 0.38 0.4 R8
Time (s)
Fig. 17. Relays maximum fault currents fluctuations with PV1 and PV3 without BESS.
525
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
20
R1
Currents (kA)
15 R2
10
R3
R4
5 R5
0 R6
0.3 0.32 0.34 0.36 0.38 0.4 R7
Time (s) R8
Fig. 18. Relays maximum fault currents fluctuations with PV1 and PV3 using BESS.
20
R1
R2
Currents (kA)
15
R3
10
R4
5 R5
R6
0
0.3 0.32 0.34 0.36 0.38 0.4 R7
R8
Time (s)
Fig. 19. Relays maximum fault currents fluctuations with PV1 and PV2 without BESS.
20
R1
Currents (kA)
15 R2
R3
10
R4
5 R5
0 R6
0.3 0.32 0.34 0.36 0.38 0.4 R7
Time (s) R8
Fig. 20. Relays maximum fault currents fluctuations with PV1 and PV2 using BESS.
526
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
PV1 frequency
freq1
62.5
60.0
50.0
47.5
45.0
42.5
40.0
Time(s) 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600
(a)
PV3 frequency
freq3
62.5
60.0
57.5
PV3 frequency (Hz)
55.0
52.5
50.0
47.5
45.0
42.5
40.0
37.5
Time(s) 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600
(b)
Fig. 21. PV systems frequency unbalance due to 0.3 ohm 3L-G faults: (a) PV1 frequency unbalance (b) PV3 frequency unbalance.
Table 1 Table 3
Main relays and Backup relays. TMS, PS and OT limits.
Main relay Backup relay Main relay Backup relay Parameters Minimum Maximum
setting (TMS ) , plug setting (PS ) and operating time (OT ) limits are
Table 2 defined in Table 3 where the number of particles population is fixed 30
PSO parameters.
as only 8 OCRs are involved in the proposed method. The objective is to
Number of Number of Weighting Minimum Maximum
find optimized relays settings and objective function (OF ) . OF re-
population iterations factors (same weighting weighting presents minimum value of total OT of relays. In fact, OF is the fitness
(maximum) value) function function value which should be optimized based constraints [15].
Optimized OCRs TMS and PS values are in Table 4 and Table 5, for
30 100 2 0.4 0.9
DSs with and without BESS, respectively. Although DS with BESS pre-
sents faults currents limited to minimum, the relays settings values are
variably random in presence of PV fluctuations in both tables.
527
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
Table 4
Optimized relays settings with BESS.
Relays PSO PV1 PSO PV1-PV4 PSO PV1 and PV4 PSO PV1 and PV3 PSO PV1 and PV2
1 0.71737 0.83002 0.48824 2.2807 0.8881 2.4692 1.0105 1.8983 0.47461 1.2434
2 0.21211 1.8077 0.66029 2.1382 0.80121 1.8765 0.73283 1.4543 0.12978 0.62842
3 0.53044 0.59691 0.52049 2.1519 0.54225 1.8801 0.6891 0.63727 0.35058 2.0409
4 0.32259 0.51946 0.20091 0.60024 0.14913 0.80138 0.407 0.57853 0.83156 0.82998
5 0.93576 0.74242 0.48412 0.60876 0.44332 0.83852 0.17728 0.72505 0.78627 1.1835
6 0.852 0.66236 0.46556 2.3105 0.70243 1.8081 0.32392 2.1898 0.24063 0.92035
7 0.67325 1.2858 0.26886 0.84709 0.13598 1.0033 0.49894 1.7352 0.22652 1.9304
8 0.9695 2.0814 0.36072 1.5688 1.0369 0.9147 0.46516 2.3373 0.68294 1.8345
OF (s) 5.6866 2.7589 4.0619 3.8603 3.9109
Time (s) 61.492 61.804 54.704 55.935 59.154
Table 5
Optimized relays settings without BESS.
Relays PSO PV1 PSO PV1-PV4 PSO PV1 and PV4 PSO PV1 and PV3 PSO PV1 and PV2
1 0.74912 1.8736 0.84452 0.6907 0.2872 2.4397 0.71895 0.75192 1.0436 1.6463
2 0.83172 0.86702 0.29379 0.62815 0.81632 1.9887 0.19211 1.0921 0.83724 2.2673
3 0.74775 1.237 0.55912 0.54391 0.23754 2.4816 0.44842 1.4001 0.44278 1.5148
4 0.55092 1.7512 0.30075 2.2016 0.13144 0.87124 0.5064 1.08 0.41655 0.75244
5 0.64701 2.0605 0.23847 0.62785 0.98149 0.6102 0.67948 1.4634 0.49881 1.0298
6 0.39632 0.66225 0.81622 2.169 0.36294 0.6553 0.22647 1.6821 0.51517 1.3078
7 0.84469 2.3588 0.3603 1.4745 0.58228 1.0138 0.32807 1.518 0.17435 0.50445
8 0.28896 2.0514 0.93653 1.7483 0.78373 2.4802 0.96289 0.82271 0.8374 0.54089
OF (s) 5.3774 2.6692 3.465 3.6397 4.2813
Time (s) 73.906 55.749 51.514 55.604 65.307
9
PSO with PV1-PV4 Without BESS
8
7
Fitness value
2
10 20 30 40 50 60 70 80 90 100
Iteration
Fig. 22. Fitness function evolution with PSO in case PV1-PV4 connected without BESS.
Large volatility and strong randomness are characteristics of PV OFs are 2.7589 s and 2.6692 s, respectively, whereas PSO algorithm
power. Limiting fault current to minimum as in this paper could be very spent 61.804 s and 55.749 s, respectively, to run the calculations.
profitable for protection systems. With PSO randomization character- Considering all the cases, PSO algorithm spent minimum and maximum
istics, it seems improper to compare relays settings of separate cases times of 51.514 s and 73.906 s, respectively. The fitness function evo-
among them. Nonetheless, a brief analysis is relevant. The reported lution with PSO in case PV1-PV4 connected without BESS is plotted in
results are the best solutions achieved over 100 times compilations of Fig. 22 showing best fitness value of 2.6692 s achieved after 17 itera-
100 iterations each, for each fluctuation case. tions. Other cases best fitness values are achieved variably between 10
From Tables 4 and 5, the optimized TMS and PS remained in spe- and 45 iterations. Because few relays and few constraints were in-
cified limits in each fluctuation case. However, there are no particular volved, PSO algorithm is able to respond in less than 100 s in each case.
similarities among TMS and PS results. On the other hand, there seems However, PSO is usually time consuming [15]. Importantly, in presence
to be slight similarities among OF values when comparing Tables 5 with of PV fluctuations, OF should be minimized to decrease the risk and
4. For instance, when PV1-PV4 connected with and without BESS, best stress on the protected zones.
528
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
imax
*
vdc + id*
PI 1
-
vdc
imin
imax
Q - PI 2 iq*
+ imin
Q*
Fig. 23. Voltage mode PQ control.
vd
+ + +
PI 6
- -
- +
PI 7 +
+ +v
q
Fig. 24. dq current control strategy.
vd
vabc abc vq wPLL θ
dq0
PI 8
∫
v0 ( neglected )
Appendix A. Appendix
The modeled voltage mode PQ control based Eq. (5) is in Fig. 23 where the discussed input and output signals are clearly depicted. The generated
529
B.S. Tekpeti et al. Electrical Power and Energy Systems 100 (2018) 517–530
id∗ and iq∗ reference currents in dq frame are further used as inputs of dq current control loop as clearly shown in Fig. 24.
The dq current control is to deliver appropriate dq frame reference voltages vd∗ and vq∗ which expressions are in (16). Referring to Fig. 24, (16) is
easily reachable.
∗
⎧ vd = vd + Δvd−wLiq
∗
⎨ vq = vq + Δvq + wLid (16)
⎩
∗ 1
⎧ Δvd = (id −id )(Kpd6 + Kid6 × s )
⎨ Δvq = (iq∗−iq)(Kpq7 + Kiq7 × 1
) (17)
⎩ s
where Δvd and Δvq in (17) are corresponding voltages of error in id and iq currents, respectively. The error in id is id∗−id
whereas the error L in iq is iq∗−iq .
is an inductance chosen from LCL filter for decoupling actions; w is grid supplied angular frequency; Kpb6 and Kib6 are PI6 proportional and integral
gains, respectively, whereas Kpb7 and Kib7 are PI7 proportional and integral gains, respectively.
PLL is a negative feedback control which role is to output appropriate grid phase angle. To achieve that, PLL transforms inverter ac voltages vabc
into dc dq control voltages (vd,vq) and dynamically proceeds adjustment of the rotational speed wPLL to fulfill vd = 0 and finally output the correct grid
phase angle θ . The modeled PLL technique is shown in Fig. 25.
Supplementary data associated with this article can be found, in the online version, at http://dx.doi.org/10.1016/j.ijepes.2018.03.003.
References [21] Datta Manoj, Senjyu Tomonobu, Yona Atsushi, Funabashi Toshihisa, Kim Ch-Hwan.
Photovoltaic output power fluctuations smoothing methods for single and multiple
PV generators. Curr Appl Phys 2010;10(2):S265–70.
[1] IEEE Recommended practice for utility interface of photovoltaic (PV) systems, IEEE [22] Shenglong Yu, Lijun Zhang, Iu Herbert HC, Fernando Tyrone, Kit Wong Po. A DSE-
Std 929–2000, 30 January 2000. based power system frequency restoration strategy for PV-integrated power systems
[2] IEEE guide for determining fault location on AC transmission and distribution lines, considering solar irradiance variations. IEEE Trans Ind Inform 2017;13(5):2511–8.
IEEE Std C37. 114™- 2014, IEEE Power and Energy Society. [23] Ghoddami Hamidreza, Yazdani Amirnaser. A mitigation strategy for temporary
[3] Paithankar YG, Bhide SR. Fundamentals of power system protection. New Delhi: overvoltages caused by grid-connected photovoltaic systems. IEEE Trans Energy
Prentice-hall of India Priviate Limited; 2003. Conver 2015;30(2):413–20.
[4] Sumathi S, Kumar LA, Surekha P. Solar PV and wind energy conversion systems. [24] Roumpakias Elias, Stamatelos Anastassios. Comparative performance analysis of
Green Energy Technol 2015:1–807. grid-connected photovoltaic system by use of existing performance models. Energy
[5] Chen Li-Hsiung. Overcurrent protection for distribution feeders with renewable Convers Manage 2017;150:14–25.
generation. Int J Electr Power Energy Syst 2017;84:202–13. [25] Danling Cheng, Mather Barry A, Richard Seguin, Joshua Hambrick, Broadwater
[6] Hernández JC, De La Cruz J, Vidal PG, Ogayar B. Conflicts in the distribution Robert P. Photovoltaic (PV) impact assessment for very high penetration levels.
network in the presence of large photovoltaic plants: the case of ENDESA. Inter IEEE J Photovoltaics 2016;6(1):295–300.
Trans Electr Energy Syst 2013;23(5):669–88. [26] Hossein Hooshyar, Baran Mesut E. Fault analysis on distribution feeders with high
[7] Elmitwally A, Gouda E, Eladawy S. Optimal allocation of fault current limiters for penetration of PV systems. IEEE Trans Power Syst 2013;28(3):2890–6.
sustaining overcurrent relays coordination in a power system with distributed [27] Baran Mesut E, Hooshyar Hossein, Shen Zhan, Huang Alex. Accommodating high
generation. Alex Eng J 2015;54(4):1077–89. PV penetration on distribution feeders. IEEE Trans Smart Grid 2012;3(2):1039–46.
[8] Liu Haoming, Peng Jianyu, Zang Qiyue, Yang Kelin. Control strategy of energy [28] Tekpeti BS, Kang X, Kheshti M. Particular PV grid-connected system under sym-
storage for smoothing photovoltaic power fluctuations. Int Feder Auto Control metrical and asymmetrical faults analysis. In: Electrical power and energy con-
2015;48(28):162–5. ference on 22–25 October 2017, Saskatoon, Canada. p. 1–6.
[9] Jayasekara Nadeeshani, Wolfs Peter, Masoum Mohammad AS. An optimal man- [29] Tekpeti BS, Kang X, Kheshti M. Fault analysis of accurate PV connected system
agement strategy for distributed storages in distribution network with high pene- against dynamic fast solar radiation fluctuation. In: Electrical power and energy
trations of PV. Electr Power Syst Res 2014;116:147–57. conference on 22–25 October 2017, Saskatoon, Canada. p. 1–6.
[10] Wang X, Yue M, Muljadi E. Modeling and control system design for integrated solar [30] Firouz Y, Farhadkhani S, Lobry J, Vallee F, Khakpour A, Durieux O. Numerical
generation and energy storage system with a ride-through capability. In: Energy comparison of the effects of different types of different types of distributed gen-
conversion conference and exposition on 15–20 September 2012, Raleigh, North eration units on overcurrent protection systems in MV distribution grids. Renewable
Carolina. p. 3727–34. Energy 2014;69:271–83.
[11] Fiodar Kazhamiaka, Catherine Rosenberg, Srinivasan Keshav. Practical strategies [31] Kobayashi Hiromu, Takigawa Kiyoshi. A new protective method for grid connected
for operation in energy systems: design and evaluation. IEEE Trans Sustain Energy dispersed PV systems to detect short circuit fault in distribution line. Sol Energy
2016;7(4):1602–10. Mater Sol Cells 1997;47(1–4):117–23.
[12] Daud MZ, Mohamed A, Wanik Che MZ, Hannan MA. Performance evaluation of [32] Conti Stefania, Nicotra Sebastiano. Procedures for fault location and isolation to
grid-connected photovoltaic system with battery energy storage. In: International solve protection selectivity problems in MV distribution networks with dispersed
conference on power and energy on 2–5 December 2012, Kota Kinabatu Sabah, generation. Electr Power Syst Res 2009;79(1):57–64.
Malaysia. p. 337–42. [33] Gimenez Ledesma Jorge Javier, de Araujo Leandro Ramos, Ribeiro Penido Debora
[13] Olabi AG. Renewable energy and energy storage systems. Energy 2017;136:1–6. Rosana. A method for evaluation of overcurrent protection in unbalanced dis-
[14] Yongheng Yang, Frede Blaabjerg, Huai Wang. Low-voltage ride through of single- tribution systems. Int Trans Electr Energy Syst 2016;26(2):412–28.
phase transformerless photovoltaic inverters. IEEE Trans Ind App [34] Tremblay Olivier, Dessaint Louis-A, Dekkiche Abdel-Illah. A generic battery model
2014;50(3):1942–52. for dynamic simulation of hybrid electrical vehicles. In: Vehicle power and pro-
[15] Kheshti M, Tekpeti BS, Kang X. The optimal coordination of overcurrent relay pulsion conference on 9–12 September 2007, Arlington, Texas. p. 284–89.
protection in radial network based on particle swarm optimization. In: IEEE PES [35] Muhamad DZ, Azah M, Hannan HA. Optimization of PI compensator parameters for
Asia-Pacific power and energy conference on 25–28 October 2016, Xi’an, China. p. grid-tied photovoltaic with energy storage systems using simplex algorithm. Int Rev
604–8. Model Simulat 2012;5(2):751–60.
[16] Saad Naggar H, El-Sattar Ahmed A, Mansour Abd El-Aziz M. Improved particle [36] Chabanloo RM, Mohammadzadeh N. A fast numerical method for optimal co-
swarm optimization for photovoltaic system connected to the grid with low voltage ordination of overcurrent relays in the presence of transient fault current. IET Gener
ride through capability. Renewable Energy 2016;85:181–94. Transm Distrib 2018;12(2):472–81.
[17] Subhashish Bhattacharya, Tapan Saha, Hossain MJ. Fault contribution from large [37] Shih MY, Conde A, Leonowicz Z, Martirano L. An adaptive overcurrent coordination
photovoltaic systems in building power supply networks. J Build Eng scheme to improve relay sensitivity and overcome drawbacks due to distributed
2016;5:222–30. generation in smart grids. IEEE Trans Indus Appl 2017;53(6):5217–28.
[18] Hossain MJ, Saha TK, Mithulananthan N, Pota HR. Robust control strategy for PV [38] Salem MM, Elkalashy NI, Atia Y, Kawady TA. Modified inverter control of dis-
system integration in distribution systems. Appl Energy 2012;99:355–62. tributed generation for enhanced relaying coordination in distribution networks.
[19] Lal Nandan Vivek, Singh SN. Control and performance analysis of a single-stage IEEE Trans Power Deliv 2017;32(1):78–87.
utility-scale grid-connected PV system. IEEE Syst J 2017;11(3):1601–11. [39] Fani B, Hadi Bisheh, Karami-Horestani A. An offline penetration-free protection
[20] Nejib Hamrouni, Moncef Jraidi, Ahmed Dhouib, Adnen Cherif. Design of a com- scheme for PV-dominated distributed systems. Electr Power Syst Res 2018;157:1–9.
mand scheme for grid connected PV systems using classical controllers. Electr
Power Syst Res 2017;143:503–12.
530