4 Lighting circuits
More recently, hybrid technology devices have been developed that combine
a solid state switch (activation on voltage passage through zero) and an
electromechanical contactor short-circuiting the solid state switch (reduction of
losses in the semiconductors) (see Fig. N68).
For three-phase circuits (power supply of luminaires between a phase conductor
and the neutral conductor), switchgear and controlgear of the three-pole type is
preferable to a control device of the four-pole type. Not switched the neutral pole
will help to prevent a harmful voltage surge at power frequency from being applied
across the terminals of the luminaire if the neutral conductor fails to close.
4.3.4 Overvoltages
The risk
As illustrated in earlier sections, switching on a lighting circuit causes a transient
state which is manifested by a significant overcurrent. This overcurrent is
accompanied by a strong voltage fluctuation applied to the load terminals
connected to the same circuit.
These voltage fluctuations can be detrimental to correct operation of sensitive
loads (micro-computers, temperature controllers, etc.)
The Solution
It is advisable to separate the power supply for these sensitive loads from the
lighting circuit power supply.
The installation of protective devices such as “surge arrester” type is recommended
for exposed installations such as public lighting, lighting for car park, or industrial
facilities.
DB422686_EN.eps
DB422687_EN.eps
60 100 120
Maximum number of luminaires
90
50 100
80
70 80
40
60
30 50 60
40
20 40
30
20
10 20
10
0 0 0
10 30 50 75 150 10 30 50 75 150 10 30 50 75 150
Luminaire power (W) Luminaire power (W) Luminaire power (W)
Curve B N33
DB422688_EN.eps
Curve C
Curve D
Curve B, C, D with iCT+ (or iTL+ up to 16 A)
Fig. N48 Maximum number of lamps according to the circuit breaker rating and curve, for LED lamps
N49