INSTALLATION OF SPRINKLER SYSTEMS
‘Table 17.4.2.1(a) Maximum Distance Between Hangers (ftin.)
‘Nominal Pipe Size (in.)
% 1 % Wm 2 % 8 % 4 5 6 8
Steel pipe except threaded lightwall | NA 120 120 150 150 150 150 150 150 150 150
‘Threaded lighowall steel pipe NA 120 120 120 120 120 120° NA NA NA NA
Copper tube 80 80 100 100 120 120 120 150 150 150 150.
eve 56 60 66 70 8D 99 100 NA NA NA NA
Dactileiron pipe NANA NA NANA NA 150 NA 150 NA. 150.
‘NA Not applicable
‘Table 17.4.2.1(b) Maximum Distance Between Hangers (m)
Nominal Pipe Size (mam)
2 2 = +4 50 68 80 90 100-425 ~«150~—-20
Steel pipe except threaded ighwall | NA 37 37 46 46 46 46 46 46 4646
‘Threaded lightwall steel pipe NA 370 370 37 37 37 37 NA NA NANA
Copper tube 24 24 380 BOT T8746 46 45 46
eve L718 20 21 24 27 30 NA NA NANA
Dactleiron pipe NANA NANA NA _NA_46 NA, NA 46 46
NA; Not applicable,
17.4.34¢ Unsupported Lengths
1744.1. For steel pipe, the unsupported horizontal length
between the end sprinkler and the last hanger on the line shall
not be greater than 36 in, (900 mm) for 1 in, (25 mm) pipe,
48 in. (1.2 m) for 1% in. (32 mm) pipe, and 60 in. (1500 m) for
UGin, (40 mm) or larger pipe.
1743.42 For copper tube, the unsupported horizontal
length between the end sprinkler and the last hanger on the
line shall not be greater than 18 in. (450. mm) for I in
(25 mm) pipe, 24 in. (600 mm) for 1% in. (82 mm) pipe, and.
30 in. (750 mm) for 1% in. (40 mm) or larger pipe.
17343 Where the limits of 17.4341 and 174342 are
‘exceeded, the pipe shall be extended beyond the end sprinkler
and shall be supported by an additional hanger.
1743.44 Unsupported Length with Maximum Pressure
Exceeding 100 pst (6.9 bar) and Branch Line Above Ceiling
‘Supplying Sprinklers in Pendent Position Below Ceiling.
174344. Where the maximum static or flowing pressure,
whichever is greater at the sprinkler, applied other than
through the fire department connection, exceeds 100 psi (6.9
bar) and a branch line above a ceiling supplies sprinklers in a
pendent position below the ceiling, the hanger assembly
supporting the pipe supplying an end sprinkler in a pendent
position shall be of a type that restrains upward movement of
the pipe,
1743.44.2 The unsupported length between the end sprin-
kler in a pendent position or drop nipple and the last hanger
fon the branch line shall not be greater than 12 in, (300 mm)
for steel pipe or 6 in. (150 mm) for copper pipe.
I7ASAA3 When the limit of 17.43.4429 is exceeded, the
pipe shall be extended beyond the end sprinkler and suppor
ted by an additional hanger
2019 Eaton
ITASAAA Unless flexible hose fittings in accordance with
174133.1 and ceilings in accordance with 17.41.8322 are
used, the hanger closest to the sprinkler shall be of a type that
restrans the pipe from upward movement,
17.4.8.5* Unsupported Armover Length.
I7A3.5.1 The cumulative horizontal length of an unsuppor-
ted armover to 2 sprinkler, sprinkler drop, or sprig shall not
exceed 24 in, (600 mm) for steel pipe or 12 in. (300 mm) for
capper tube,
17.43.5.2° Unsupported Armover Length with Maximum
Pressure Exceeding 100 psi (6.9 bar) and Branch Line Above
Ceiling Supplying Sprinklers in Pendent Position Below Ceil:
ing.
1743.5.2.1 Where the maximum static or flowing pressure,
whichever is greater at the sprinkler, applied other than
trough the fire deparument connection, exceeds 100 psi (6.9
bar) and a branch line above a ceiling supplies sprinklers in a
pendent position below the ceiling, the cumulative horizontal
length of an unsupported armoxer to a sprinkler or sprinkler
drop shall not exceed 12 in, (300 mm) for steel pipe and 6 in,
(150 mam) for copper tube.
1743.5.22 Unless flexible sprinkler hose fitings in accord
ance with 17.4.1.3.3.1 are used, the hanger closest to the sprit
ler shall be of a type that resirains upward movement of the
pipe.
174.3.5.2.3 Where the armover exceeds the maximum ansup-
ported length of 17.4.3.52.1, a hanger shal be installed so that
the distance from the end sprinkler or drop nipple to the
hhanger is not greater than 12 in, (300 mm) for steel oF 6 in.
(150 mm) for copper, or the pipe shall be extended beyond,
the end sprinkler and shall be supported by an additional
hanger,
174.3.6* Wall mounted sidewall sprinklers shall be restrained,
to prevent movement.