You are on page 1of 16

Supersedes: 160.52-PW3 (797) Form 160.

52-PW3 (1098)

WIRING DIAGRAM, MILLENNIUM


MODEL YK (STYLE D) LIQUID CHILLERS
PRODUCT DRAWING
MICROCOMPUTER CONTROL CENTER
YORK INTERNATIONAL CORPORATION
P.O. Box 1592, York, PA 17405
WITH VARIABLE SPEED DRIVE
CONTRACTOR _______________________ PURCHASER ____________________________________________
ORDER NO. __________________________ JOB NAME _______________________________________________
YORK CONTRACT NO. _________________ LOCATION _______________________________________________
YORK ORDER NO. ____________________ ENGINEER ______________________________________________

REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE _________

JOB DATA:

CHILLER MODEL NO. YK ________________________________________________________


NO. OF UNITS _____________
COMPRESSOR MOTOR ______________ VOLTS, 3-PHASE, _____________ Hz
OIL PUMP MOTOR _____________ VOLTS, 3-PHASE, _____________ Hz, _____________FLA

REMARKS:
2
REV. 035-15979 (REV. B)
ELEMENTARY DIAGRAM

YORK INTERNATIONAL
FORM 160.52-PW3 FORM 160.52-PW3

FOR ADAPTIVE CAPACITY


SEE PAGES 12 & 13

LD03445
LD03454
* Function provided by condenser transducer.
** See operator’s manual for a detailed description of low oil pressure and high oil flow shutdowns.

Applicable if unit was shut down for 30 mins. or less.
††
Applicable if unit was shut down for greater than 30 mins.

14 YORK INTERNATIONAL YORK INTERNATIONAL 3 YORK INTERNATIONAL 3A


FORM 160.52-PW3 FORM 160.52-PW3

ELEMENTARY DIAGRAM (Cont’d)

TIMING DIAGRAM
LD03446

LD03453

LD03447

YORK INTERNATIONAL 3B 4 YORK INTERNATIONAL YORK INTERNATIONAL 13


FORM 160.52-PW3

LEGEND

LD03448

NOTES:

1. This wiring diagram describes the standard electronic Note 7). A remote start S-33P switch may be con-
control scheme for use with a YORK VSD. For de- nected to terminals 1 , 7 and 8 (Lines 32 & 33) (See
tails of standard modifications, refer to Product Form Note 7). Remote start-stop switch (Line 32) is op-
160.49-PW13. erative only in the “remote” operating mode.

2. Field wiring to be in accordance with the National 7. Device contact rating to be 5 milliamperes at
Electric Code as well as all other applicable codes 115VAC.
and specifications. See Product Form 160.49-PW10
for field wiring connections. 8. Contact rating is 5A resistive @ 120VAC or 240VAC.

3. Numbers along the left side of the diagram are line 9.


identification numbers. The numbers along the right
10. For Wiring Diagram of V.S.D., refer to Product Form
side indicate the line number location of relay con-
160.00-PW1, 160.00-PW2, or 160.00-PW3.
tacts. An underlined contact location signifies a nor-
mally closed contact. 11.
4. Main Control Panel Class I field wiring terminal con- 12. Run contact (TM) on V.S.D. Logic Board is set to
nection points are indicated by numbers within a trip at 105% FLA.
rectangle, i.e. 15 . Main control panel factory wiring
terminal connection points are indicated by num- 13. Contact rating is 5 amps resistive @ 250VAC &
bers within a triangle, i.e. 5 . Control terminal mark- 30VDC, 2 Amp inductive ( .4 PF) @ 250VAC &
ings are indicated by numbers within a circle, i.e. 30VDC.
C1. Numbers adjacent to circuit lines are the circuit
identification lines. 14. Field connected control power supply is not required,
as control transformer is supplied on the VSD.
5. To cycle unit off and on automatically with contacts
other than those shown, install a cycling device be- 16. Each 115VAC field-connected inductive load: i.e.
tween terminals 1 and 13 (Line 37) (See Note 7). If a relay coil, motor starter coil, etc. shall have a tran-
cycling device is installed, jumper must be removed sient suppressor wired in parallel with its coil, physi-
between Terminals 1 and 13 . cally located at the coil. Spare transient suppres-
sors and control circuit fuses are supplied in a bag
6. To stop unit and not permit it to start again, install a attached to the top of the hinged panel.
stop device between terminals 1 & 8 (Line 33) (See

YORK INTERNATIONAL 5
CONNECTION DIAGRAM

6 YORK INTERNATIONAL
FORM 160.52-PW3

LD03449

(CONTINUED ON PAGES 8 & 9)

YORK INTERNATIONAL 7
CONNECTION DIAGRAM (Cont’d)

8 YORK INTERNATIONAL
FORM 160.52-PW3

LD03450

YORK INTERNATIONAL 9
WIRING FOR 230V AND 460V UNITS

LD03457

10 YORK INTERNATIONAL
FORM 160.52-PW3

WIRING FOR 346V AND 600V UNITS

LD03458

YORK INTERNATIONAL 11
12 YORK INTERNATIONAL
FORM 160.52-PW3 FORM 160.52-PW3

ELEMENTARY DIAGRAM (Cont’d)

TIMING DIAGRAM
LD03446

LD03453

LD03447

YORK INTERNATIONAL 3B 4 YORK INTERNATIONAL YORK INTERNATIONAL 13


FORM 160.52-PW3 FORM 160.52-PW3

FOR ADAPTIVE CAPACITY


SEE PAGES 12 & 13

LD03445
LD03454
* Function provided by condenser transducer.
** See operator’s manual for a detailed description of low oil pressure and high oil flow shutdowns.

Applicable if unit was shut down for 30 mins. or less.
††
Applicable if unit was shut down for greater than 30 mins.

14 YORK INTERNATIONAL YORK INTERNATIONAL 3 YORK INTERNATIONAL 3A


FORM 160.52-PW3

OIL PUMP MOTOR OIL PUMP FUSING


FULL DUAL
VOLTS-PH-HZ LOAD ELEMENT
AMPS FUSE SIZE*
440-3-60 3.5 7
460-3-60 3.3 7
480-3-60 3.2 7
* Oil pump motor supply fuses located in Variable Speed Drive.

YORK INTERNATIONAL 15
Proud Sponsor
of the 1998
U.S. Olympic Team

36USC380

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 1998 ALL RIGHTS RESERVED

Form 160.52-PW3 (1098)


Supersedes: 160.52-PW3 (797)