Professional Documents
Culture Documents
16 Structural Design
16 Structural Design
1603.1.7 Replace ‘on the community’s Flood Insurance Rate Map (FIRM)’ with ‘of the base flood elevation’.
16.00: continued
16.00: continued
16.00: continued
1605.3.2 Delete.
Table 1607.1 Item 30. Revise ‘Classroom’ uniform loading as follows: 50 psf
16.00: continued
1607.9.2 Delete.
1608.3 Concave Curved Roofs. Section 7.4.3 of ASCE 7 applies to convex curved roofs only.
The effective loaded area of a concave curved roof shall be that area of the surface of the roof
where the tangents to the surface have a slope of 50 degrees or less. The total uniform snow load
for concave curved roofs shall be Pƒ multiplied by the total horizontal projected area of the roof.
This total load shall be applied uniformly over the effective loaded area of the roof.
1608.4 Drifts on Multiple Level Roofs. For multiple stepped roofs similar to that shown in
Figure 1608.4.1, the sum of all the roof lengths upwind above the drift under consideration, lu*,
in Figure 1608.4.1, shall replace lu in Figure 7-8 of ASCE 7. For multiple level roofs similar to
that shown in Figure 1608.4.2, if the total calculated height of a drift and the underlying uniform
snow layer on the upwind side of a higher roof (hd + hb) is equal to or greater than 0.7(hb + hc),
then the length, lu*, as shown in Figure 1608.4.2, shall be used in place of lu in Figure 7-8 of
ASCE 7.
FIGURE 1608.4.1
FIGURE 1608.4.2
16.00: continued
1608.5 Very High Roof Separations. When the ratio hr/LT is greater than 1.0, where LT is the
dimension in feet of the upper roof perpendicular to the wind flow (perpendicular to lu in Figure
7-8 of ASCE 7) and hr = hb + hc, the drift surcharge load on the lower roof due to drifting of snow
from the upper roof may be reduced. The reduced height of the drift surcharge, hdr, shall be not
less than: hdr = hr (2 - hr/LT), except that when hr/LT is greater than 2.0, hdr shall be equal to zero.
1608.6 Snow Pockets or Wells. Account shall be taken of the load effects of potentially
excessive snow accumulation in pockets or wells of roofs or decks.
1608.7 Roof Projections. The term roof projections used herein and in section 7.8 of ASCE 7
shall be interpreted to include screen walls, parapets, fire wall projections, and mechanical
equipment. Drift loads at roof projections shall be in accordance with section 7.8 of ASCE 7.
1608.8 Sliding Snow. In addition to the sliding snow load on a lower roof as required in section
7.9 of ASCE 7, the lower roof shall be designed for a windward drift surcharge at the wall
separating the upper and lower roofs in accordance with Figure 1608.4.1 and section 7.8 of
ASCE 7. The sliding snow load and the windward drift surcharge need not be considered to act
concurrently.
1608.9 Snow Guards. Sliding snow from an adjacent sloping high roof need not be considered
on the low roof if snow guards, as specified herein, are provided on the high roof. In this case,
the sloping roof with snow guards shall be designed for the unit snow loads required for a flat
roof. The roof area(s) requiring snow guards shall be indicated on the construction documents.
Snow guards shall be designed by a registered design professional. The registered design
professional shall insure that there are adequate load paths from the snow guards into the
supporting members and from the supporting members into the primary structure. The structural
design of snow guards shall account for the impact of the sliding snow. The effectiveness in
preventing the sliding of snow of proprietary snow guard systems shall be demonstrated by tests.
1608.10 Snow Storage and Collection Areas. Consideration of potentially excessive snow
accumulation shall be given to portions of structures designated or used as snow collection or
storage areas during and after snow removal operations (e.g. temporary snow collection areas
when mechanically removing snow from a roof; snow storage areas for parking structures).
16.00: continued
where SS is the maximum considered earthquake spectral response acceleration from Table
1604.11, Fa is the site coefficient from Table 1613.5.3(1), ãt is the total unit weight of the
soil, and H is the height of the wall measured as the difference in elevation of finished
ground surface or floor in front of and behind the wall. The earthquake force from the
backfill shall be distributed as an inverted triangle over the height of the wall.
Surcharges that are applied over extended periods of time shall be included in the total
static lateral soil pressure and their earthquake lateral force shall be computed and added to
the force determined above. The point of application of the earthquake force from extended
duration surcharge shall be determined on an individual case basis.
If the backfill or the existing soil behind the backfill consists of loose saturated granular
soil, the potential for liquefaction of the backfill or existing soil adjacent to the wall during
seismic loading shall be evaluated in accordance with the requirements of section 1806.4.
If the backfill or existing soil beyond the backfill is potentially subject to liquefaction, the
increase in design lateral load on the foundation wall or retaining wall shall be determined
by a registered design professional.
For wall strength design, a load factor of 1.43 shall be applied to the earthquake force
calculated above.
1612.1 At the end of the first sentence add this text: ‘in accordance with this section and Appendix G.’
COASTAL WETLAND RESOURCE AREA. Any coastal wetland resource are a subject to
protection under the Wetlands Protection Act, M.G.L. c. 131, § 40, and the Wetlands Protection
Act regulations, 310 CMR 10.21 through 10.35. Coastal Wetland Resource Areas include barrier
beaches, coastal beaches, coastal dunes, rocky intertidal shores, tidal flats, land subject to 100
year coastal storm flowage, coastal banks, land containing shellfish, lands subject to tidal action,
and lands under an estuary, salt pond or certain streams, ponds, rivers, lakes or creeks within the
coastal zone that are anadromous/catadromous fish runs.
1612.3 Replace text with ‘See section 1612.2 for flood hazard areas’.
16.00: continued
16.00: continued
Note. Seismic design category A shall not be used in Massachusetts. Any structure that
could satisfy the requirements of seismic design category A in section 1613 or ASCE 7 shall
be assigned to seismic design category B for purposes of implementing this Code.
16.00: continued
Note 1. Permitted only at exterior walls and fire-rated walls and not permitted for buildings
in Occupancy Category IV and not permitted for buildings where the dead load of any
laterally supported floor or roof exceeds 25 psf.
Note 2. Connections shall be designed for two times the computed forces and moments
resulting from seismic loads, in combination with other loads, as applicable, but need not be
designed for forces greater than the expected nominal yield strength (RyFyAg) of diagonal
braces in braced frames or 1.1 times the expected flexural capacity of beams (1.1RyMp) in
moment frames. Columns that are part of the seismic force-resisting system shall satisfy the
requirements of section 8.3 Column Strength of ANSI/AISC 341 Seismic Provisions for
Structural Steel Buildings. K-Braced Frames shall not be permitted. Beams in V-Type and
Inverted V-Type Braced Frames shall meet the following additional requirements:
a. A beam that is intersected by braces shall be continuous between columns.
b. A beam that is intersected by braces shall be designed to support the effects of all
tributary dead and live loads from load combinations stipulated by the Building Code,
assuming that braces are not present.
c. Top and bottom flanges of the beam at the point of intersection of braces shall be
designed to support a horizontal force perpendicular to the longitudinal axis of the beam
that is equal to 2% of the nominal beam flange strength: Fybf tbf.