é Workshop on
a sTransportatlog of OIL & GAS through Pipelines:
PRESENTATION ON
WMresicrccion Facilities,
=
Emergency Response Plan” ”
Hydrocarbon Fire fighting > f
Hazards and accident ww
M. a DWIBEDYFLOW OF PRESENTATION
{cia
Hanan and accident potentials
What is Hazard
+ Why to know about hazard
Kind of hazard
+ Special Risks Association with pipeline
transportation
+ Management control of hazards
Fire Protection Facilities
Basics of fire
+ Fire extinction principle
+ Types of fire protection facilitiesWhat is Hazard
{nda
+ Untoward incidents hidden behind the curtain of reality are
called hazard.
+ Unexpected events having damage potential for man or
machine or property.
+ Hazard is the potential to cause harm.
+ Ahazard is a situation in the workplace that has the potential to
harm the health and safety of people or to damage plant and
equipment.Why to Know about the hazard
1120 ey
lf not handled properly they will result in
accident/ disaster etc.
*To eliminate accidents.
*To minimise occurrence of accidents.
*To control the loss and damage that an accident
may cause.
*To provide various protection measures to safe
guard man and machine.Kind of Hazards
{nda
A. Material
|. Alkali, Acid
Il. Toxic Materials
lll. Explosive materials
B. Conditions
|. Hanging loads
Il. Slippery surfaces
Ill. Rotating machinesKind of Hazards
nian
C. Energy
i. Heat due to Steam, Flame, Fire
Electricity
iii. Noise
iv. UV radiation, cosmic rays, atomic radiation
D. Activities
i. Vehicle races
ii. Overhead construction
iii. Swimming in sea and high current rivers
iv. Sky divingKind of Hazards
{nda Oi
E. NATURAL
i. Lightning,
ii. Earth quake
iii. Flood
iv. Cyclone
F. HUMAN ELEMENT
i. Presence of enemy
ii. Lack of knowledge
iii. Wrong attitude
iv. Negligence
v. Adamant, egoistic , saboteursSpecial Risks Association with
= pipeline Transportation
e Highly Inflammable hazardous material is handled.
e High Pressure encountered in the process.
e Ignition from outside on Leakage from System.
e Loss of Containment/Accidental Releases.
« Inapproachability to the leakage site to control the
fire/Accident.
¢ Restoration takes considerable time.
¢ Pollution of environment
« Payment of huge compensationManagement Control of Hazard
+Safe guarding all machines,
equipments, work space etc.
+Reetifying or _ preventing
defective conditions.
*Suitable & safe design &
construction
*Safe arrangements, processes,
methods of work ete.
+ Suitable illumination
+ Ventilation
+PPEs
+ Job safety Analysis
+Inyestigation of
accidents
+Inspection of Plant
& equipments
+ Recording &
tabulation of data
+ Analysis of data
q
«Personal Adjustment
*Safety Education
and training
+Supervision
Self disciplineindianOil
What is Fire
An exothermic reaction resulting from
combination of heat fuel and oxygen.
Fire involves rapid oxidation at high
temperatures accompanied by the evolution
of highly heated gaseous products of
combustion and emission of visible and
invisible radiation.
Initiation of fire requires combustible
materials, oxygen and an energy source
(heat) to provide ignition. Three components -
fuel , oxygen & heat are referred as the fire
triangle
Am
FUELClassification of Fire
1120 ey
Class-A - Fires involving ordinary combustible materials
like wood,paper,textiles,rubber etc.
Class-B -Fires involving flammable liquids or liquefiable
solids, such as oils, solvents, petroleum products,paints,
varnishes etc.
Class-C - Fire involving gases or liquefied gases under
pressure for eg. LPG, Hydrogen etc.
Class-D Fire involving combustible metal such as
Magnesium, sodium Zinc, Titanium etc.Classification of Petroleum Product
(hia O
Petroleum Products are divided in to following
classes
= ClassA - Flashpoint < 23 deg.C
= ClassB - Flash point > 23 degC &< 65 degC
= Class C - flash point > 65 degC & < 93 deg.C
= Unclassified : flash point> 93 deg.c and aboveImportant Properties of Petroleum Product
116200 ey
For all flammable liquids, it is the vapour which burns and not the
liquid.
Flammable vapour burns only when mixed with proper percentage
of oxygen as support of combustion.
Flammable limits of petroleum products roughly lies between
slightly greater than 1% and less than 10%.
Petroleum vapour is heavier than air so it has tendency to discend
on ground or lower level or sump.
Petroleum is immiscible with water. Its specific gravity is less than
1, so they float on water
Electric conductivity of almost all petroleum products ( except
crude oil, ethanol etc.) is very low and hence it generates static
electricity during storage and transportationPrinciple of fire Extinction
Indianoit
Starvation - Removing or blanketing the fuel
Smothering - Cutting off or diluting the oxygen supply
Cooling - Removing heat from the fire.
4h
y \Different Agents to Fire Fire
+ Blanketing
+» Water
Steam
“+ Chemical foam
« Carbon dioxide
«+ Dry Chemical Powder
«+ Aqueous Film Forming Foam ( AFFF)Class of
Fire
A
Description
Fires involving ordinary combustible
materials such as wood, paper, textiles
etc.
Fires involving flammable liquids like
oils, petroleum products, paints
varnishes etc.
Fires involving gaseous substances
such as LPG, Hydrogen etc.
Fires occurring in Combustible metals
such as Sodium, Potassium,
Magnesium, Zinc etc.
Extinguishing
media
Water
Foam, Dry chemical
Powder,Carbon Dioxide.
Dry Chemical Powder
Carbon Dioxide.
Special Dry Powders
such as Ternary
Eutectic ChlorideFire Protection Facilities in
IndianOil
Fire Protection Facilities
Fire Detection Fire FightingAutomatic Fire Detection System
{nda
“+ Smoke- Ionisation or Optical type
* Heat — Fixed temperature or rate of rise
temperature type
“> Flame — UV or IR or UV/IR or IR?
«+ Heat And Smoke — Multiple criteriaAutomatic Fire Detection System
(2
*» Detection system can be conventional type, addressable type and
analog addressable type.
* Selection of detection system is carried out based on specific
requirement of industry.
«> Conventional -
> Detectors are in zones with max. 30 devices
+ Addressable -
> Detectors are in loop with max. 198 devices per loop, each device
has an address.
¢ Analog addressable -
+ Same as addressable with ability to send actual value of smoke
particle/ tepmarature etc. in the chamber of each detectorAutomatic Fire Detection System
(2
Advantages of analog addressable detectors over
conventional type of detectors
-Each device has an unique address and location can be
easily identified
» All signals are verified and no chance of false alarm
» Exact location is pin pointed rather than area
» Single loop comprises of 198 devices connected by 2 core
cable.
- All devices connected to the fire alarm panel are scanned
by the panel all the time. All the devices report their
condition to the panel.Automatic Fire Detection System
(hia ee
Modification is simpler. The device only needs to be
added to the existingloop with a minimum change in panel
software.
«History of each device can be seen by means of a printout.
eEasier maintenance. Device itself indicates about
maintenance.
«Lesser cable length.
«Lower power consumption.
«Compact & elegant design.Automatic Fire Detection System
Block Diagram for Automatic Fire Detection and CO2 Release systemAutomatic Fire Detection SystemAutomatic Fire Detection System
(2Schematic Layout of CO, systemFire Fighting System
(2
> Fire Water Reservoir
* Pumping units
“> Fire water Network
+ Fire hydrants and foam cum water monitor
«Water spray system
“*Foam pourer system
+» Automatic rim seal fire protection systemFire Water Reservoir
INO a
“ Open water reservoirs dedicated for storage of fire
water requirement of minimum 4 hrs. fire fighting
capability.
>» Open top pond with RCC wall all sides.
* Above ground fire water tanks of adequate nos. to
meet the norm of 4 hr. continuous fire fighting.
> Coned roof or open top above ground tanksFire Water Reservoir
Peerekern ne kecuct cl
eadFire Fighting Pumping units
(2
“ Motor or engine driven pumping units dedicated for
supply of fire water to
+ Pumping units may be vertical turbine type or
horizontal type.
‘No. of pumps shall be based on design pumping
requirement.
“ Standby pumping units for facilitating maintenance
without compromising safety of the installation.Fire Fighting Pumping units
IndianOit
Horizontal Motor Driven
pump( Jockey)
Engine driven pump
(horizontal)
Vertical Turbine type pump( Motor driven)Fire Water Network
11620 ey
MOC of network may be carbon steel or composite material or its
equivalent if used for fresh water.
Incase of saline, brakish water, steel pipes, internally cement,
mortar lines or glass reinforced epoxy, coated or pipes made of
material suitable for the quality of water shall be used.
Shall be laid above ground and under ground only in case of
crossings/ other unavoidable circumstances.
The fire water network shall be laid in closed loops as far as
possible to ensure multi-directional flow in the system.
The hydraulic analysis of network shall be done at the design time.Fire Water Network-Typical schematic
[6 TS),Fire Hydrants and Monitors
16 ee
* Fire hydrants and foam cum water monitors to be provided on
the fire water network.
* Inter distance shall not be more than 30 m.
* Monitors shall be provided with individual isolation valve.
* Distance of hydrants from tanks or equipment under protection
shall not be less than 15 m.
* Monitors shall be provided with individual isolation valve.Water Spray System
IndianOil
+ V
System consists of fixed piping with pipe fittings, isolation
valves, NRV and water spray nozzles.Water Spray System-Schematic
(2Water Curtain system in BuildingFoam Pourer System
{nda
“ Semi-fixed foam Pourer system
>» Comprises of fixed pipings and pipe fittings, drain valves,
foam coupling, foam makers, foam pourer and deflector plate
on tank.
>» Mobile Foam tender is required for actuating the system.
« Fixed foam pourer system( Manual/Automatic)
>» Manual system comprises of fixed foam concentrate storage
shed, foam supply pumps, proportioning system, pipings and
pipe fittings, isolation valves, drain valves, foam coupling,
foam makers, foam pourer and deflector plate on tank.
> Automactic system requires motor operates valves at
different points and PLC for its actuation based on feed back
from automatic fire detection and alarm system.Foam Pourer SystemSchematicFoam Pourer System-Schematic‘oam Pourer System-Components/ working
TS
++ Foam pourer system for tanks
>
‘Foam pourer system for Engine driven mainline
pumping unit shed.( Automatic/Manual)Foam Pourer System-PhotographsFoam Flooding system for Mainline engine shed
IndianOil
MAJOR COMPONENTS
Detection system
* Intrinsically safe Heat Detectors (HDs)
% Intrinsically safe Ultra Violet / Infra Red flame detectors (UV/IR)
* Addressable Manual Call Point (MCP)
Extinguishing system
“ Y-type strainer, Solenoid valve
* Deluge valve, Bladder type foam tank (capacity 2000 litres)
“Foam proportioning unit, Piping network for protected area
Foam cum water spray nozzlesFoam Pourer System
IndianOil
View of engine shed showing foam
solution piping and discharge nozzles
Deluge valve and bladder tank
skidFoam Flooding system in Mainline Pump shed
IndianOil
Hydrant line Foam bladder tank
f
Deluge Valve
6", 14000 IpmTypical Arrangement of Rim seal Units
IndianOilMA VI FOdilh MOQUIC ASSCHIDIy
IndianOilDischarge Nozzles& Rim Seal Fire Protection SystemRim Seal Protection SystemHydrocarbon Fire Fighting Techniques
In ETT
» Reduction of fire load from the fire site by
transferring the combustible material, if possible.
» Containment of fire and fire fighting.
» Reducing domino effect of fire by providing
suitable exposure protection measures.
» Salvaging usables after fire fighting.Hydrocarbon Fire Fighting Techniques
{cia
» Inter tank transfer of the product based on
availability of ullage in the installation.
» Operation of isolating devices to stop supply of
fuel to fire site.
» Localising the combustible product.Hydrocarbon Fire Fighting Techniques
(iO
First aid Use of first aid fire fighting extinguishers, fire
buckets, sand scoops, hose reel, water jel blanket
Manual Use of hose lines and nozzles, fire beaters,
portable monitors, fixed monitors
Fixed Fire hydrant network, sprinkler system, fixed
foam flooding system in MLPS/Tanks, CO2 total
flooding, Halon system, Deluge system
(The above system may be fixed/semifixed/
manual/automatic)
Mobile Water tender, foam tender, DCP tender, crash
tender, rescue tender, Foam nurser, trolley
mounted monitors.
Advanced Dynamite blasts etc.Emergency Response Plan-Statutory Requirements
(dia Ol ee
«+ Factories Act- 1948 (amended in 1987)
#Section 41-B requires that an “On-Site Emergency
Plan” with detailed Disaster Control Measures by every
occupier of an installation involving hazardous process
shall be prepared and submitted to Factory
Inspectorate.Statutory Requirement.... Contd
{nda
Manufacturer, Storage and Import of Hazardous
Chemicals Rules ( Amendments) Rules, 2000
#Rule - 5 - Notification of major accident
#Rule-7,8,9 - Notification of site and updation of same
#Rule- 10- Preparation of safety report
#Rule-11 - Updating of safety report
#Rule-13- Preparation of On-site Emergency plan (By occupier)
@Rule-14 - Preparation of Off - site Emergency plan ( By concerned
authority)Statutory Requirement.... Contd
In
Rules on Chemical Accidents (Emergency planning,
Preparedness and Response)
This rule envisages a 4-tier crisis management system in the country
1. Central crisis group
2. State Crisis Group
3. District Crisis Group
4. Local Crisis Group.General Guidelines for Drafting ERP
a
® — General Information about the Factory
> Brief information about the Company in general and Factory in Particular
@ Organisational Set Up
> Hierarchy in form of a tree showing the unit head and his subordinates up-to-the
Departmental / Sectional heads
® Manpower
» Shift wise manpower break up for A, B, C and G shift in tabular form
® — Product/ Bi-Product
> Name of Product and bi-product and their quantity per day / annum
® Inventory of Raw material
> Names of raw-material showing their quantity / threshold quantity
® Inventory of Hazardous substances
> Names of hazardous substances used as raw material showing their tank /
container capacity and thresh hold capacity
@ — Hazardous substances / gases produced/ generated during the process
> Names of hazardous substances / gases produced/ generated during the process
with the quantitiesGeneral Guidelines for Drafting ERP
i
Identification of Hazard
» Hazards are mostly manifested in form of fire / explosion / toxic release
> Each anticipated hazard scenario associated in the factory be described along with
its assessment of impact of plant and locality
Identification of most credible hazard scenario
> The most credible ( max) hazard scenario be identified trom among all anticipated
hazard scenario associated with the unit and its spread assessed through
dispersion model or other techniques
Plot Plan
> Aplot plan be made showing the plant location, iso-risk contour around the hazard
zones, emergency control room, assembly points, emergency exit, roads and other
relevant details
Emergency Command centre
> Atree snowing the emergency command structure, such as Works main controller,
Site Incident Controller, Combat team , Rescue team etc
Role of Key persons
» The role of key persons to be described in brief which should include members in
the command structuresGeneral Guidelines for Drafting ERP
IndianOil
# Action Plan for Emergency Response Plan
» The action of each person in the event of an emergency since it was
noticed by an employee to be described
# Silent Hour Command Structure
>» Acommand structure for the silent hour be prepared who should sprin:
into action during the silent hour till the members of the main comman
structure reach the site
® Activation and closing procedure
» The activation and closing procedure in the event of an emergency be
described in brietEmergency Response Plan
(¢iaNO
Objectives:
* To ensure that loss of life and injuries to persons are minimised
* To ensure that property losses are minimum
* Ensure that relief and rehabilitation measures are put into effective action
in the shortest possible time.
* To ensure that potential loss due to prolonged shut down of facilities is
minimised.
* To effectively make use of available resources
* — Identification of organizational and operational details
* Delineate functions of concerned departments & agencies for operational
responsibilitiesKey Element of ERP
IN ETT
* Assessment of the size and nature of the events foreseen and
probability that might occur
* Formulation of the plan and liaison with outside authorities
including the emergency services.
* Procedures — Raising the alarm and communication ( Both
within & outside pump station)
* Appointment of Key Personnel and defining their duties and
responsibilities
“+ Setting up of emergency control center
* Action on site
“ Station shut down procedures
*% Action off-sitePriorirty of handling emergency
(hia
Priority of Handling Disaster
42
Safe guard life
Safe guard property
Stop product leakage and contain
Extinguish any fire
Reclaim spilled product and clean the area
Probable Disaster
Fire
Leakage of oil & damage
Operational
Natural calamities
Man madeResponse Procedure & Measure
{cia
&
¢ @ ¢ @ ¢
Response procedure for all emergency situations( Causes,
Consequences, control measures, Man power & Equipments)
Organogram & Responsibilities
Resources (Internal/External)
Emergency Control Room
Mutual Aid Scheme
Name, Addresses, Contact numbers of concerned person/companyTeam Responsibility
{o_O
Team is responsible for
Handling of emergency at site
For supplying material/equipment/manpower
Plant operational control
Medical Services
General Support
Communication and media arrangement
Co-ordination with external agencies
@#e¢ 828 8 & &
All team leaders shall work under the command of an over
all commander.IndianOit
Control Room
Central control room shall be equipped with
@#e¢ ce 8 @ G&G Se 8 @
Plant layout
P&l diagram
Operating parameters of equipment
Organogram of ERP
Meteorological data
Mutual Aid Scheme
Telephone Numbers of persons to be contacted
Report forms
List of Internal & External Resources
Communication facilities
Material Safety Data Sheet(MSDS)Recovery Plan
IN ETT ae
Recovery Procedure
# Post - emergency Recovery
# Incident Investigation
# Damage Assessment
# Clean-up and RestorationEffective Implementation
{cai
Effective Implementation
e
e
&
e
Plan to be implemented through team work
Periodical Mock Drills activating DMP
Regular review and updation of plan
Constant liasoning with Mutual Aid Memberseo
THANK YOU