A proper water treatment program is an essential part of routine maintenance to ensure
the safe operation and longevity of this unit. A water treatment company familiar with local water conditions should be consulted. Any water treatment system used in the unit must be compatible with the unit’s materials of construction. Although high quality galvanized steel is used in most units, To control corrosion and scale, the recirculation water chemistry must be within certain ranges as shown in Table or within the limits provided by your local water treatment specialist.
Guidelines for Recommended Water Chemistry*
Property G-235 pH 6.5 to 7.5 Hardness as CaCO3 (ppm) 50 to 100 l Alkalinity as CaCO3 (ppm) 50 to 100 Total Dissolved Solids (ppm) < 300 Total Suspended Solids (ppm) < 25 Bacteria Count (cfu/ml) < 10,000 Chlorides as Cl (ppm) < 400 (Type 304 Stainless Steel) Stainless Steel