BLOCK - E

C8 (12"X36")
11'-6"

C10 (12"X42")
C5 (12"X30")
C8 (12"X36")
C6 (12"X36")
C3 (12"X30")
Dt: 17 Mar 2020

11'-0"

10'-0"
9'-0"

7'-6"
11'-0"

7'-6"
9'-0" 10'-0"
11'-6" 11'-0"
11'-0" 10'-6"
C7 (12"X30") C5 (12"X30")
GOOD FOR CONSTRUCTION

10'-6"

9'-0"
DATE : 11-03-2020
9'-0"
13'-0" C11 (12"X42") C9 (12"X36") C8 (12"X36") C11 (12"X42") NOTE *M20 = 320 Kg/Cum
C5 (12"X30") 1. GRADE OF CONCRETE MIX SHALL BE AS FOLLOWS : *M25 = 340 Kg/Cum
C6 (12"X36")
*M30 = 360 Kg/Cum
11'-0"

11'-0"
C14 (12"X54") * FOOTINGS M20 -
12'-0"

12'-0"

10'-0"
with minimum cement content of 320Kg/Cum

9'-0"
* COLUMNS
*M25
11'-0" 11'-0" with minimum cement content of 340 Kg/Cum
10'-0" 9'-0"
24'-6"

CF1 12'-0" C6 (12"X36") 12'-0" 10'-6" 2. GRADE OF CEMENT


ULTRA TECH /AMBUJA / BIRLA /CORMANDAL
C7 (12"X30") C7 (12"X30") C7 (12"X30") C8 (12"X36")
3. PEDESTAL HEIGHT MINIMUM 300mm & MAXIMUM 3 TIMES LEAST LATERAL DIMENSION.
10'-0"

10'-0"
10'-6"

10'-6"

10'-6"

11'-0"
4. ALL MAIN BARS DIAMETER 16 mm & ABOVE SHOULD BE Fe 500
C6 (12"X36")
C10 (12"X42") 5. ALL BARS OF DIAMETER BELOW 16 mm SHOULD BE Fe 415
10'-0"

10'-0" 6. REINFORCEMENT SHALL BE HIGH STRENGTH.


10'-6" 10'-6" 11'-0" DEFORMED BARS OF GRADE Fe 500 & Fe 415
CONFIRMING TO IS : 1786 - 1985.
7. CLEAR COVER TO REINFORCEMENT AS FOLLOWS :
3'-0"

FOOTINGS : 50mm
C18 (9"x30") C22 (9"x24") COLUMNS : 40mm
C9 (12"X36") C14 (12"X54")
C13 (12"X48") 8. LAP LENGTH OF BARS FOR TENSION & COMPRESSION AS FOLLOWS :
3'-0"
3'-0" LIFT 9. LAPS SHALL BE STAGGERED
13'-0"

C12 (12"X48") C9 (12"X36")


11'-0"

12'-6"

10. LAPPING AT COLUMN BEAM JUNCTIONS SHALL BE AVOIDED


12'-6"

3'-0"

C18 (9"x30") C18 (9"x30") 11. WORK SHALL BE IN ACCORDANCE WITH IS : 456 LATEST PRINT
11'-0" CF4 12. WHERE CEMENT CONSUMPTION IS GREATER THAN 100 BAGS CUBES TEST ARE TO BE DONE
13'-0" THERE SHALL BE ONE SET OF 3 CUBES PER EVERY 20 Cu. M. OF CEMENT CONCRETE OR
23'-0" PART OF THERE OF USED AT SITE AND SHALL BE TESTED ON 7th. / 28th. DAY
12'-6" C5 (12"X30")
13. AT JUNCTION OF TWO ELEMENTS OF DIFFERENT CONCRETE MIXES THE COMMON CONCRETE
SHALL BE DONE WITH RICHER MIX
9'-0"

13'-0" 14. CONCRETE SHALL BE MACHINE MIXED AND VIBRATED


3'-0"

9'-0" C19 (9"X30") C18 (9"X30") 11'-0" C8 (12"X36") 15. MAXIMUM WATER CEMENT RATIO USED SHALL BE LIMITED TO 0.50 FOR SLAB, BEAMS, COLUMNS.
C14 (12"X54") C9 (12"X36")
C7 (12"X30") 3'-0" 3'-0" C8 (12"X36") 16. CHIPPING OF ANY STRUCTURAL CONCRETE ELEMENTS SHALL NOT BE DONE ANY
LIFT 11'-0" CIRCUMSTANCES UNLESS WITH THE SPECIAL PERMISSION OF CONSULTANTS
13'-0"

11'-0"
10'-6"

C18 (9"X30") C18 (9"X30")


11'-0"

11'-0"

17. ALL COVER SHALL BE ENSURED BY PRECAST COVER BLOCKS MADE UP C.M. 1 : 1
3'-0"

11'-0" 18. DO NOT SCALE THE DRAWING FOLLOW WRITTEN DIMENSIONS ONLY
19. ANY DISCRIPANCY SHALL BE BROUGHT TO THE NOTICE OF THE CONSULTANTS
LIFT
3'-0"
10'-6" 3'-0" C10 (12"X42") C8 (12"X36") C7 (12"X30")
DEVELOPMENT LENGTH OF BARS FOR Fe-500 GRADE
11'-6"

11'-0"

10'-6"
3'-0"

C18 (9"X30") C18 (9"X30")


IN TENSION IN COMPRESSION

C9 (12"X36") C6 (12"X36") GRADE OF CONCRETE GRADE OF CONCRETE


C10 (12"X42") 11'-6" 11'-0" 10'-6"
DIA M-20 M-25 M-30 M-35 M-40 DIA M-20 M-25 M-30 M-35 M-40
10'-0"
11'-0"

8 mm 520 450 415 370 330 8 mm 415 360 335 300 265
11'-6"

11'-0" C16 (12"X60") 10 mm 650 560 520 460 410 10 mm 520 450 415 370 330

10'-0" 12 mm 780 670 625 550 495 12 mm 625 535 500 440 330

C8 (12"X36")
14'-0"

11'-6" 16 mm 1040 890 835 735 660 16 mm 835 715 670 590 530
C9 (12"X36")
CF1 C10 (12"X42")
11'-0"

11'-0"

13'-0"

20 mm 1302 1115 1040 920 825 20 mm 1040 900 835 735 660
11'-6"

11'-0" C14 (12"X54") 25 mm 1627 1395 1300 1150 1025 25 mm 1300 1115 1040 920 820

C10 (12"X42") 32 mm 2085 1785 1670 1470 1315 32 mm 1670 1430 1335 1175 1050
11'-0" 14'-0" 24'-6"
11'-6" DEVELOPMENT LENGTH OF BARS FOR Fe-415 GRADE
IN TENSION IN COMPRESSION

GRADE OF CONCRETE GRADE OF CONCRETE


C15 (12"X54")
C23
C12 (12"X48") C8 (12"X36") DIA M-20 M-25 M-30 M-35 DIA M-20 M-25 M-30 M-35

3'-0"
CF3 8 mm 435 375 350 305 8 mm 350 300 280 245
13'-0"
11'-0"

14'-0"
1'-0"
12'-6"

10 mm 10 mm 435 375 350 310


13'-6"

540 475 435 385


3'-0"

2'-0"

C11 (12"X42") C14 (12"X54")


1'-0"
2'-0" 12 mm 650 575 520 460 12 mm 525 450 415 370

16 mm 875 750 695 615 16 mm 700 600 555 490


11'-0" 24'-6"
12'-6" 14'-0" 20 mm 1100 950 865 765 20 mm 875 750 695 610
13'-6"
25 mm 1350 1175 1080 955 25 mm 1100 950 865 765

C8 (12"X36")
C5 (12"X30") 32 mm 1730 1485 1385 1220 32 mm 1385 1190 1110 980
12'-6" 12'-0" PROJECT :
C12 (12"X48") C12 (12"X48") C9 (12"X36") GREEN APLHA @ TELLAPUR
11'-0"

9'-0"

C11 (12"X42") TRIPURA CONSTRUCTION


C12 (12"X48")
12'-6"

12'-6"

CLIENT :
11'-0"
12'-0"

9'-0" 11'-0" TITLE :


11'-0"
19'-6"

CF2 12'-6"
C4 (12"X30")
EXCAVATION KEY PLAN
C2 (12"X24") C3 (12"X30") NOTES :
12'-6"
C4 (12"X30") C2 (12"X24") 1 STRUCTURE IS DESIGNED FOR 3STILT+10 FLOORS.
9'-0"

8'-0"

9'-0"
7'-0"

2 S. B. C. IS CONSIDERED AS 45 T/SQM .(Subject to change or as per site conditions)


7'-0"

7'-6"

3 COVERING FOR MAIN REINFORCEMENT SHALL BE 40MM FOR COLUMNS


C5 (12"X30") & 50MM FOR FOOTINGS.
C5 (12"X30") 4 CURING SHALL BE DONE FOR 21 DAYS
9'-0" 8'-0" 7'-0" 7'-0" 9'-0" 7'-6" 5 STRUCTURE IS DESIGNED FOR SIESMICFORCES AS PER I. S. 1893 ZONE II CONDITIONS.
DATE : R.NO. REVISIONS : DATE : DEALT : DRAWN : CHECKED :
28-01-2020 ZAKI AHMED M.MUQEEM M.A. NAYEEM

STRUCTURAL ENGINEERS.
4th. FLOOR ,ANASUYA COMM. COMPLEX
ARCHITECT Beside Remidy Hospital
Liberty Circle Himayathnagar Hyd. ST/E/01
(:55613497 , 23224772.
ZAKI AHMED
CONSULTING ENGINEER