Thank you for using the company’ s PC800 Series Poner Center-loop digital monitoring
and control devices. By reading this manual, you can fully understand the PC800 and control
installations.
IHL If the use of manual features and products described in the actual functions of some
discrepancies, please check the menu and products, subject to the actual functionality,
The Conpany reserves the right to make any prior notice cases, the contents of this manual
in the right to make changes without notice.
11! This product need to be a reasonable provision of the relevant parameters debugging,
otherwise all the negative consequences caused by, the Company shall not be responsible,
111 Please operators in strict accordance with the instructions to operate the product,
otherwise the operation due to an error caused by all the negative consequences, the Company
shall not be responsible.
111 Tf operation questions, please call our technical support hotline 021-68795734
(8:30-17:00, Mon-Fri) consulting, or due to unauthorized operation of all the negative
consequences caused by, the Company shall not be responsible.
Rapid advances in technology, based on the PC800 controller V2.2 edition version of
the manual, PC822 Module V2.1 version of the preparation, different versions of the
slightly different instructions, such as different versions of the event, please call
technical support line advice.
PC800 Control unit wiring diagram
_ a - -
. : + Signal Stateful Tripping/ closinj
L_ Main circuit | geteetion | rnd8eefed ty ppl (a8, | Module
a
LOAD
1/20The photo shows the use of circuit breakers + PC800 + points, closing the second coil
typical application schematic (only PC800 control part), the figure for the PC800 current
transforner built-in, no external current transformer (only if a loop current is greater
than 250A external protection, the level when the current transformer C1540, protection
of accuracy 5P10).
PC comprehensive protection circuits, measurement function, a variety of control
functions and control devices from the PC800 to complete.
Parameter display, parameter setting, alarm, fault management functions such as
information inquiry be completed by the PC822 module.
When the controller PC800 get electricity, PC822 show “in English and Chinese language
selection interface”, after you enter the option to “Ready By Closing” the default message
window, “Tripping” green light; At this point press the switch on button, PC800 receive
@ closing order, its internal pull-closing relays, the closing coil was electricity,
cireuit breaker closing, PC822 display signal measurement interface, “closing” red light;
When the PC800 receive to the sub-gate conmand, its internal disconnect switch on relays,
closing coil loss power, sub-gate pull-relays, sub-gate coil was electricity, circuit
breaker, PC822 redisplay ” Ready By Closing ” the default message window, sub-gate green
light.
One, Control panel and Display module description
1.1. Control panel and Display module description
'@®0OOOOOO
omen
—, 0
coms
Teo us oi
Indicator
Reset
Controller Current Level
PC800
@88G88G08
LED lights from top to bottom as:
Sub-gate, closing—Sub-Gate lighting, Closing hours flashing are all green lights,
5us——Constant communication device when the light or flashing, are all green lights.
Fault, Alarm—Failure lighting, Alarm flashing, are all green lights.
P.C822 Interface: Through the DB-9 data lines connected with the PC822 module to achieve
operational control, data display and parameter setting functions.
2/20Terminal Pin Function Description
{Number Pema Manin
D1 _cow Nol tage signal inpula-phase volta
2WProgranable DI [Connon 10 NO Woltage si, inpufB-phase vol tag
Gf |Progranmable DI2 [Tripper Action} NC Woltage si; [C=phase_ vol tay
WMH Programmable O13 [Tsolator statud NC Analog Out
ff Programmable D14_ [Closing NO [Analog Our
(MG Progrannable b15 {Tripping NO kr 1 in
[RAP Programmable D16 [Common 10 NO RTD 2 Ty
MiBNE|Programable DI7 [Reset |] S485 Portza
U9Progrannable DIS |Local /Renota | _NO RS485 Port:B
HOM Progranmable DI9 [externa No__| FRRGIMRs485 Port:§
WA Leakage transforme|Input_1 [7 RS485 Port2:S2
MPN Leakage transforme|input 2 RS485 Port2:A2
GyWProgranmable p02 [Tripping NO IRS485 Port2:B2
Programmable D01 [Closing NO Programmable D110 NO.
HsHif01 /002_cow Programmable DIL NO
[HG Protective earthin f Programmable DI12 No
DM Power Input (-) i Progranmable DO5. NO
Misi |Power Input @) [ Programmable DO6 NO.
1D03/004 cow 05/006 CoM
MP0 [Programmable 03 [Fault NC Progranmable DOT NO
(vi Progranmable p04 [Alarm NO, [p07 _coM L
Note: 1. DO support the 0.1s ~ 3.0s pulse / level in two ways, DI / DO mode by default level,
2. 35 ~ 42 terminals in the EM580 expansion module.
3. DI / DO parameters can be set.
1.2 PC822 Module Introduction
Saitfar
LED lights from left to right as:
Glosing—Red lights, Direct current circuit breaker for the switch on state, can also
identify the work of the P0800 power is normal
Standby——The current version of this key non-functional definition, indicator for the off
state,
3/20Tripping—Green lights, Indicate the current status of circuit breaker for the sub-gate
Alarm——Red lights, Indicator lit, he said that alarm ocurred, no alarm information out.
Fault—Red lights, Indicator light, said circuit breaker failure trip; no fault information
and fault reset after the off.
Function keys:
Closing——In the local authority, this button can control the circuit breaker closing.
Tripping—In the local authority, This button can control the circuit breaker Sub-gate
Standby—The current version of this key non-functional definition.
Reset——After the exit for troubleshooting fault condition, can clean a variety of
instructions or failure status display.
Confirm. Return, #. # 4 function keys for parameter setting and inquiries
Confirm——From the default interface into a menu (main menu), and then gradual ly into the
2 menu 3 menu, eventual ly into the query interface or configuration interface: If the
state is saved for editing data or parameters, otherwise, enter the edit mode,
Return —If the state has withdrawn from the editor in the editing state, and the parameters
are not preserved; otherwise, exit to the main menu or the default interface.
* t “love the cursor or soroll off, if the editor is used to adjust the parameters of
the state.
* # "Hove the cursor or scroll off, if the editor is used to adjust the parameters of
the state,
Note: The above function control keys can be locked according to the actual needs of users do not
have,
Two, Parameter settings and Functional applications
Menus and Submenus
Menu is a simple options menu. Some of these options more in-depth level can enter the options
menu known as the sub-menu. Browse in the menu when the menu is divided into different levels,
will help to understand. System into the default menu is called the default menu, first clase
for the “Wain Menu”, the next one for the “Sub-menu”. When the system boot, the controller
automatically enter the default menu,
24 Default Menu
Figure2.1.1 Select Interface Language
Here I will only introduce English portion of the menu,
[Prepare closing conditions, ithe isolator status appear correctly
[Control authority the focal command or a remote command and effective
Run mode
4/20Figure2.1.2 Closing ready interface
In the closing state, a variety of protection begins with start, in the closing state, there
are faults or fault alarm, the system interface will automatically pop-up failure or malfunction
alarm information. As shown below:
| ip cause
— Action Trip delay time
}-— Fault nip-related parameter values
Figure 21.3 Fault trip information interface
Other types of faults related to the generation and various protection, protection action
displayed when the corresponding fault type, but it does not reflect the failure of all the
circumstances, if you need to see the electrical failure of the current fault data, see the failure
Part of the record shows . Defective, the user can not switch on, and mist reset before re-closing.
Tf the fault action time is set to zero, but not tripping fault conditions is reached, there
Will be failure alarms. Interface is shown below (new adjustment of the display module has not
been tested)
Figure2.1.4 Fault alarm information interface
If there exist several fault alarm will be displayed page, and the 2s automatically next page.
Figure2.1.5 Isolator status error interface
Isolator status error in the state is not allowed users to close, until the error goes away,
return to “Ready By Closing” interface only allows the user to switch on,
As the operation of PC822 and PC800 module with DB-9 cable connections, bad contacts, so if
there is broken or the cable itself is the problem, the data will not transfer,
When the communication has not been established, the display interface for the next figure,
the table can not establish communication, or cable is not connected,
Sm at
Figure2.1.6 Communication Failure Interface
2.2 Menu
The mode of entry for the main menu: in the default menu, then press confirm button to enter the
main menu, as shown:
5/20Ready By Closing
Measure
&Contro)
Local
Signal Measurement
‘Alarm Inquiry, 2
Figure2.2.1 Constitute a block diagram of the menu
The following describes in detail the contents of the menu.
Fi
Figure 2.2.2
Signal measurement can enter the main menu inside the view parameter measurement.
Alarm Inquiry menu, you can check some of the major will not lead to tripping of information,
Figure 2.2.3
Fault record eight times the menu can be information on the latest failure of recording
information, fault record information, including fault information, three-phase current, current
inbalance rate, line voltage, power, thermal resistance, grounding / leakage current and contactor
status.
Management Message menu, you can query the current parking time, the current running time,
the latest start-up time, the latest starting current, operating frequency, trip frequency, the
total stopping time, total run time.
Figure 2.2.4
DI / DO status of the inquiries can search for DI / DO terminals of the state to determine
whether the opening and closing movements.
Protection Para. Set menu can be a variety of protection parameters settings.
Figure2.25
Start Para, Set menu is to set some of the main starting parameters, such as start-up time,
power-on self-starter and so on.
System Para. Set menu is mainly set up some communication protocol, operation mode, rated
voltage, rated power, full load current, AO parameter setting.
6/20Figure 2.2.6
1/0 Config, menu is mainly DI feature set, the normal state is set, DO feature set, the
normal state is set, the mode settings, and these parancters settings.
Version Nunbers is displayed the menu, motor controller and display module version numbers
for easy identification software version,
Figure227
Fassword Managenent aenu is mainly for users to set a password to protect the paraneters are
not arbitrarily modified.
Parallel to the main menu to switch between various levels is carried out through the
¥ keys.
2.3 Signal Measurement Menu
From the main menu to find “Signal Measurenent” menu, press confirm button to enter the
measurement menu interface.
A-phase current
Bphase current
‘C-phase current
Ground or leskage current
Figure 2.3.1 Current Measurement Interface
Figure above Ta, Ib, Ie, Tg, respectively, A-phase current, B-phase current, C-phase current,
sround or leakage current, 100.0% Ir1 expressed relative to the percentage of rated current.
Figure 23.2 Current Asymmetry Rate Measurement Interface
Figure above is Current Asymmetry Rate measurement.
A-phase voltage
B-phase voltage
‘C-phase voltage
‘Average phase voltage
Figure2.33 Three-phase voltage and the average phase voltage measurement interface
‘The figure above shows the average three-phase voltage and phase voltage measurements,
AB line voltage
BC line voltage
CA line voltage
[-——~ Average line voltage
Figure 23.4 Three-phase Line voltage, and the average line voltage measurement interface
The photo shows the three-phase line voltage and the average line voltage measurement,
7/20When there is no voltage feature, the map interface will not be displayed.
Toon Frequency
Active power
| Reactive power
‘Apparent Power
Figure2.35 Frequency, active power, reactive power and apparent power measurement interface
The figure above shows the frequency, active power, reactive power and apparent power
measurements.
Active electrical power
Reactive electrical power
Power Factor
Figure2.36 Active power, reactive power and power factor measurement interface
The upper photo was active power, reactive power and power factor measurenents.
Note: When tho system power over measuring range 65535Wh, the system will automatically be
cleared.
2.4 Alarm Inquiry Menu
Fron the main menu, look for “Alarm Inquiry” menu, press confirm button to enter alarm inquiry
menu interface. Police inquiries can search for some of the main menu interface will not lead
to tripping of the alarm.
In the absence of alarm situations, the interface is shown below do not show any alarm,
RTE
Figure24.1 Alarm Inquiry Interface
Real-time display alarm information, each page can display two warning messages, more than
‘to can be to see the next page: by actual police case, there will be PT cutting, overload, ground,
undervoltage, over-eurrent section of over-current See , external fault, closing loop break,
sub-gate loop break alarm information and so on.
Figure2.4.2 Undervoltage Alarm Interface
2.5 Fault Inquiry Menu
From the main menu to find “Fault Inquiry” menu press confirmation button to enter fault inquiry
menu interface.
Figure2.8.1 Fault Recording menu interface
The interface shown in the Up and Don keys to switch through the last eight of this record
of Failure, The meaning of the "No. 8 / 8": A total of eight failures, at present for the recent
failures, The previous figure for the alternative record of the mmber of recent failures, Nuaber
8/20of larger faults closer to the present; the latter figure is the total number of times the fault
occurred, up to 8 times.
‘When the system interface remain in the interface shown below, press confirmation button to
enter the reasons for the recent failure of interfaces.
ieryol Trip cause
‘Action Trip delay time
Flt rip-eated parameter vals
Figure 25.2 Cause of the malfunction interface (undervoltage fault trip)
Into the cause of the malfunction when the system interface, can be up and down keys to obtain
the fault parameter query.
Fault tripping current
Fault tripping current imbalance ate
Fault tripping curent secondary side voltage
~ Fouit tripping power, earth leakage current
Figure 25.3 Failure constitutes a diagram Records menu
Tn the figure above, Fault records are mainly trip delay time when the three-phase current,
current imbalance in the rate of secondary-side line voltage, power, grounding / leakage current.
2.6 Management Message Menu
From the main menu, look for “Management Message” menu, press confirm button to enter the
management information menu interface.
Figure 2.6.1 Management message menu interface
Management message menu main can learn about the operating frequency of trip times.
Operation Nunber refers to the closing number, regardless of the success of closing all
considered to be a normal operation.
Trip Number refers to the controller because of failure causes the number of trip.
2.7 DI/DO Status
From the main menu to find “DI / DO Status” menu, press confirm to enter DI / DO status
query menu interface.
Figure27.1 DI/DOStatus Query menu interface 1
When the system interface shown in the previous stay at the interface, press the “confirm
9/20button” can be found to the 12 way DI state,
Pigure2.7.3 DI /DOStatus Query menu interface 2
When the system interface shown in the previous stay at the interface, press the “confirm button”
can be found to the 7 way DO state.
Figure2.7.4 DOStatus Query menu interface
2.8 Protection Para. Set
From the main menu, look for “Protection Para, Set” menu, press confirm to enter protection
parameters set menu interface,
PC800 protection provided by a PT Cutting Protection, Overload Protection, Earthing/ Leakage
Protection, Undervoltage Protection, Overcurrent! Protection, Overcurrent? Protection, External
Protection. PT Cutting Protection, Undervol tage Protection in a voltage function to enter settings,
no-voltage conditions can not be reached to set key set.
PT Cutting Earthing
Overload Undervoltage
Figure2.81 Constitute a block diagram of the protection set of parameters
‘The following describes in detail the various protection parameters settings.
Figure 2.82 PT Cutting Protection Interface
Note: In the absence of voltage feature can not enter this interface change.
PT Disconnection protection parameters set:
10/20Mode Of Execute: Trip / Alarm
Acting Value: 526Un~40%Un+OFF, OFF is turn off the feature
Delayed Time: 0. 1s~5.0s
2.8.2 Overload Protection
Pigure283 Overload Protection Interface
Overload protection parameters set:
Mode Of Execute: Trip / Alarm
Curve: 1.0~10.0
Time Set: 0.0s~100. 0s
Reset Mode: Manual / Automatic
2.8.3 Earthing Protection
Figure 2.84 Earthing / Leakage Protection Interface
Earthing / Leakage Protection parameters set:
Mode Of Execute: Trip / Alarm
Acting Value: 10%1Am~100%1 Am +0FF, OFF is turn off the feature
Protection Delayed Time: 0.00s~60. 00s
Protection Delayed Time refers to the earthing / leakage protection switch on after the set
Period of time not do this earthing / leakage protection, over i
/ leakage protection.
setting is put into earthing
11/20Delayed Time: 0.00s~60. 00s
Shear coefficient: 1.5~6.0+0FF, OFF is turn off the feature
Note: In the absence of voltage feature can not enter this interface change.
Figure2.8.5 Undervoltage Protection Interface
Undervoltage Protection parameters se
Mode Of Execute: Trip / Alarm
Acting Value: 18Un~90%UntOFF, OFF is turn off the feature
Delayed Time: 0. 1s~50. 0s
2.8.5 Overcurrent Protection
Figure 2.8.6 Overcurrentl Protection Interface
Overcurrent! Protection parameters set:
Mode Of Execute: Trip / Alarm
Delayed Time: 0.0s~60. 0s
2.8.6 Overcurrent2 Protection
Figure 2.87 Overcurrent2 Protection Interface
Overcurrent2 Protection parameters set:
Node Of Execute:
Trip / Alarm
12/20Acting Value: 100%Ir1~200%Ir1+0FF, OFF is turn off the feature
Delayed Time: 0.0s~60. 0s
2.8.7 External Protection
Figure 2.8.8 External Protection Interface
External Protection parameters set:
Mode Of Execute: Trip / Alarm
Delayed Time: 0. 1s~60. 0s
2.9 Start Para. Set
From the main menu to find the “Start para. Set” menu button to enter boot parameters in
accordance to confirm the configuration settings menu interface.
co a
a han al Ip — Locanemonsoiten
Figure 2.9.1 Software operating permissions interface
Local: Said the current operation in the local authority, the local keyboard and the local
terminal order is in force, the remote terminal and remote conmunications were barred.
Remote: Said the current operation permissions on the remote, remote terminal and remote
communication order is in force, local keyboard and local terminals were barred.
Forbidden: When the software operation permissions are set to disabled, also in DI terminal
to set up a local / remote button input, in the local / remote button is not pressed, the software
operating in the local authority; on the contrary, the software operating privileges on the remote.
If there are no local / remote set the software operating system default permissions on the local.
Te
oe
eat
Figure 2.9.2. Terminal property settings interface
Local; When the above contro! permissions set to local time, terminal, said terminal property
is set to the local order is in force.
When the above contro! permissions set to the remote when the Property is set toa remote
terminal, said terminal command is invalid.
When the above, the control authority is set to disabled, if not set up a local / remote
command button that terminal properties of the local effective; if it has set up a local / remote
command button, in the absence of pressing local / remote command button, it said that properties
[= Locayremore
are now in the local terminal, if the press local / remote command button, thet properties are
now in the remote terminal
Remote: When the above control permissions set to the remote when the property is set toa
remote terminal, said terminal order is in force.
When the above control permissions set to local time, property is set toa remote terminal,
said terminal command is invalid.
33/20When the above control permissions set to prevent, if not set up a local / remote command
button, the remote terminal attribute is invalid; if it has set up a local / remote command button,
in the absence of pressing local / remote command button,
't said that properties are now in the
local terminal, if the press local / remote command button, that properties are now in the remote
terminal.
7
Time
TOADS Ils
}— Range: 0.1s~3s
Figure2.9.4 MCCB Reset Time settings interface
The time contro! method for molded case circuit breaker, when effective, it needs in accordance
with the actual circuit breaker tripping time is set to return.
2.10 System Para. Set
From the main menu, look for “System Para. Set” menu button to enter system parameters in
accordance to confirm the configuration settings menu interface.
Ay
Control Key
Enabled
Figure210.1 Constitute a block diagram of the system parameter set
The following describes in detail various system parameter settings.
—~ MODBUS/PROFIBUS-DP/DEVICE NET.
Figure2.10.2 Protocol type setting Interface
Range: 1~255(Modbus), 3~126(Profibus-DP)
Figure2.103 Address setting interface
14/20Under no such menu in the Profibus-DP.
‘Range:9600 / 19200 / 38400
eet
Figure210.6 Primary voltage setting interface
Primary voltage refers to the secondary side voltage of 100V or 400V at a voltage of an external
transformer,
Range: 100V /400V
Figure 2.10.7 Secondary voltage setting interface
Secondary voltage means a loop voltage level, but also the requirements of the value of
transformer secondary side.
Range:250W~1100kW.
Figure 2.10.8 Rated power setting interface
Rated power refers to thr
phase active power.
ENS i
Figure 2.10.9 Full load current setting interface
Full load current refers to the maximum motor full load current stability.
| ~ Transformers for 1A and SA when this interface
Range: 1(1A). 5(5A)-9999A+OFF
Figure 2.10.10 Primary current setting interface
Primary Current means for measuring and control device rated current 1A or 5A, the external
side of IA or 5A secondary current transformer primary side current. OFF said that no external
current. transformer.
Figure2.10.11 AO Output setting interface
'a Iby Ie, lav: Were associated with analog three-phase current and average current;
15/20Uab, Ube Ucay Ulla
peace and average voltage;
Were associated with analog | ine voltage, respectively associated with
"Ba, IBb, 18c, IBav: Were associated with analog unbalanced three-phase current and average
current imbalance rate;
F: Associated with analog frequency:
AO output function only with the option key makes sense
Range: 1.0~10.0
Figure2.10.12 AO Max. Output setting interface
Relative to the AO output, AO output options for maximum X:
la, Ib) Icy lav) IBay IBb, IBc, IBav: 20mA corresponds to X
jimes the full load current;
Vab, Ubc. Uca, Ullav: 20mA corresponds to X times the rated voltage;
Fs 20mA corresponds to X times the S0Hz;
P: 20mA corresponds to X times the rated power
Age }— ACB/MCCB / Common Control
Figure 2.10.13 Mode of control setting interface
ACB: Control object within the framework of circuit breakers, there are closing, sub-gate
two states. Reconmends that users need to DO according to operating mode settings are set to pulse
mode, that is, 0.18 ~ 3.0s,
MCCB: Control object for the molded case circuit breaker, there are closing, sub-gate, tripping
three states. Recommends that users need to DO according to operating mode settings are set to
pulse mode, that is, 0.1s ~ 3.0s. Trip state does not allow users to switch on, in the closing
minutes before engaging gate.
Common Control: Control object for the user to make any object, Users can be DO mode settings
are set to pulse or level mode,
Enabled / Disabled
Figure2.10.14 Control Key setting interface
Enabled: PC822 keys on the display module is functioning correctly.
Disabled: PC822 keys on the display module features is prohibited.
Figure 2.10.16 Mode of Self-launch setting interface
Power on self-launch: In the power process, according to the system settings to determine
whether to allow self-investment, if the system power-on self-cast feature set to allow,
self-starting mode is set to direct start, then the system will directly switch on; if the
16/20auto-switch mode is set to the original state of starting, then the system will be based on
Pre-poner-down state, to determine whether the system is closing, if power-down before the system
is in closing state, the system will be restored to power-down before the closing state, If the
controller in power-down before the brake system is sub-state, the system will not be closing.
If the power-on self-cast feature set for the banned, then no matter what kind of automatic switch
mode is set to mode, the system will not switch on.
2.11 Input and output configurations
From the main menu and look for the “I / 0 Configuration” menu, press confirm button to enter
input and output configuration settings menu interface. For DI / DO parameter settings, can be
associated with terminal set, Common type: 9 Road, DI, 4 way DO effective; Enhanced: 12 Road, DI,
2 way DO effective. Pictured below are DI / DO port selection.
Figure 211.3 D0 Mode setting interface
DI Parameter configuration interface
To DI 01, for example, the next picture shows the option settings associated with DI. DI can
according to actual needs and the design of circuits to set the function set and the normal status
is set.
Disconnector Status / Close / Open / Local Remotion / Reset /
Extemal/ Common 10 / Close Loop Cutting / Open Loop Cutting /
Release Acting / Energy Storing Stas / Trolley Position
Figure 211.4 DIO1 Function setting interface
Li Range:NO / NC
Figure 2.115 DIO1 Normal status setting interface
When the DI state and normal state is set when there is agreement that the corresponding feature
set DI No signal input; When the DI status is inconsistent with the normal settings that DI feature
set with the corresponding input.
00 Parameter configuration interface
To DO O1, for example, the next picture shows the option settings associated with DO. DO can
be designed according to actual needs and set the corresponding line function set, the normal
Status set and mode of work settings. Parking associated with the state to modify the DO option
is set controller can operate effectively.
17/20‘Alarm / Fault Under-Volge Fault /Earthing Fault / Overload Fault/
External Fault SelCheck Fault / Common / Close / Open / PT Cutting /
‘Overcurent / Overeutent2 / Close Loop Cutting
Figure 2.11.6 O01 Function setting interface
Range:NO / NC
Figure 2.11.7 DOO1 Normal status setting interface
th Range:Level /0.1s~3.0s,
Figure2.11.8 D001 Mode setting interface
D0 Normal status set: When the control ler which meets DO function set option, D0 act ion—Normal
status is set to always open when the time for the DO closed; Normal status is set to always close
when the time for the DO opened.
DO mode setting level: At this point if the DO action, action status continues, Until the
situation does not meet the DO controller function set. Control the situation does not meet the
DO function settings DO is set to return to normal status.
DOmode settings 0. 1s ~ 3.05: At this point if the DO action, the state continued to set the
time to set the state back to normal status. If the DO mode set to 1s, then the logic diagram is
as follows:
Pull-Is Pull-1s
Closing relay
Pull-1S |
| |
| 1 t
Tripping relay
Closing ‘Tripping Closing
2.12 Version Numbers
From the main menu, look for “Version number” menu, press button to enter the version number
to confirm menu interface.
PC measure and control unit version
‘Module version
Figure 2.12.1 Version numbers interface
Is used to view the controller and display module version,
2.413 Password Management
From the main menu to find the “Password Management” menu, press confirmation button to enter
‘the password management menu interface.
38/20Log On: Login password for the user to modify the parameter settings.
Change Password: For users to change passwords.
ae
Unlog
Cee
Figure 2.13.2 Password management sub-interface 2
In the absence of the registry under the premise of change parameter settings, will pop-up
“unlog, no right to change” window, tips you need to be logged in order to modify the password
management menu parameter settings.
Press confirmation button will return to password
‘management sub-interface 1, exit the login
Figure 2.13.3 Password management, sub~interface 3
In the password management sub-interface, an interface click “confirm button” to enter a
Figure 2.13.4 Enter password interface
Enter Password: A total of three numbers, each bit range of 0 ~ 9, The ed key to press
‘to confirm the first post~subscr ipt wil! be moved to second place, the second confirmation button
press, after the revised standard will be moved under the third, Three-digit password change
confirmation key press to confirm, if the password is correct, there wil be the password is correct
interface; if the password is incorrect, an error occurs password interface.
Figure 2.13.5 Password is correct interface
Press to confirm at this interface button to return to the main menu interface. At this time
have been logged three minutes in the absence of operation, the automatic log
Figure 2.13.6 Password Error Interface
Press confirm button in this interface to return to the “Enter password” interface or “Enter
old Besant ea re-enter your password.
Figure 2.13.7 Enter old password interface
When you need to modify the original password, enter the “Change Password” menu, then appear
on the map interface. Enter three of the original password, click to confirm key, if the password
is correct, there will be “Enter new password” interface, if an error, there will be ” Password
error” interface.
19/20You can according to your need to set a new password, modified after the key press to confirm
your password has been modified interface will appear, then a successful password change.
This interface that password has been modified, press confirm button to return to the password
management sub-interface 1, the arrows point to change password.
20/20