You are on page 1of 10

.

IS 15142:2002

VRmwm

m @i * Wm-fa a w-l-fad faw’lc *mmi-vT” a

faa-a & W-wVJir “ * WdPl a Wid2icM

Indian Standard
GUIDE TO THE USE OF ELECTRICAL APPARATUS FOR
POTENTIALLY EXPLOSIVE ATMOSPHERES IN THE
PRESENCE OF COMBUSTIBLE DUST

ICS 29.260.20

Q BIS 2002
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

Sep~ember 2002
Price Group 4

/ 1 I
Electrical Apparatus for Explosive Atmosphere Sectional Committee, ET 22

FOREWORD
This Indian Standard was adopted by the Bureau of Indian Standards, after the drafi finalized by the Electrical
Apparatus for Explosive Atmosphere Sectional Committee had been approved by the Electrotechnical Division
Council.
This standard gives guidance on the use of electrical apparatus and systems complying with the requirements
for electrical apparatus’ to be used in explosive gas atmospheres under conditions when the hazard will be from
combustible dust.
While preparing this standard, assistance has been derived from British Standard BS 7535:1992 ‘Guide to the
use of electrical apparatus’ complying with BS 5501 or BS 6941 in the presence of combustible dust.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis shall be rounded off in accordance with
IS 2: 1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this standard.

i
Is 15142:2002

Indian Standard
GUIDE TO THE USE OF ELECTRICAL APPARATUS FOR
POTENTIALLY EXPLOSIVE ATMOSPHERES IN THE
PRESENCE OF COMBUSTIBLE DUST
1 SCOPE to have been certified and without detailed assessment
of the apparatus or system being required from the
1.1 This standard gives guidance on using electrical
user. There may be particular circumstances in which
apparatus and systems complying with the
the recommendations are felt to be too restrictive and
requirements of Indian Standards for electrical
suitably experienced and qualified persons may make
apparatus to be used in explosive gas atmospheres
an assessment of the circumstances and then decide
under conditions when the hazard will be from
either not to apply or else to modify the
combustible dust. The guidance covers selection,
recommendations taking responsibility for maintain-
installation and maintenance.
ing an adequate level of safety. In such cases, the
This standard is based upon the use of apparatus guidance in this standard should be followed as for as
and systems specified in IS 2148, IS 5780, IS 6381, is practicable.
IS 7389 (Part 1) and IS 8289 without modification.
Exceptionally the user may decide that a modification
This is so that any claim for compliance of the
should be made, for example, to improve the degree
appatatus or systems with those standards will not be
of protection by enclosure. As this would invalidate
invalidated and so that the apparatus or systems remain
the original claim for compliance and any certificate,
suitable for use, as originally intended in an explosive
the marking of the apparatus or systems and any
gas atmosphere.
documentation should be changed so that there can
Not all such apparatus and systems will be suitable be no fhture misunderstanding.
for use according to the recommendations of this
standard. 2 REFERENCES
The guidance in this standard takes as a criterion of 2.1 The Indian Standards listed in Annex A are
acceptability that the electrical apparatus is able to necessary adjuncts to this standard.
operate safely under a dust Iayer on the external surface
of the enclosure having a maximum thickness of 5 mm, 3 DEFINITIONS
which is the thickness used in the measurement of the 3.0 For the purposes of this standard, the following
ignition temperature of dust layers. definitions shall apply.
This standard does not apply to the use of electrical
3.1 Rating
apparatus in dust from materials regarded as
explosives, nor does it take into account any risk The designed performance of an electrical apparatus.
resulting fkomthe emission of flammable gas or vapour
from the dust. It does not apply to electrical apparatus 3.2 Degree of Protection of Enclosure
and systems intended for or used in mines susceptible The measures applied to the enclosures of electrical
to firedamp (Group 1 apparatus). apparatus to ensure the following:
This standard gives guidance on the application of ‘a) protection of persons against contact with live
apparatus constructed for use in explosive gas or moving parts inside the enclosure and
atmospheres and complying with IS 2148, IS 5780, protection of the apparatus against ingress
IS 6381, IS 7389 (Part 1) and IS 8289, in situations of solid foreign bodies.
where the hazard is only from the presence of
b) protection of apparatus against ingress of
combustible dusts.
liquids.
It does not give guidance on the use of electrical NOTE—Theenclosuretogivethe‘degreeofprotection’isnot
apparatus in atmospheres that may simultaneously necessarilyidenticaltotheapparatusenelosurefor‘typeofpTo-
contain explosive gas and combustible dust. teetion’andwillbedefinedbythemanufacturer.
1.2 The guidance in this standard has been prepared 3.3 Terminal Compartment
to be as widely applied as possible without requiring
modification of apparatus or systems which are likely A separate compartment or part of a main enclosure,

I’i
IS 15142:2002

communicating or not with the main enclosure, and 3.11 Non-Hazardous Area (Dust)
containing connection facilities.
Area in which combustible dust-air mixtures are not
3.4 Connection Facilities expected to be present so that special precaution for
the construction and use of electical apparatus are
Terminals, screws and other parts, used for the not required.
electrical connection of conductors of external circuits.
3.12 Source of Release (Dust)
3.5 Maximum Surface Temperature
Place from which combustible dust may be released
The highest temperature which is attained in service into the atmosphere,
under the most unfavorable conditions (but within
the tolerances) by any part or surface of an electrical 3.13 Maximum Surface Temperature of the
apparatus, which is able to produce an ignition of the Enclosure
surrounding atmosphere. Highest temperature that is attained under the most
NOTES
adverse electrical conditions (but within the specified
tolerances) by any part of the external surface of the
1 Since this definition is from IS 5571, ‘surroundingatmosphere’
should be understoodas ‘surroundingexplosive gas atmosphere’. enclosure of an electrical apparatus that would be able
The ‘part’ or ‘surface’ may therefore be inside or on the outside to produce an ignition of the surrounding atmosphere.
for any enclosure of the apparatus depending on the type of
protection. 3.14 Ignition Temperature of a Dust Layer/Cloud
2 The most unfavorable conditionsincluderecognizedoverloads
and fault conditions specified in the standard for the type of Lowest temperature at which ignition occurs under
protectionconcerned. defined test conditions of a combustible dust Iayed
cloud.
3.6 Dust
3.15 Area Classification (Dust)
Small solid particles that settle out under their own
weight but that may remain suspended for some time. National division of works, plant or installation
(hereinafter referred to as plant) into zones in
3.7 Combustible Dust accordance with the likelihood of the existence of a
Dust that is combustible or ignitable in mixtures with hazardous area (dust) for the purpose of selection,
air. installation and maintenance of electrical apparatus.
NOTES 3.16 Extent of Zone
1 Most combustible dusts form explosive mixtures with air only
between certain concentration limits. Distance in any direction from a source of release to
2 Although a mixturewhich is abovethe upperconcentrationlimit the point where the hazard associated with that zone
is not an explosive mixture, it can become so by dilution. is considered no longer to exist.
3 Combustible dusts are capable of being ignitedby externaligni-
tion sources and will continue to burn at atmosphere tempera- 3.17 Zone 21
tures but they will only spontaneously ignite above a certaintem-
perature, Area in which combustible dust, is, or may be, present
as a cloud during normal processing, handling or
3.8 Free Dust cleaning operations in suftlcient quantity to be capable
Apparatus that can either be moved while in operation of producing an explosive concentration of
or that can easily be moved from one tiace to another combustible or ignitable dust in a mixture with air.
ready for use, while connected to the supply. NOTE — Zone 21 is an area outside the dust containment.

3.9 Hazard (Dust) 3.18 Zone 22

Presence, or risk of the presence, of a combustible Area not classified as Zone 21, in which accumulations
mixture of dust and air, or layers or combustible or ignitable dust may be
present under abnormal conditions and give rise to
3.10 Non-Hazardous Area (Dust) ignitable mixtures of dust and air.
Area in which combustible mixtures of dust, in close NOTE — Zone 22 is an area outside the dust containment.
or layer form, and air are, or may be expected to be,
3.19 Dust Containment
present in quantities such as to require special
precautions for the construction and use of electrical Those parts of the process equipment inside which
apparatus. dust is handled, processed, transported or stored.

l’!
IS 15142:2002

3.20 Conductive Dust consideration of matters such as those listed in 6.2


to 6.6 which might have implications for the electrical
A dust with electrical resistivity equal to or less than
apparatus and which should be taken into account by
103Q cm.
the plant designer and operator.
4 CLASSIFICATION OF HAZARDOUS AREAS
6.2 Toxic Risks
This standard adopts the concept, which is inter-
Even though there may be no ignition risk, there maybe
nationally agreed for flammable gases and vapours,
toxic risks associated with combustible, or other, dusts
of using an area classification (see 3. 15) to denote the
particularlywhere these are deposited on heated surfaces.
risk of tire andfor explosion. As the hazard from
combustible dusts, unlike that from flammable gases 6.3 Fire Risks
and vapours, will not necessarily be removed by
ventilation or diffusion after the release has stopped, Attentions should be given to the installation of
a common classification is not practicable. Indeed, in apparatus, particularly to any guards or covers,
the case of combustible dusts, accelerated ventilation including those intended to reduce the deposition of
may, by the creation of dust clouds, give a greate] combustible dust on electrical apparatus, to avoid
rather than less hazardous condition. Furthermore, the thereby an increasing fue risk.
formation of dust layers may be cumulative, thus
6.4 Static Electricity
increasing the hazard unless the dust is physically
removed. Reference is made to electrostaticcharges on enclosures
of electrical apparatus. Attention also needs to be given
The definitions of Zones21 and 22 are given in 3.17
to the avoidance of electrostatic charges on other parts
and 3.18 respectively, this classification relying on an
of that plant. It is recommended that reference be made
assessment of the likelihood of the existence of a
to IS 7689.
hazardous area (dust). The situation where there could
be the simultaneous presence of combustible dust and 6.5 Lightning and Electromagnetic Radiation
of flammable gas or vapour is not directly considered
and it is recommended that such situations should be Although outside the scope of this standard, it should
the subject of individual assessments based on the not be forgotten that combustible dust under certain
recommendations of this standard and of IS 5572. In circumstances, may be ignited by lightning and
classifying a hazardous area, account should not be electromagnetic radiation and the implications for the
taken of catastrophic failures, whether of electrical electrical installation should be borne in mind. It is
apparatus producing a source of ignition or of for recommended that reference be made to IS 2309.
example, process equipment and pipelines which by
6.6 Miscellaneous Ignition Sources
fracture, could beoome sources of release. Such
catastrophic failures would be assumed to be of low In any plant, irrespective of size, there are likely to be
probability in plants designed, constru~ted, tested, source of ignition other than those represented by
inspected and maintained in accordance wib accepted electrical apparatus. The possible implications of these
standards and codes of practice. should be taken into account when installing electrical
apparatus.
By implication, an area outside the dust containment
that is not classified as Zone 21 or Zone 22 is deemed 7 PRINCIPLES FOR SELECTION OF APPARA-
to be a non-hazardous area for the purposes of this TUS AND SYSTEM
standard.
7.1 General
5 PROPERTIES OF COMBUSTIBLE DUSTS
The selection of electrical apparatus complying with
[flee IS 14154 (Part 2)]
IS 2148, IS 5780, IS 6381, IS 7389 (Part 1) and
6 OTHER HAZARDS IS 8289 for use in any specific application in areas
where a combustible dust hazard may be present,
6.1 General should be taken into account of all of the following:
This standard is concerned specifically with the a) the construction and design of the apparatus;
ignition risks associated with apparatus complying b) the maximum surface temperature;
with IS 2148, IS 5780, IS 6381, IS 7389 (Part 1) and c) the area classification;
IS 8289 when used in a hazardous area. There are d) the concepts of protection of the apparatus
other hazards that exist in plants where such apparatus and systems; and
is used and the assessment of the risk, which is not e) the degree of ingress protection provided by
within the scope of this standard, will involve the enclosure of the apparatus.
3
IS 15142:2002

7.2 Selection According to Apparatus Construction Table 1 1P Rating Requirements and Impact
Strength of Apparatus Complying with IS 2148,
For any specific application consideration should be
IS 6381, IS 7389 (Part 1) and IS 8289
given to the design and construction of the apparatus,
and particularly to its enclosure, taking into account [Clause 7.2(b)l
the points discussed in (a) to (Q as follows: IS No. Types Solid Liquid Impact
of Pro- Ingress Ingress (J) Range
a) Dust Layer Thickness — The thickness of any tection (First (First 7/1(High
Character- Character- RjskLow
layer of deposited dust on the external surface istic istic Rkk)
of the enclosure should be as small as possible Numeral) Numeral)
and should not exceed 5 mm. In any specific (1) (2) (3) (4) (5)
application, the extent to which dust will 7389 ‘, 4 0 711
P
accumulate on the enclosure will depend (Psrt 1)
2148 $.d Not Not Ill
upon a number of factors, such as the design Scecitied Specified
of the enclosure and of the apparatus; the 6381 ‘,e 512 4/0 711
,.,1 2/0 0 Not
ventilation natural or artificial; the proximity 5780
Specified
of the apparatus to other objects; the ease of ‘> 4/0
8289 n 5/2 3.5/0.5
cleaning, by manual or other means; the
presence of attractive forces, magnetic or d) Electrostatic Attraction — When non-
electrostatic [see (c) and (d)]. metallic enclosures are used they may not
have been designed and constructed to
In some cases, the accumulation of dust in minimize the accumulation of electrostatic
unacceptable thicknesses may be: charges (see IS 2148) and may bear the
1) avoided by the choice of attitude for the warning label indicating the safety measures
apparatus, for example by mounting it to be applied in service. It is important that
so that large flat surfaces are not the siting and installation of the apparatus
horizontal; or does not encourage dust accumulation due to
electrostatic attraction.
2) hindered, for example by using protective
guards, although it should be e) Light Metal Construction — Under
remembered that these may also make conditions of frictional contact, the light
cleaning more difficult and/or the metals, for example ahnniniurn, magnesium
presence of dust more difficult to discern. and titanium, and their alloys containing
more than 50 percent light metal by atomic
b) Degree of protection of enclosure (see
proportion, can give rise to incendive
Table 1). In Zone 21 or where the dust is
sparking.
electrically conductive, apparatus having a
f) Environmental Conditions — As the
degree of protection by enclosure 1P 6X
continued compliance of apparatus in
should be used. In Zone 21 apparatus having
accordance with IS 2148, IS 5780, IS 6381,
enclosures providing a degree of protection
IS 7389 (Part 1) and IS .8289 is often
of at least 1P 5X and without permanently
dependent on the continued integrity of its
open breathing and draining devices may be
enclosure and/or the quality of its insulation,
used.
it is important that the selection process gives
The degree of protection by the enclosure c~eful consideration to factors such as the
should be inherent in the design of the risk of mechanical damage, chemical and
enclosure. It is not recommended for the user solvent attack. Similarly other environmental
or installer to achieve 1P 5X or 1P 6X for the factors which could affect the temperature
purpose of dust ingress protection by the use classification, for example, the proximity of
of additional sealing measures, for example, hot items of plant, solar gain and the presence
adhesive or tape. This does not, however, of obstructions to cooling should be
preclude their application additionally by the considered.
user or installer for weatherproofing. 7.3 Selection According to Surface Temperature
c) Magnetic Attraction — If ferromagnetic dust In selecting IS 2148, IS 5758, IS 6381, IS 7389 (Part 1)
may be present, it is desirable that the and IS 8289 apparatus, attention should be given to
apparatus should have the smallest possible the fact that the marked temperature cIass may refer
external magnetic field and its enclosure to a surface inside the enclosure. The degrees of
should preferably be of non-magnetic protection by enclosure referred to in this standard
material [see (d) and (e)]. are assumed to prevent the entry of dangerous
4

1’
IS 15142:2002

quantities of dust into the apparatus and the significant 7.4 Selection for Use within the Dust Containment
temperature is, therefore, taken to be that of an external
7.4.1 The selection of apparatus for use within the dust
surface on which dust may accumulate. Consequently
the use of certain IS 2148, IS 5780, IS 6381, IS 7389 containment requires special consideration because the
(Part 1) and IS 8289 apparatus with a given effect on the apparatus of thick dust layers, or immersion
temperature classification is likely to give a safety in dust cannot be predicted. It is considered, however,
margin. Alternatively the maximum surface that non-heat dissipating apparatus, part of whose
temperature of the enclosure may be measured under enclosure forms part of the dust containment and whose
the conditions specified in IS 2148, IS 5780, IS 6381, electrical parts may thus be considered to be outside
IS 7389 (Part 1) and IS 8289 as applicable and the the dust containment is permissible. For the purposes
apparatus selected on the basis of the measured value of this standard, non-heat dissipating apparatus is
of temperature and the guidance in this clause. considered to be apparatus whose surface temperature
at the hottest point of the external surface of the
The temperature class of apparatus is determined in enclosure atler thermal stability has been reached does
accordance with the results of temperature measure- not exceed 5 K above ambient temperature when
ments made under normal operating conditions and
measured in free air under the conditions specified for
with recognized overloads, if any. The validity of
the allocation of the temperature classification in the
temperature classification may be dependent upon
standard for the method of protection. This may be
operation within recognized tolerances of supply
determined by test, from a declaration by the certificate
voltage variation; in cases of doubt the apparatus
holder for the apparatus or by a declaration from the
manufacturer should be consulted.
certifying body. Such apparatus includes, but is not
Generally, an ambient temperature of 40°C is assumed necessarily limited to the following:
in the rating of electrical apparatus for use in
a)measuring devices operating via a pocket or
hazardous areas. Higher temperatures in exceptional
cases lower temperatures, may have been taken into thermowell which forms part of the dust
account in determining the rating of apparatus. In that containmen~
event, the value of the maximum ambient temperature b) apparatus having only mechanical parts
should be clearly marked on the apparatus and/or within the dust containrnenc
stated on the certificate. It should be noted that a c) apparatus which has access to the inside of
certificate will be invalidated if the apparatus is used the dust containment only through a solid
at an ambient temperature higher than that for which window, or other solid boundaxy of the dust
the certification applies. The principle to be observed containment. In this case the general
is that the maximum surface temperature should be recommendations given in 7.1, 7.2 and 7.3
less than the ignition temperature of the dust(s) and the specific recommendations in 7.4 to
concerned, in cloud and layer form, with a suitable 7.8 inclusive should be followed on the basis
safety margin. of the area classification outside the dust
It is recommended that the safety margin is obtained containment; and
by selecting apparatus having a temperature class or d) capacitance probes.
a maximum surface temperature less than the
7.4.2 Where intrinsically safe apparatus and systems
following:
are considered for use within the dust containment
a) two-third of the minimum ignition tempera- they should be of category IA, Group IIC, in
ture of the combustible dust/air mixture(s) accordance with IS 5780, and the apparatus intended
cloud(s) concerned; and for use therein should have an 1P 6X enclosure. The
b) 75 K less than the mini!nurn ignition installation should be accepted as suitable only if
temperature of a 5 mm layer of the consideration of potential causes of ignition demonst-
combustible dust(s) concerned. rates that the apparatus will not ignite the d,ust under
NOTE — Group 11apparatus complying withIS2148, the fault conditions specified in IS 5780. The potential
IS 5780, 1S 6381, 1S 7389 (Part 1) and IS 8289 is nor- causes of ignition which should be considered include,
mally temperature classified as follows: but are not necessarily limited to the following:
Temperature MaximumSurface a) the thick layer ignition temperature of the
Class Temperature,0C
dust;
T1 450
T2 300 b) the surface temperature of the enclosure of
T3 200 the apparatus under a thick layer of the dust;
T4 135 c) accumulation of electrostatic charge on the
T5 100 enclosure of the apparatus or parts thereofi
T6 85

5
IS 15142:2002
[
d) sparking between the enclousre of the dust is electrically conductive, apparatus having a
apparatus and its surroundings; and [
degree of protection by enclosure of 1P 6X should
always be selected. i
e) ohmic heating of the dust.

7.5 Selection of Apparatus Complying with IS 7389 In circumstances where the IS 5780 intrinsically safe
(Part 1) (Pressurized Apparatus ‘p’) apparatus does not have the 1P 6X or 1P6X enclosure
recommended, an assessment of suitability shou Id be
Pressurized apparatus may be used in Zone 22 carried out by examination and, where necessary,
provided the degree of protection by enclosure is at testing to show that the required integrity of the
least 1P5X. In Zone 21, or where the dust is electrically intrinsically safe circuit is maintained despite a layer
conductive an 1P 6X enclosure should be used. of dust.
The pressurized enclosure should have one or more For this purpose all exposed clearance and creepage
inlet apertures and one or more outlet apertures for distances should be assumed to have failed to the most
the connection of the inlet and outlet ducts for the onerous conditions. The normal criteria for acceptable.
protective gas. These apertures are excluded from the energy release are those for Group IIC gases and
degree of protection recommendations in 3.2. vapours specified in IS 5780. The category of intrinsic
However, outlet apertures discharging into the safety chosen should be ‘IA’ for Zone21 applications
hazardous area should be so constructed that they are and at least’ IB’ for Zone 22 applications.
closed at the end of the purging period in the case of
It is necessary to re-assess the temperature
leakage compensation systems, or on cessation of
classification of the apparatus taking into account the
pressurization in the case of continuous circulation
additional possibility of failure of exposed clearance
systems.
and creepage distances. In particular the temperature
7.6 Selection of Apparatus Complying with IS 2148 classification of any exposed small components shou Id
(Flameproof Enclosure ‘d’) be reconsidered. In the design, advantage may have
been taken of the small component relaxation on
Apparatus with flameproof enclosures may be used in surface temperature requirements and these may
Zone 21 or Zone 22 and should have a degree of achieve a temperature higher than the marked
protection by enclosure of at least 1P 5X for Zone 22 temperature classification. Temperature excursions of
and 1P 6X for Zone21. Where the dust is electrically small components under conditions of test may exceed
conductive, apparatus having degree of protection by the ignition temperature of the dust (in cloud or layer
enclosure of 1P 6X should always be selected. form) provided that the dust(s) in question is (are) not
ignited or charred by the component.
7.7 Selection of Apparatus Complying with
IS 6381(Increased Safety ‘e’) The additional assessment and any necessary testing
should be documented and carried out by a competent
increased safety apparatus may be used in Zone 22
body using techniques and facilities similar to those
provided the degree of protection by enclosure is at
normally used by a national certi@ing authority for
least 1P5X. In Zone 21 or where the dust is electrically
intrinsically safe apparatus.
conductive, increased safety apparatus having a degree
of protection by enclosures of 1P6X should always be Each piece of apparatus or its immediate location
selected. should be marked or identified so that the particu Iar
application can readily be traced back to the related
7.8 Selection of Apparatus and Systems in safety documentation.
Accordance with IS 5780 (Intrinsically Safe
Apparatus ‘i’) If there is any doubt about the suitability of the
appakatus, then enclosures having the recommended
Intrinsically safe apparatus, having enclosures 1P ratings should be used.
providing a degree of protection of at least 1P 5X, and
systems may be used in Zone 21. Intrinsically safe 7.9 Selection of Apparatus Complying with IS 8289
apparatus, having enclosures providing a degree of with Type of Protection ‘n’
protection of 1P 6X, and ‘systems may be used in
Type of protection ‘n’ apparatus having enclosures
Zone 21. Uncertified parts of intrinsically safe systems
providing a degree of protection of 1P5X may be used
such as simple devices, junction boxes, etc, should
in Zone 21. Where the dust is electrically conducting
have a degree of protection by enclosure of at least
an 1P 6X enclosure should always be used.
1P5X for Zone 22 and 1P 6X for Zone21. Where the

6
IS 15142:2002

ANNEX A
(Clause 2.1)
LIST OF REFERRED INDIAN STANDARDS

IS No. Title IS No. Title

2148:1981 Flame proof enclosures for electrical apparatus with type of protection ‘e’
apparatus (second revision) 7389 Pressurized enclosures of electrical
2309:1989 Code of practice for the protection (Part 1): 1976 apparatus for use in explosive
of buildings and allied structures atmospheres: Part 1 Pressurized
against lightning (second revision) enclosures with no internal source
5571:1979 Guide for selection of electrical of flammable gas or vapour (jirst
equipment for hazardous areas (first revision)
revision) 7689:1989 Guide for the control of undesirable
5572:1994 Classification of hazardous areas static electricity @rst revision)
(other than mines) having 8289:1976 Electrical equipment with type of
flammable gases and vapours for protection ‘n’
electrical installation (second 14154 Electrical apparatus with protection
revision) (Part 2): 1997 by enclosure for use in the presence
5780:1980 Intrinsically safe electrical apparatus of combustible dusts: Part 2 Guide
and circuits first revision) to election, installation and
6381:1972 Construction and testing of electrical maintenance
Bureau of Indian Standards

i31S is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffn-med when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards: Monthly Additions’.

This Indian Standard has been developed from Doc : No. ET 22 (3796)

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters :
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams : Manaksanstha
Telephones :3230131,3233375,323 9402 (Common to all offices)

Regional Offices : Telephone


Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 3237617
NEW DELHI 110002 { 3233841
Eastern : 1/14 C.I.T. Scheme VII M, V. I. P. Road, Kankurgachi 3378499,3378561
KOLKATA 700054 { 3378626,3379120
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022 603843
{ 602025
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113 2541216,2541442
{ 2542519,2541315
Western : Manakalaya, E9 MIDC, Marol, Andheri (East) 8329295, 8327858
MUMBAI 400093 { 8327891,8327892
Branches ,: AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE. FARIDABAD.
GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW. NAGPUR.
NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM. VISAKHAPATNAM

Reprography Unit, BIS, New Delhi, India

l“

You might also like