You are on page 1of 2

Cover removable

for lifting
4440 2635 Cu 100x10
1

25
COOLING 7 14
AIR OUT 40

480
883 Cu 150x6
70
U V W 5

480
2 ... 7
13

25
12 14
4351

COG 10

720
COG
11 1 HV connection / OS Anschluss
11 9 4 797 2 LV connection / US Anschluss d11:10

480
290 290 1

2864
3 LV connection / US Anschluss d11:30

aktive part
1 3

housing
4 LV connection / US Anschluss d11:50

480
COOLING
2148

AIR IN 5 LV connection / US Anschluss d0:10


2 6 LV connection / US Anschluss d0:30

1219
7 LV connection / US Anschluss d0:50

905
8 Earthing M12 / Erdung M12
8 9 Rating plate / Leistungsschild
200 1500
95

70 753
12 10 Temp.control / Temperaturüberwachung
3640 1505
2500 11 Ball pin / Kugelbolzen K 20
12 Cable support / Kabelhalter
3x MCT 6+6x1
2 ... 7 1090 1090 on top 13 Fan mounting / Lüfteranbau
3-Phase Dry-Type Transformer / 3-Phasen Trockentransformator
Type / Typ RESIBLOC
Rated power / Leistung [kVA] 8322//1387/1387/1387/1387/1387/1387
Rated voltage HV / Spannung OS [V] 6300
Rated voltage LV / Spannung US [V] 1845/1839/1844/1844/1839/1845
Vector group / Schaltgruppe Yd11:10d11:30d11:50d0:10d0:30d0:50
COG
Protection mode / Schutzart IP23
2581

Frequency / Frequenz [Hz] 50


Insulation class / Isol.Klasse F
Total weight / Gesamtgewicht [kg] 20800
2 Höhenmaß angepasst TFOTSCH 09.12.2013
RevInd Revision Appd Date
Prepared Date Responsible department Title File: <auftrag>\trafo\massbild.drw

J. Mertens 29.10.2012 BT General Arrangement


Massbild
Approved Date Take over Department Language
MCT 4x1
on bottom de
1
ABB Transformatoren 14220121364MB
Document No. Sheet

1/2
COOLING A
IR OUT

COOLING A
IR IN
HV side LV side

2270
1180

2 Höhenmaß angepasst TFOTSCH 09.12.2013


RevInd Revision Appd Date
Prepared Date Responsible department Title File: <auftrag>\trafo\massbild.drw

J. Mertens 29.10.2012 BT General Arrangement


Massbild
Approved Date Take over Department Language

de
ABB Transformatoren 14220121364MB
Document No. Sheet

2/2