Professional Documents
Culture Documents
Protection IED
Technical Manual
Version:V1.00
Doc. Code:F0SF.450.069(E)
Issued Date:2010.07
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipments do not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
COPYRIGHT
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the product description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result; it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Tel: +86-10-62961515
Fax: +86-10-62981900
Internet: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
CSC-326 Transformer Protection IED Technical Manual
Important notes
Scope of Application
Please read the manual carefully and the specification of the installation, adjustment,
Restricted liability
No responsibility is assumed by SIFANG for any consequences arising out of the use
of this manual. This document is not intended as an instruction manual for untrained
persons.
Device operation
The user is responsible for checking that the rated characteristics of the device are
suitable for its application. The user is responsible for reading and following the
maintain it. Failure to follow these instructions can affect device operation and
Please use the testing instruments which comply with the relevant standards for test
To prevent damage from equipment, don‘t hot-plug and hot-unplug any module of the
relay; touching the chips and components in printed circuit board is inhibited.
Operation password
The operation password is: 8888, the system setup password is: 7777.
~I~
CSC-326 Transformer Protection IED Technical Manual
Protective grounding
The user is responsible for compliance with all the existing international and national
Safety instructions
Read these instructions carefully and look at the protective relay to become familiar
with the device before trying to install, operate, service or maintain it. The following
special messages may appear throughout this bulletin or on the equipment to warn of
procedure.
indicates that an electrical hazard exists, which will result in death or personal injury if
Safety alert
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards and prompt you to consult the manual. Obey all safety instructions that follow
~ II ~
CSC-326 Transformer Protection IED Technical Manual
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could
NOTE
NOTE indicates matters need attention regarding a certain special application,
~ III ~
CSC-326 Transformer Protection IED Technical Manual
CONTENTS
Important notes .................................................................................. I
1 Introduction ................................................................................ 1
1.1 Application............................................................................................... 1
1.2 Features ................................................................................................... 1
1.3 Functions ................................................................................................. 2
2 Technical data............................................................................. 5
3 Hardware................................................................................... 15
6 Reports ...................................................................................... 75
8 Operation .................................................................................. 85
1 Introduction
1.1 Application
CSC-326 transformer protection IED is used for two- and three-winding transformers,
auto-transformers, generator-transformer units, and shunt reactors.
1.2 Features
The equipment has characteristics as follows:
Fault wave recorder with great capacity, memory up to 4M bytes, can record
full process of any fault, and can save no less than 24 records. Optional data
format or wave format is provided when the records need to be printed, and
also fault wave recorder can be exported to serial port or Ethernet port by
COMTRADE format.
Event recorder can store operating reports, alarm reports, start reports and
general operation records, every kind of record isn‘t less than 2 000 events,
and is memorized when power is off.
The product can record protection operating process, logic flow and varied
calculation values that can be analyzed in whole process by analyzing
software CSPC developed by us. PC which installed this fault analyzing
software, can manipulate the protection system via series ports RS-232 on
-1-
CSC-326 Transformer Protection IED Technical Manual
2-channel high speed reliable electric Ethernet ports (optional optical fiber
Ethernet ports), 2-channel LonWorks ports, RS-485 port and series printing
port are provided; the user can select any of these according to the
requirements. The protocol supports IEC60870-5-103, IEC61850 or
CSC-2000 of Sifang Company, easy to interface with substation automatic
system and protection management information system.
1.3 Functions
CSC-326 series is presented briefly in Table 1.
Main protection
-2-
CSC-326 Transformer Protection IED Technical Manual
Definite and IDMTL overcurrent protection for HV, MV and LV sides (with
selective direction)
Definite and IDMTL earth fault protection for HV, MV and LV sides (with
selective direction)
-3-
CSC-326 Transformer Protection IED Technical Manual
-4-
CSC-326 Transformer Protection IED Technical Manual
2 Technical data
2.1 Basic data
-5-
CSC-326 Transformer Protection IED Technical Manual
-6-
CSC-326 Transformer Protection IED Technical Manual
0.7 fixed
-7-
CSC-326 Transformer Protection IED Technical Manual
-8-
CSC-326 Transformer Protection IED Technical Manual
-9-
CSC-326 Transformer Protection IED Technical Manual
-10-
CSC-326 Transformer Protection IED Technical Manual
I eq 2 1 H / C I P 2
t ln
IEC Hot Curve I eq I
2 2
-11-
CSC-326 Transformer Protection IED Technical Manual
-12-
CSC-326 Transformer Protection IED Technical Manual
-13-
CSC-326 Transformer Protection IED Technical Manual
60255-22-4
Surge disturbance 4 class : IEC 60255-22-5,
•communication port IEC 61000-4-5;
--2kV; Note: Harsh more 3 Class of IEC
• others ports --4kV 60255-22 -5
Conducted disturbance of 3 class:10V IEC 60255-22-6
RF IEC 61000-4-6
Power frequency magnetic 5 class :100A/m IEC 61000-4-8;
field disturbance Note: No defined in IEC60255-22
Pulse frequency magnetic 5 class:1000A/m IEC 61000-4-9;
field disturbance Note: No defined in IEC60255-22
Damped oscillatory 5 class:100A/m IEC 61000-4-10;
magnetic disturbance Note: Actual up to 120A/m ,No
defined in IEC 60255 -22
interruptions in auxiliary 50ms GB/T 8367-1987 (equal
energizing quantities IEC60255-11)
IEC 61000-4-11
Electromagnetic emission IEC 60255-25
limits (GB/T14598.16-2002,IDT)
safety
IP rating IP20 IEC 60529,
GB 16836-1997
Insulation cooperation Clearance IEC 60255-5:2000
and creepage GB 16836-1997
distance
Maximum temperature of According with the GB 16836-1997
material standard
Flammability of insulation V 0 class IEC 60950
materials GB 16836-1997
Protection against I class IEC 60536
Electric shock GB 16836-1997
-14-
CSC-326 Transformer Protection IED Technical Manual
3 Hardware
3.1 Mechanical structure
The layout of equipment is 19 inches in width and 4U in height according to IEC
60297-3.
The equipment is flush mounting with panel cutout and cabinet mounting.
The modules can be combined through the bus on the rear board. Both the
equipment and the other system can be combined through the rear
interfaces.
-15-
CSC-326 Transformer Protection IED Technical Manual
3.2 Dimensions
Dimension drawings for CSC-326 are shown in Fig. 1.
1 2 3 4 5 6 7 8 9 10 11 12
TIM TIM TIM CPU CPU COM BIM BOM BOM BOM BOM PSM
-16-
CSC-326 Transformer Protection IED Technical Manual
receiving and storing the fault report and event report of the CPU module, output for
printing and communicating with the monitoring system and protection engineering
workstation by or Ethernet network
Output report to the display screen and operating the device with the keyboard of the
front panel.
The standard RS-232 port in front panel is suitable for connecting a PC. The PC
based software CSPC can be used for convenient and transparent setting, recording
disturbance and evaluation as well as commissioning. 2 RS485 and 2 Ethernet
interfaces (or 2 electric or fiber Ethernet interfaces, selective) are equipped on the
rear board. It is convenient to connect to a substation automation system or to a
protection data master unit.
-17-
CSC-326 Transformer Protection IED Technical Manual
-18-
CSC-326 Transformer Protection IED Technical Manual
4 Protection functions
4.1 Differential protection (ANSI-87T)
4.1.1 Function description
I1 I2
Figure 3 Basic principle of differential protection for two ends (single phase)
I diff I res
The differential current and the restraining current are calculated by the
following formula (5-1):
N
I diff
i 1
Ii
N 1
1
I I
res 2 j (max)
i 1
I i (i j )
(5-1)
Where:
Ii is the current vector of side I, Ii is the vector of current of HV, MV and LV
windings;
N- Total current input, suppose it is N sides;
I j (max)
- The maximum current vector of the N input, suppose it is side j;
N 1
I (i j)
i 1
i
-19-
CSC-326 Transformer Protection IED Technical Manual
I
effect quantity, I res counteracts this effect i is the current of every side. To clarify
the situation, three important operating conditions with ideal and matched
measurement qualities should be examined.
Transformers are subject to a number of influences that induce differential currents
even during normal operation, such as automatic ratio compensation, automatic
vector group compensation, instantaneous differential protection, treble slope
percentage differential protection, inrush stabilization, overexcitation stabilization, CT
saturation recognition and CT failure supervision etc.
Differences in the matching of CTs to the rated current of the transformer are not
uncommon. These differences result in an error that leads to a differential current.
The characteristic values of the transformer, i.e. rated apparent power, rated voltages
and primary rated CT currents, are entered in the protective device, and the rated
current of the every side of the transformer I1N is calculated automatically according
to the following formula:
SN
I 1N
3U 1N
Where
S N - Rated apparent power of the transformer
U 1N -Rated voltage
The secondary rated current is calculated by the following formula, for differential
I
protection, e is taken as the reference current.
I 1N
Ie
nCTHV
Rated current of the High voltage side is taken as the reference current. The digitized
currents are automatic matched the rated current of the high voltage side of the
transformer, and a correction factor KCT for MV or LV side is calculated according to
the following formula:
Where:
K CTMV - Correction factor for middle voltage side
Note:
To ensure the accuracy of devices, range of correction factor should be 0.1 ~ 5.
I1N I1NHV I1NMV
- Primary rated current of the transformer ( for high voltage side, for
I
middle voltage side, 1NLV for low voltage side)
-20-
CSC-326 Transformer Protection IED Technical Manual
I 2 N -Secondary rated current of the transformer ( I 2 NHV for high voltage side,
I 2 NMV for middle voltage side, I 2 NLV for low voltage side)
nCT - CT ratio of the transformer ( nCTHV for high voltage side, nCTMV for middle
Transformers have different vector groups, which cause a shift of the phase angles
between the primary and the secondary side. Without adequate correction, this phase
shift would cause a differential current.
Transformers often have a wye-delta connection, to allow a maximum of versatility in
the use of the CSC326, all imaginable vector group compensations have been
integrated in the software. If the setting ―Vector Group Angle (VET GRP ANGLE)‖ and
the settings for every connection type (wye or delta, 1-delta, 0-wye) are entered to the
device, the vector group compensation is automatically completed.
The basic principle of numerical vector group connection is as follows.
4.1.1.4.1 Take example for Yy0 connection, including similar ones of Yy0, YNy0,
Yyn0, YNyn0, Ydy0, Yndy0, Ydyn0, Yndyn0 and so on.
A B C A (a)
Side 1:
C (c) B (b)
Side 2:
a b c
Figure 4-1 Vector Group compensation for Yy0 transformer
I A 1 -1 0 I A I a 1 -1 0 Ia
1 1
I B 0 1 -1 I B I b 0 1 -1 I b
I 3
-1 0 1 I C I 3
-1 0 1 I c
C c
I I I
Deducting on side 1 the currents A B results in the current A , this has the same
I
direction as A on side 2. Multiplying it with
1 3
matches the absolute value. The
matrix describes the conversion for all three phases. The zero sequence currents are
-21-
CSC-326 Transformer Protection IED Technical Manual
4.1.1.4.2 Example for Yd1 connection, including similar ones of Yd1, YNd1 and
YNd1 + earthing Transformer.
A a
A B C
Side 1: c
C B
b
Side 2:
a b c
Figure 4-2 Vector Group compensation for Yd1 transformer
I A 1 0 -1 I A
1
I B -1 1 0 I B
I 3
0 -1 1 I C
C
4.1.1.4.3 Example for Yy2 connection, including similar ones of Yy2, YNy2, Yyn2,
YNyn2, Ydy2, YNdy2, Ydyn2, Yndyn2 and so on.
A B C
A
Side 1: c a
C B
Side 2: b
b c a
Figure 4-3 Vector Group compensation for Yy2 transformer
I A 1 -1 0 I A I a 0 -1 1 I a
1 1
I B 0 1 -1 I B I b 1 0 -1 I b
I 3
-1 0 1 I C I 3
-1 1 0 I c
C c
-22-
CSC-326 Transformer Protection IED Technical Manual
4.1.1.4.4 Example for Yd3 connection, including similar ones of Yd3, YNd3 and
YNd3 + earthing Transformer.
b A
Side 1:
c
C B
Side 2: a
I A 0 1 -1 I A
1
I B -1 0 1 I B
I 3
1 -1 0 I C
C
4.1.1.4.5 Example for Yy4 connection, including similar ones of Yy4, YNy4, Yyn4,
YNyn4, Ydy4, YNdy4, Ydyn4, Yndyn4 and so on.
A B C
A (c)
Side 1:
c a b
Figure 4-5 Vector Group compensation for Yy4 transformer
I A 1 -1 0 I A I a -1 0 1 I a
1 1
I B 0 1 -1 I B I b 1 -1 0 I b
3 I 3
I -1 0 1 I C 0 1 -1 I c
C c
4.1.1.4.6 Example for Yd5 connection, including similar ones of Yd5, YNd5 and
-23-
CSC-326 Transformer Protection IED Technical Manual
A B C
A b
Side 1:
a
C B
Side 2: c
c a b
Figure 4-6 Vector Group compensation for Yd5 transformer
I A -1 1 0 I A
1
I B 0 -1 1 I B
I 3
1 0 -1 I C
C
4.1.1.4.7 Example for Yy6 connection, including similar ones of Yy6, YNy6, Yyn6,
YNyn6, Ydy6, YNdy6, Ydyn6, Yndyn6 and so on.
A B C
A
Side 1: b c
C B
Side 2:
a
a b c
Figure 4-7 Vector Group compensation for Yy6 transformer
I A 1 -1 0 I A I a -1 1 0 I a
1 1
I B 0 1 -1 I B I b 0 -1 1 I b
I 3
-1 0 1 I C I 3
1 0 -1 I c
C c
4.1.1.4.8 Example for Yd7 connection, including similar ones of Yd7, YNd7 and
YNd7 + earthed Transformer.
-24-
CSC-326 Transformer Protection IED Technical Manual
A B C
Side 1: c A
a
Side 2:
C B
b
b c a
Figure 4-8 Vector Group compensation for Yd7 transformer
I A -1 0 1 I A
1
I B 1 -1 0 I B
I 3
0 1 -1 I C
C
4.1.1.4.9 Example for Yy8 connection, including similar ones of Yy8, YNy8, Yyn8,
YNyn8, Ydy8, YNdy8, Ydyn8, Yndyn8 and so on.
A B C
A (b)
Side 1:
b c a
Figure 4-9 Vector Group compensation for Yy8 transformer
I A 1 -1 0 I A I a 0 1 -1 I a
1 1
I B 0 1 -1 I B I b -1 0 1 I b
3 I 3
I -1 0 1 I C 1 -1 0 I c
C c
4.1.1.4.10 Example for Yd9 connection, including similar ones of Yd9, YNd9 and
YNd9 + earthing Transformer.
-25-
CSC-326 Transformer Protection IED Technical Manual
A B C
A c
Side 1:
b
C B
Side 2: a
b c a
4.1.1.4.11 Example for Yy10 connection, including similar ones of Yy10, YNy10,
Yyn10, YNyn10, Ydy10, YNdy10, Ydyn10, Yndyn10 and so on.
A B C
A
Side 1: a b
C B
Side 2:
c
c a b
Figure 4-11 Vector Group compensation for Yy10 transformer
I A 1 -1 0 I A I a 1 0 -1 I a
1 1
I B 0 1 -1 I B I b -1 1 0 I b
I 3
-1 0 1 I C I 3
0 -1 1 I c
C c
4.1.1.4.12 Example for Yd11 connection, including similar ones of Yd11, YNd11
and YNd11 + earthed Transformer.
-26-
CSC-326 Transformer Protection IED Technical Manual
A B C
a A
Side 1:
b
C B
c
Side 2:
a b c
Figure 4-12 Vector Group compensation for Yd11 transformer
I A 1 -1 0 I A
1
I B 0 1 -1 I B
I 3
-1 0 1 I C
C
4.1.1.4.13 Example for Dy1 connection, including similar ones of Dy1, Dyn1 and
Dyn1 + earthed Transformer.
A B C
A a
Side 1:
c
C B
Side 2: b
a b c
Figure 4-13 Vector Group compensation for Dy1 transformer
I a 1 -1 0 I a
1
I b 0 1 -1 I b
I 3
-1 0 1 I c
c
4.1.1.4.14 Example for Dy3 connection, including similar ones of Dy3, Dyn3 and
Dyn3 + earthed Transformer.
-27-
CSC-326 Transformer Protection IED Technical Manual
A B C
b A
Side 1: c
C B
a
Side 2:
c a b
Figure 4-14 Vector Group compensation for Dy3 transformer
I a 0 -1 1 I a
1
I b 1 0 -1 I b
I 3
-1 1 0 I c
c
4.1.1.4.15 Example for Dy5 connection, including similar ones of Dy5, Dyn5 and
Dyn5 + earthed Transformer.
A B C
A b
Side 1:
a
C B
c
Side 2:
c a b
Figure 4-15 Vector Group compensation for Dy5 transformer
I a -1 0 1 I a
1
I b 1 -1 0 I b
I 3
0 1 -1 I c
c
4.1.1.4.16 Example for Dy7 connection, including similar ones of Dy7, Dyn7 and
Dyn7 + earthed Transformer.
-28-
CSC-326 Transformer Protection IED Technical Manual
A B C
c A
Side 1:
a
C B
b
Side 2:
b c a
Figure 4-16 Vector Group compensation for Dy7 transformer
I a -1 1 0 I a
1
I b 0 -1 1 I b
I 3
1 0 -1 I c
c
4.1.1.4.17 Example for Dy9 connection, including similar ones of Dy9, Dyn9 and
Dyn9 + earthed Transformer.
A B C
A c
Side 1:
b
C B
a
Side 2:
b c a
Figure 4-17 Vector Group compensation for Dy9 transformer
I a 0 1 -1 I a
1
I b -1 0 1 I b
I 3
1 -1 0 I c
c
4.1.1.4.18 Example for Dy11 connection, including similar ones of Dy11, Dyn11
and Dyn11 + earthed Transformer.
-29-
CSC-326 Transformer Protection IED Technical Manual
A B C
a A
Side 1:
b
C B
Side 2: c
a b c
Figure 4-18 Vector Group compensation for Dy11 transformer
I a 1 0 -1 I a
1
I b -1 1 0 I b
I 3
0 -1 1 I c
c
Some cautions for the setting ―Vector Group Angle (VET GRP ANGLE)‖ are follows:
Table 11 Instruction for Vector Group Angle setting
Setting name values
HV WIND CONN/Y-0 0 0 0 1 1 1 0 1
D-1
MV WIND CONN/Y-0 0 1 0 1 1 0 1 0
D-1
Note:
If the winding connection mode is set error or invalid, alarm report ―SetErr‖
will be sent out with the parameter ―WIND CONN‖.
If the vector group angle is set error or invalid, alarm report ―SetErr‖ will be
sent out with the parameter ―VET GRP‖.
-30-
CSC-326 Transformer Protection IED Technical Manual
protection is provided for fast tripping on heavy internal faults. As soon as the
differential current rises above the threshold I D (setting I D ), a trip signal is
issued regardless of the magnitude of the restraining current. This is always the case
when the short-circuit current is higher than 1/Ud*IN.
This stage can operate even when, for example, a considerable second harmonic is
present in the differential current, which is caused by current transformer saturation
by a DC component in the short-circuit current, and which could be interpreted by the
inrush inhibit function as an inrush current.
This high-current stage evaluates the fundamental component of the differential
current as well as the instantaneous values, Instantaneous value processing ensures
fast tripping even in case the fundamental component of the current is strongly
reduced by current transformer saturation. Fast trip area is shown in the Figure 7.
Idiff
Fast trip area
ID>>
Differential current
Slope 3
Trip area
Slope 2
block area
Slope 1
Ires
ID >
IR1 IR2 Restraint current
-31-
CSC-326 Transformer Protection IED Technical Manual
I D - Setting for the sensitivity threshold of the differential protection, (setting ―DIFF
ID‖)
I R1 - Setting for the first breakpoint restraint current, (setting ―DIFF IR1‖)
I R 2 - Setting for the second breakpoint restraint current, (setting ―DIFF IR2‖)
If the quantities result into a locus in the trip area, a trip signal is given. This stage
can‘t operate when it is the inrush or overexcitation stabilization.
CSC-326 provides 2 schemes to cope with the magnetizing inrush conditions. One
scheme is 2nd harmonic stabilization; the other scheme is fuzzy recognition of inrush
conditions based on the waveform. The two schemes are convenient for user to
select by the setting―2nd HAR NOT WAVE‖ (1- 2nd harmonic; 0-fuzzy recognition of
inrush based on waveform).
I d
- Fundamental frequency component of differential current.
In ―modern type‖ transformers in particular, the 2nd harmonics content may not
exceed the threshold value in all three phases on switch-on. To avoid spurious
tripping, the cross block function is activated. As soon as an inrush current is
detected in one phase, the other phases of the differential protection stage are
blocked.
I (k )
Assume differential current derivative as , sampling number per circle is 2n, for
sequence of number:
-32-
CSC-326 Transformer Protection IED Technical Manual
X (k ) I (k ) I (k n) /( I (k ) I (k n) ), k 1,2...n
(5-4)
Since the smaller X (k ) is, the more fault current information the point contains.
Degree of confidence for fault current is larger for this point. Otherwise, the larger
X (k ) is, the more inrush current information the point contains. Degree of
confidence for inrush current is larger for this point. Assume membership function
as A[ X (k )] , for k 1,2...n , get the fuzzy similarity coefficient N with point of one cycle:
n
N A[ X (k )] / n
k 1 (5-5)
Assume threshold K, if NK, consider as fault current .otherwise, consider as inrush
current.
The blocking mode is for each phase, which means that current is considered as
inrush current. Percentage differential current protection of this phase is blocked.
CT failure supervision can be enabled or disabled through setting ―CT FAIL DETECT‖
(1-On, 0-Off), when CT failure, if the differential protection is in trip area, the
differential will trip.
The criteria for CT failure detection are as follows:
All three phases are normal, and the differential current is near to zero. When one
phase current is decreased to less than a threshold (half of the memory current),
maybe CT failure occurs in the mutative phase.
Only one phase in one side has no current and all three phases in others sides are
normal and differential current is more than a threshold, maybe CT failure occurs in
the phase without current.
CT failure detection logic is shown in Fig.9.
CT saturation recognition is integrated in differential protection. The criteria for CT
saturation are as follows:
2nd and 3rd harmonic current of all phase current, if the result of 2nd and 3rd
harmonic is more than a threshold (fixed in the software), maybe CT
saturation occurs.
Making use of the sampling differential to judge whether internal fault induce
the CT saturation.
If the CT saturation induced by external fault, the differential protection will be blocked,
whereas the protection will give trip signal.
-33-
CSC-326 Transformer Protection IED Technical Manual
>=1
ID >
2nd HAR ON
I dA.2 K 2 I dA &
IDIFF> Trip
&
I dB .2 K 2 I dB >=1
I dC .2 K 2 I dC
5th HAR ON
I dA.5 K 5 I dA
&
I dB.5 K 5 I dB >=1
I dC .5 K 5 I dC
I dA ISet
I dB I Set >=1
&
I dC I Set 5s DIFF Alarm
DIFF ALARM ON
Fig. 6 Tripping logic of the differential protection
CT FAIL DETECT
Max{Id_A,Id_B, Id_C}>0.3*ID>
Among{IMA,IMB,IMC}, only 1
or 2 phase current decreased
≥1 & CT Fail
Among {IHA,IHB,IHC} and &
{ILA,ILB,ILC}
All currents without changing
-34-
CSC-326 Transformer Protection IED Technical Manual
-35-
CSC-326 Transformer Protection IED Technical Manual
Note:
When the equipment is delivered, the differential protection function is switched to
0(OFF), This is because this protection function must not be used before at least the
vector group angle and common parameters for every side have been correctly set.
Without these settings the equipment may show unpredictable behavior.(e.g.
tripping)!
The restricted earth fault protection detects earth faults in transformers. It is sensitive,
and more sensitive than the classical differential protection. Typical application would
be star point earthing transformers and auto-transformers. The restricted earth fault
protection is relative to the winding connection mode. If delta connection is set in
Common Para setting value, the protection will be invalid.
A precondition is that a CT is installed in the star point connection, i.e. between the
star point and earth. The star point CT and the three phase CTs define the limits of
the protected zone exactly.
Examples are illustrated in the Fig. 8 to Fig. 9.
CSC-326 3I01
3I01
CSC-326
-36-
CSC-326 Transformer Protection IED Technical Manual
When an earth fault occurs in the protected zone, a neutral current 3I 01 will flow;
depending on the neutral point earthing conditions of the power system a further
neutral current may be recognized in the residual current path of the phase CTs.
Since all currents which flow into the protected zone are defined positive, the residual
current from the system will be more or less in phase with the neutral point current.
When an earth fault occurs outside the protected zone, a neutral point current 3I 01
will flow equally; but the residual current of the phase CTs 3I 02 is now of equal
magnitude and in phase opposition with the neutral point current.
When a fault without earth connection occurs outside the protected zone, a residual
current may occur in the residual current path of the phase CT which is caused by
different saturation of the phases under strong through-current conditions. This
current could simulate a fault in the protected zone. Wrong tripping must be avoided
under such condition.
I diff 0 I res0
The differential current and the restraining current are calculated
according to formula (5-6),
I diff 0 I
and res 0 are compared by the restricted earth fault protection with the
operating characteristic according to the following formula(5-7), Ratio compensation
and CT fault recognition etc are integrated in the protection.
I diff 0 I 0 D I res0 I 0 D / S 0 D
I diff 0 S 0 D I res0 I res0 I 0 D / S 0 D
(5-7)
Where:
I 0D
- setting for the sensitivity threshold of restricted earth fault protection
S 0 D - Slope of the branch
I Diff0
Trip area
S0D
I 0D
block area
I Res0
-37-
CSC-326 Transformer Protection IED Technical Manual
If 3-phase CT ratio is unequal to REF CT ratio, the difference in currents may result
an error that leads to a zero differential current. So the reference side is taken and
zero differential ratio compensation is calculated by the software.
For normal transformer, zero differential ratios are calculated according to the
following formula:
n REFHV n REFMV n REFLV
K REFHV K REFMV K REFLV
n HV n MV n LV
, ,
Where:
K REFHV
-ratio compensation for HV NCT;
K REFMV -ratio compensation for MV NCT;
For autotransformer, zero differential ratios are calculated according to the following
formula:
n MV n REF
K MV K REF
n HV n HV
,
Where:
K MV -ratio compensation for MV CT;
Note:
To ensure the accuracy of devices, range of ratio compensation should be 0.1 ~ 5.
When the imbalance zero differential current is more than a threshold (settable),
alarm will be given to remind user to detect the secondary circuit.
In order to avoid the incorrect alarm, a step is adopted for the threshold when the
zero differentials current is less than limits. It is shown in following formula.
Timer for both trip stage and alarm stage also can be settable.
-38-
CSC-326 Transformer Protection IED Technical Manual
REF TRIP ON
Idiff0>Ialarm.0
Fig. 11 Tripping logic of the restricted earth fault protection
Tripping logic of the restricted earth fault protection is shown in Fig. 11.
-39-
CSC-326 Transformer Protection IED Technical Manual
iron core and to large eddy current losses. The overexcitation protection feature
servers to measure the voltage/frequency ratio which is proportional to the B
induction and puts it in relation to the BN nominal induction. In this context, both
voltage and frequency are related to nominal values of the object to be protected
transformer. The formula (5-8) is for calculating the voltage/hertz ratio. The
calculation is based on the maximum voltage of the three phase-neutral or phase-
phase voltages. Setting ‖V/F Voltage (1-VPP, 0-VPN)‖ is used to select the voltage
for overexcitation protection from phase-to-phase voltage or phase-neutral voltage.
The frequency range from 25Hz to 65Hz can be monitored in this way.
B U f U*
N
BN U N f N f*
(5-8)
Where:
N- ratio of volt/hertz
U- phase-neutral or phase-phase voltage (selectable)
The overexcitation protection feature includes two staged characteristics and one
thermal characteristic for an approximate modeling of the heating which the
overexcitation may cause to the protected transformers. The inverse characteristic
can be set via thirteen points derived from the manufacturer data (see Fig. 12); In
addition, a definite-time alarm stage and a definite-time trip stage can be used.
u/f
overflux trip stage
1.70
Pickup threshold u/f
1.65
1.60
1.55
1.50
1.45
Inverse trip stage
1.40
1.35
1.30
1.25
1.20
1.15
1.10
-40-
CSC-326 Transformer Protection IED Technical Manual
U AB
V / F _ Alarm
f
U BC
V / F _ Alarm >=1
f
U CA
V / F _ Alarm &
f
V/F Voltage VP-P
UA
V / F _ Alarm
f &
UB
V / F _ Alarm >=1
f
UC
V / F _ Alarm
f
U AB
V / F _ Trip
f
U BC
V / F _ Trip >=1
f
U CA
V / F _ Trip &
f
V/F Voltage VP-P
V/F Trip> ON
T Trip DEF V/ F Trip
UA
V / F _ Trip
f
&
UB
V / F _ Trip >=1
f
UC
V / F _ Trip
f
IVR V/F PA
&
IVR V/F PB >=1
IVR V/F PC
-41-
CSC-326 Transformer Protection IED Technical Manual
-42-
CSC-326 Transformer Protection IED Technical Manual
1-VPP; 0-VPN.
In one function, above the double line for settings, below double lines for
Control word.
-43-
CSC-326 Transformer Protection IED Technical Manual
U A U B
Z AB
I A I B
U B U C
Z BC
I B IC
Z CA U C U A
IC I A
(5-9)
Where
ZAB, ZBC, ZCA: phase-to-phase distance
Phase-to-earth distance protection has one settable distance stage, with 1 timer
delay setting. The formula for calculation phase-to-earth distance is as follow:
U
Z
I K 3I0
(5-10)
Where:
U - Phase voltage ( A, B, C )
X X
XZ XZ×NZ
RZ
R RZ×NZ R
RZ×NZ
RZ
XZ×NZ XZ
-44-
CSC-326 Transformer Protection IED Technical Manual
When all kinds of faults occur in the protected section, current in HV or MV side will
be abrupt change. Abrupt current startup element is adopted in distance protection;
the formula is as (5-11):
i 0.2 I N
i i (t ) i (t n) 2i (t 2n)
(5-11)
Where:
i - abrupt current startup element
When the imbalance fault occurs in the protected section, negative current occurs at
the same time. Using negative current is helpful to detect the imbalance faults.
Auxiliary negative current startup element adopts formula (5-12):
I 2 0.2I ie i h, m
( ) (5-12)
Where
I ie - rated current of HV or MV side.
Phase-to-phase distance and phase-to-earth distance have same logic. The typical
logic of 1 stage of distance protection is shown in Fig. 15.
DIS ON
I2>0.2Ie
>=1 T DIS Trip
i 0.2 I N &
Distance Point
inside the Circle
VT failure
-45-
CSC-326 Transformer Protection IED Technical Manual
-46-
CSC-326 Transformer Protection IED Technical Manual
Remarks:
In one function, above the double line for settings, below double lines for
Control word.
This protection function is a backup protection for the transformer and the power
system. The protection comprises 2 stages definite overcurrent I and 1 stage IDMTL
overcurrent. The integrated directional function can be applied to the overcurrent
protection via binary settings. This function is offered in every side of the transformer.
If the direction is disabled, the overcurrent element only use the maximum current of
three phase current, the operation criterion is
max( I a , I b , I c ) I set
(5-13)
Where:
I set
-setting for overcurrent protection.
If the direction is enabled, the overcurrent element operate for each phase, the
operation criterion is:
-47-
CSC-326 Transformer Protection IED Technical Manual
I I set ( a, b, c ) (5-14)
IDMTL overcurrent element using the IEC or ANSI curves is provided. Both IEC
curves and ANSI curves can be expressed by one formula as follows,
A
t M P
B
I
1
I
S (5-15)
Where:
I - Fault current;
I S -current setting;
M -time multiplier;
A, P, B- the characteristic parameter for IDMTL curves, reference to Table 16.
IEC IDMTL curves include four kind curves, and they are NI (Normal Inverse), VI
(Inverse), EI (Extreme Inverse), and LTI. ANSI curves include three kinds of curves,
and they are MI, VI and EI. The maximum timer t for IEC and ANSI is fixed to 100s.
In order to meet the IEC and ANSI curves, the function include setting M, setting A,
I
setting P, setting B and setting S .
Table 16 parameters for IDMTL curves
Curves No. IDMTL Curves Parameter A Parameter P Parameter B
1 IEC NI 0.14 0.02 0
2 IEC VI 13.5 1.0 0
3 IEC EI 80.0 2.0 0
4 IEC LTI 120.0 1.0 0
5 ANSI MI 0.0515 0.02 0.114
6 ANSI VI 19.61 2.0 0.491
7 ANSI EI 28.2 2.0 0.1217
The phase angle difference of input current and voltage of the directional element
is 90 , and the operation range is
lm 85 . There are three separate directional
elements.
lm is positive when voltage is leading to current.
-48-
CSC-326 Transformer Protection IED Technical Manual
Ia
850 lm
45
0
U bc U bc
850
lm 1350
Ia
a) Direction to transformer b) Direction to system
The logic for Definite and IDMTL overcurrent protection is shown in Fig. 17.
O/C ON
I>Iset &
O/C DIR ON
T OC Trip
VT failure &
DIR Positive
IDMTL O/C ON
Inverse Curve> &
IDMTL DIR ON
T IDMTL OC Trip
VT failure &
DIR Positive
-49-
CSC-326 Transformer Protection IED Technical Manual
-50-
CSC-326 Transformer Protection IED Technical Manual
-51-
CSC-326 Transformer Protection IED Technical Manual
This protection function is a backup protection for the transformer and the power
system. The protection comprises 2 stages definite residual current 3I0 and 1 stage
IDMTL neutral current. The integrated directional function can be applied to the
neutral current protection via binary settings.
This protection is only using as backup protection for transformer and adjacent
element for ground fault in directly earthed system. This function is offered in every
side of the transformer.
Zero sequence overcurrent element calculated by three phase current for every side.
3I 0 3I 0set (5-16)
Where:
IDMTL neutral current curves are same to IDMTL overcurrent curves, it is reference
to IDMTL overcurrent.
Voltage and current for zero sequence directional elements all are calculated by three
-52-
CSC-326 Transformer Protection IED Technical Manual
N/C ON
3I0>3I0set &
N/C DIR ON
T NC Trip
VT failure &
DIR Positive
IDMTL N/C ON
Inverse Curve> &
IDMTL DIR ON
T IDMTL NC Trip
VT failure &
DIR Positive
Fig. 19 Tripping logic for definite and IDMTL neutral current protection
-53-
CSC-326 Transformer Protection IED Technical Manual
-54-
CSC-326 Transformer Protection IED Technical Manual
This protection is often used for the transformer which the neutral is not earthed. The
protection comprises 2 stage 3U0, 1st stage for alarming, and 2nd stage for tripping.
This function is offered in every side of the transformer.
For LV side, neutral displacement protection adopts the zero sequence voltage
calculated by three phase voltage.
3U0> Alarm ON
3U0> & T1 3U0 Alarm
3U0> Trip ON
3U0> & T2 3U0 Trip
-55-
CSC-326 Transformer Protection IED Technical Manual
Transformer design has changed, with less and less metal being used per MVA of
transformed power. This has reduced the withstand time a transformer can be
allowed to be run in an overloaded state. It is becoming more important to provide an
additional thermal protection to supplement the Winding Temperature device.
Thermal overload protection characteristic is provided as THERMAL IEC 60255-8.
There are IEC cold and IEC hot curves.
The cold curve is
I eq 2
t ln 2 2
I eq I
(5-17)
The hot curve is
I eq (1 H / C ) I P
2 2
t ln
I eq I
2 2
(5-18)
Where:
t- thermal trip time
2
I eq I eq
I A IB IC
- Equivalent thermal current, 3 ,
- Thermal time constant
IP
- Prior current takes into account cyclic loading.
-56-
CSC-326 Transformer Protection IED Technical Manual
When the thermal overload is accumulated to 80% of the total thermal ability, the
alarm report ―THERM Alarm‖ will be given.
Other auxiliary protections are provided. For example, overload protection. The
overload protection is to protect all sides of windings of transformer continuous
overload currents. The protection only comprises a definite time alarm stage.
Overload protection use the maximum current element of three phases.
The logic for overload protection is shown in Fig. 21.
-57-
CSC-326 Transformer Protection IED Technical Manual
4.10 VT failure
4.10.1 Function description
VT failure supervision can be enabled or disabled through setting ―VT FAIL DETECT‖
(1-On, 0-Off), when VT failure, the distance protection will be blocked.
VT failure includes three phase VT failure element and single or two phase VT failure
element. The criteria for VT failure detection are as follows:
3 phases VT failure element: voltages of three phases all are under 18V and
current of any phase is larger than threshold (fixed in the software, for 1A CT,
the threshold is 0.06A; for 5A CT, the threshold is 0.3A.), confirm three VT
failure over 10s. The logic for 3 phases VT failure is shown in Fig. 22.
VT FAIL DETECT
UA<18V
UC<18V
10s VT Fail
IA>Iset
IB>Iset >=1
IC>Iset
VT FAIL DETECT
|UAB-UBC|>18V
|UCA-UAB|>18V
10s VT Fail
U A U B U C 18V
4.11 DI Trip DO
External digital input operated record disturbance functions are also provided.
-58-
CSC-326 Transformer Protection IED Technical Manual
There are several special digital inputs which can trip respective digital output
according to the anticipated setup in control-word setting value. At present three DIs
(DI1~DI3) are provided. Whether DI1~DI3 will trip DO1~DO3 respectively or not
depends on the corresponding settings.
The logic for DI 1 trip Digital Output (DO) 1 directly is shown in Fig. 24. The instance
of DI2 to DO2 and DI3 to DO3 is similar to DI1 to DO1.
DI 1 is high
& DO 1
DI 1 enable DO 1
LED 7
-59-
CSC-326 Transformer Protection IED Technical Manual
-60-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Function
options setting
protection
Neutral CT (NCT)
parameter
14. HV NCT SEC 1 OR 5A 1 Secondary(SEC) current in HV
s for HV
side for REF
side
1..1000 Nominal voltage (UN) in Middle
15. MV UN 110
kV voltage (MV)side
Voltage transformer(VT) Ratio in Common
16. MV VT RATIO 1..9999 1100
MV side parameter
50..9999 CT Primary(PRI) current in MV s for MV
17. MV CT PRI 1200 side
A side
CT Secondary(SEC) current in
18. MV CT SEC 1 OR 5A 1
MV side
1..1000k Nominal voltage (UN) in Low
19. LV UN 10.5
V voltage (LV)side
Voltage transformer(VT) Ratio in Common
20. LV VT RATIO 1..9999 105
LV side parameter
50..9999 CT Primary(PRI) current in LV s for LV
21. LV CT PRI 3000
A side side
CT Secondary(SEC) current in
22. LV CT SEC 1 OR 5A 1
LV side
-61-
CSC-326 Transformer Protection IED Technical Manual
options setting
-62-
CSC-326 Transformer Protection IED Technical Manual
side
MV DEF V/F
20. 1.0..1.5 1.1 Alarming setting of volt/hz
Alarm
MV T DEF V/F Timer setting for volt/hz
21. 0.1..9999s 10
Alarm alarming stage
Tripping setting of definite
22. MV DEF V/F Trip 1.0..1.5 1.2
volt/hz stage
MV T DEF V/F Timer setting for definite
23. 0.1..9999s 10
Trip volt/hz stage
MV T1 IVR
24. 0.1..9999s 90 Timer setting for volt/hz=1.10
V/F=1.10
MV T2 IVR
25. 0.1..9999s 80 Timer setting for volt/hz=1.15
V/F=1.15
MV T3 IVR
26. 0.1..9999s 70 Timer setting for volt/hz=1.20
V/F=1.20
MV T4 IVR
27. 0.1..9999s 60 Timer setting for volt/hz=1.25
V/F=1.25
MV T5 IVR
28. 0.1..9999s 50 Timer setting for volt/hz=1.30
V/F=1.30
MV T6 IVR
29. 0.1..9999s 45 Timer setting for volt/hz=1.35
V/F=1.35
MV T7 IVR
30. 0.1..9999s 40 Timer setting for volt/hz=1.40
V/F=1.40
MV T8 IVR
31. 0.1..9999s 35 Timer setting for volt/hz=1.45
V/F=1.45
MV T9 IVR
32. 0.1..9999s 30 Timer setting for volt/hz=1.50
V/F=1.50
MV T10 IVR
33. 0.1..9999s 25 Timer setting for volt/hz=1.55
V/F=1.55
MV T11 IVR
34. 0.1..9999s 20 Timer setting for volt/hz=1.60
V/F=1.60
MV T12 IVR
35. 0.1..9999s 15 Timer setting for volt/hz=1.65
V/F=1.65
MV T13 IVR
36. 0.1..9999s 10 Timer setting for volt/hz=1.70
V/F=1.70
-63-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Function
options setting
7. IDMTL HV OC I 0.1..100A 5
Phase-to-earth
8. HV DIS PH-N X 0.1..125Ω 10 distance(DIS PH-N)
setting X
Phase-to-earth
9. HV DIS PH-N R 0.1..125Ω 1 distance(DIS PH-N) HV earth
setting R distance
HV DIS OFFSET protection
10. 0.0..1.00 1 Offset ratio to setting (DIS PH-N)
RATIO
zero sequence
11. HV K FACTOR 0.0..99.0 1
compensation coefficient
12. T HV DIS PH-N 0.1..20.0s 5 Timer setting for DIS PH-N
1st stage Phase-to-phase
13. HV DIS1 PH-PH X1 0.1..125Ω 10
distance(DIS1) setting X
1st stage Phase-to-phase
14. HV DIS1 PH-PH R1 0.1..125Ω 1
distance(DIS1) setting
HV DIS1 OFFSET Offset ratio to setting of 1st
15. 0.0..1.00 1
RATIO stage DIS1 HV
Timer setting for 1st stage inter-phase
16. T HV DIS1 PH-PH 0.1..20.0s 5
DIS1 distance
2nd stage Phase-to-phase protection
17. HV DIS2 PH-PH X2 0.1..125Ω 10
distance(DIS2) setting X (DIS
2nd stage Phase-to-phase PH-PH)
18. HV DIS2 PH-PH R2 0.1..125Ω 1
distance(DIS2) setting
HV DIS2 OFFSET Offset ratio to setting of 2nd
19. 0.0..1.00 1
RATIO stage DIS2
Timer setting for 2nd stage
20. T HV DIS2 PH-PH 0.1..20.0s 5
DIS2
Neutral Current (NC)
21. HV NC I01 0.1..100A 100
setting for 1st stage ( I01 )
Timer setting for 1st stage Definite and
22. T HV NC I01 0.1..20s 20 IDMTL
NOC
Neutral Current (NC) neutral
23. HV NC I02 0.1..100A 100 current
setting for 2nd stage ( I02 )
Timer setting for 2nd stage protection
24. T HV NC I02 0.1..20s 20 (with
NOC
IDMTL HV NC selective
25. 0.025..2 1 direction) in
TimeMult Ref to IEC and ANSI
IDMTL HV NC CRV High
26. 1.. 7 7 Curves
SEL voltage side
Please refer to NOTE.
27. IDMTL HV NC I0 0.1..100A 5
IDMTL HV IDMTL
28. 0.025..2 1
NeuTimeMult Ref to IEC and ANSI neutral
IDMTL HV Neu CRV Curves, Please refer to current
29. 1.. 7 7
SEL NOTE. protection
30. IDMTL HV Neu I0 0.1..100A 5 in HV side
-64-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Function
options setting
HV THERM Time const for thermal overload
32. 1..1000s 10
TimeConst overload protection protection
HV WeightFactor
33. 0..1 0 Hot cool weight factor H/C
H/C
Overcurrent Setting of
34. HV OVLD I 0.1..20A 100 Definite
overload
overload
0.1..3600
35. T HV OVLD I 20 Timer setting for overload protection
s
NOTE:
IDMTL characteristic is:
A
t M P
B
I
1
IS
In which, 7 IDMTL curves can be set.
Table 26 Value of A,P and B for each curve
Curves No. IDMTL Curves Parameter A Parameter P Parameter B
-65-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Function
options setting
0.1..100
7. IDMTL MV OC I 5
A
Phase-to-earth
0.1..125
8. MV DIS PH-N X 10 distance(DIS PH-N)
Ω
setting X
Phase-to-earth
0.1..125
9. MV DIS PH-N R 1 distance(DIS PH-N) MV earth
Ω
setting R distance
MV DIS OFFSET protection
10. 0.0..1.00 1 Offset ratio to setting
RATIO (DIS PH-N)
zero sequence
11. MV K FACTOR 0.0..99.0 1
compensation coefficient
0.1..20.0
12. T MV DIS PH-N 5 Timer setting for DIS PH-N
s
0.1..125 1st stage Phase-to-phase
13. MV DIS1 PH-PH X1 10
Ω distance(DIS) setting X
MV DIS1 PH-PH 0.1..125 1st stage Phase-to-phase
14. 1
R1 Ω distance(DIS) setting
MV DIS1 OFFSET Offset ratio to setting of 1st
15. 0.0..1.00 1
RATIO stage DIS1
MV
0.1..20.0 Timer setting for 1st stage
16. T MV DIS1 PH-PH 5 inter-phase
s DIS1
distance
0.1..125 2nd stage Phase-to-phase
17. MV DIS2 PH-PH X2 10 protection
Ω distance(DIS2) setting X
(DIS PH-PH)
MV DIS2 PH-PH 0.1..125 2nd stage Phase-to-phase
18. 1
R2 Ω distance(DIS2) setting R
MV DIS2 OFFSET Offset ratio to setting of
19. 0.0..1.00 1
RATIO 2nd stage DIS2
0.1..20.0 Timer setting for 2nd stage
20. T MV DIS2 PH-PH 5
s DIS2
0.1..100 Neutral Current (NC)
21. MV NC I01 100
A setting for 1st stage ( I01 )
Timer setting for 1st stage Definite and
22. T MV NC I01 0.1..20s 20
NOC IDMTL
0.1..100 Neutral Current (NC) neutral
23. MV NC I02 100
A setting for 2nd stage ( I02 ) current
Timer setting for 2nd stage protection
24. T MV NC I02 0.1..20s 20
NOC (with
IDMTL MV NC selective
25. 0.025..2 1
TimeMult direction) in
IDMTL MV NC CRV Ref to IEC and ANSI Middle
26. 1.. 7 7
SEL Curves voltage side
0.1..100
27. IDMTL MV NC I0 5
A
Overcurrent Setting of
28. MV OVLD I 0.1..20A 100 Definite
overload
overload
0.1..360
29. T MV OVLD I 20 Timer setting for overload protection
0s
-66-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Function
options setting
Overcurrent (OC) setting
1. LV OC I1 0.1..100A 100
for 1st stage ( I1 )
Timer setting for 1st stage
2. T LV OC I1 0.1..20s 20 Definite and
OC
Overcurrent (OC) setting IDMTL
3. LV OC I2 0.1..100A 100 overcurrent
for 2nd stage ( I2 )
protection
Timer setting for 2nd
4. T LV OC I2 0.1..20s 20 (with
stage OC
selective
IDMTL LV OC
5. 0.025..2 1 direction) in
TimeMult
IDMTL LV OC Ref to IEC and ANSI Middle
6. 1.. 7 7 Curves voltage side
CRV SEL
7. IDMTL LV OC I 0.1..100A 5
Neutral voltage setting for
8. LV 3U0 ALARM 2..100V 100
alarming stage Neutral
Timer setting for neutral displaceme
9. T LV 3U0 ALARM 0.1..20s 20
voltage nt
Neutral voltage setting for protection in
10. LV 3U0 TRIP 2..100V 100
tripping stage Low voltage
Timer setting for neutral side
11. T LV 3U0 TRIP 0.1..20s 20
voltage
Overcurrent Setting of Definite
12. LV OVLD I 0.1..20A 20
overload overload
13. T LV OVLD I 0.1..3600s 20 Timer setting for overload protection
Remark:
The former eight bits in the TRIP setting control-words in Table 29 are of meaning,
which is ―DO TRIP-1 ON/OFF‖ ~ ―DO TRIP-8 ON/OFF‖ respectively.
-67-
CSC-326 Transformer Protection IED Technical Manual
Remarks:
These settings are only used for test, they are calculated by software automatically
according to the common parameters. These settings cannot be modified by user.
-68-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Menu
options setting
2nd harmonic (HAR) inhibit not the
2nd HAR NOT fuzzy recognition based on the
3. 1/0 0
WAVE waveform(WAVE)
1-2nd harmonic on; 0- waveform on
5th harmonic (HAR) inhibit on
4. 5th HAR ON 1/0 0
1-on; 0-off.
Differential current (DIFF) Alarming
5. DIFF ALARM ON 1/0 0 on
1-on; 0-off.
CT FAIL CT Failure Detection On/Off
6. 1/0 0
DETECT 1-On, 0-Off.
HV REF TRIP HV Restricted earth fault(REF) Trip
7. 1/0 0 ON
ON REF
1-on; 0-off.
Set
HV REF ALARM HV Restricted earth fault(REF)
8. 1/0 0 Alarm ON
ON
1-on; 0-off.
HV Definite Overexcitation (V/F)
HV DEF V/F
9. 1/0 0 Alarming on
ALARM ON
1-on; 0-off.
HV Definite (DEF)Overexcitation
HV DEF V/F
10. 1/0 0 (V/F) on
TRIP ON
1-on; 0-off.
HV Inverse (IVR)Overexcitation
11. HV IVR V/F ON 1/0 0 (V/F) on
1-on; 0-off.
HV Overexcitation protection uses
HV V/F Voltage phase-to-phase voltage(VPP) or
12. 1/0 0
(1-VPP,0-VPN) phase-to-earth voltage(VPN) Overex
1-VPP; 0-VPN.
citation
MV Definite Overexcitation (V/F)
MV DEF V/F Set
13. 1/0 0 Alarming on
ALARM ON
1-on; 0-off.
MV Definite (DEF)Overexcitation
MV DEF V/F
14. 1/0 0 (V/F) on
TRIP ON
1-on; 0-off.
MV Inverse (IVR)Overexcitation
15. MV IVR V/F ON 1/0 0 (V/F) on
1-on; 0-off.
MV Overexcitation protection uses
MV V/F Voltage phase-to-phase voltage(VPP) or
16. 1/0 0
(1-VPP,0-VPN) phase-to-earth voltage(VPN)
1-VPP; 0-VPN.
1st stage(_1) Overcurrent (OC) in
17. HV OC_1 ON 1/0 0
HV side on
Direction (DIR) detection of 1st
HV OC_1 DIR
18. 1/0 0 Stage(_1) of Overcurrent(OC) in
ON HV
HV side
Backup
Direction (DIR) of 1st stage (_1)
HV OC_1 DIR Set
19. 1/0 0 Overcurrent (OC)to system not
TO SYS
transformer itself in HV side
2nd stage(_2) Overcurrent (OC) in
20. HV OC_2 ON 1/0 0
HV side on
-69-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Menu
options setting
Direction (DIR) detection of 2nd
HV OC_2 DIR
21. 1/0 0 Stage(_2) of Overcurrent(OC) in
ON
HV side
Direction (DIR) of 2nd stage (_2)
HV OC_2 DIR
22. 1/0 0 Overcurrent (OC)to system not
TO SYS
transformer itself in HV side
HV IDMTL OC IDMTL Overcurrent (OC) in HV side
23. 1/0 0
ON on
HV IDMTL OC Direction (DIR) detection of IDMTL
24. 1/0 0
DIR ON Overcurrent(OC) in HV side
Direction (DIR) of IDMTL
HV IDMTL OC
25. 1/0 0 Overcurrent (OC)to system not
DIR TO SYS
transformer itself in HV side
HV DIS PH-N Phase to earth distance(DIS PH-N)
26. 0/1 0
ON in HV side on.
Phase to earth Distance (DIS
HV DIS PH-N
27. 0/1 0 PH-N) direction(DIR) to
DIR TO SYS
system(SYS) in HV side
HV DIS1 PH-PH 1st stage phase to phase distance
28. 0/1 0
ON (DIS1) in HV side on
1st stage Phase to phase Distance
HV DIS1 PH-PH
29. 0/1 0 (DIS1) direction(DIR) to
DIR TO SYS
system(SYS) in HV side
HV DIS2 PH-PH 2nd stage phase to phase distance
30. 0/1 0
ON (DIS2) in HV side on
2nd stage Phase to phase Distance
HV DIS2 PH-PH
31. 0/1 0 (DIS2) direction(DIR) to
DIR TO SYS
system(SYS) in HV side
1st stage(_1) Neutral Current (NC)
32. HV NC_1 ON 1/0 0
in HV side on
Direction(DIR) detection of 1st
HV NC_1 DIR
33. 1/0 0 stage(_1) Neutral Current (NC) in
ON
high voltage (HV)side on
Direction (DIR) of 1st stage (_1)
HV NC_1 DIR
34. 1/0 0 Neutral Current (NOC)to system
TO SYS
not transformer itself in HV side
2nd stage(_2) Neutral Current (NC)
35. HV NC_2 ON 1/0 0
in HV side on
Direction(DIR) detection of 2nd
HV NC_2 DIR
36. 1/0 0 stage(_2) Neutral Current (NC) in
ON
high voltage (HV)side on
Direction (DIR) of 2nd stage (_2)
HV NC_2 DIR
37. 1/0 0 Neutral Current (NC)to system not
TO SYS
transformer itself in HV side
HV IDMTL NC IDMTL Neutral Current (NC) in HV
38. 1/0 0
ON side on
Direction(DIR) detection of IDMTL
HV IDMTL NC
39. 1/0 0 Neutral Current (NC) in high
DIR ON
voltage (HV)side on
Direction (DIR) of IDMTL Neutral
HV IDMTL NC
40. 1/0 0 Current (NC)to system not
DIR TO SYS
transformer itself in HV side
-70-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Menu
options setting
HV NEU IDMTL
41. 1/0 0 Neutral IDMTL OC in HV side on
OC ON
HV THERM
42. 1/0 0 Thermal overload in HV side on
OVLD ON
43. HV OVLD ON 1/0 0 Overload (LOAD)in HV side on
1st stage(_1) Overcurrent (OC)
44. MV OC_1 ON 1/0 0
with time delay T in MV side on
Direction (DIR) detection of 1st
MV OC_1 DIR
45. 1/0 0 Stage(_1) of Overcurrent(OC) in
ON
MV side
direction (DIR) of 1st stage (_1)
MV OC_1 DIR
46. 1/0 0 Overcurrent (OC)to system not
TO SYS
transformer itself in MV side
2nd stage(_2) Overcurrent (OC)
47. MV OC_2 ON 1/0 0
with time delay T in MV side on
Direction (DIR) detection of 2nd
MV OC_2 DIR
48. 1/0 0 Stage(_2) of Overcurrent(OC) in
ON
MV side
direction (DIR) of 2nd stage (_2)
MV OC_2 DIR
49. 1/0 0 Overcurrent (OC)to system not
TO SYS
transformer itself in MV side
MV IDMTL OC IDMTL Overcurrent (OC) in MV
50. 1/0 0
ON side on
MV IDMTL OC Direction (DIR) detection of IDMTL
51. 1/0 0
DIR ON Overcurrent(OC) in MV side
Direction (DIR) of IDMTL
MV IDMTL OC
52. 1/0 0 Overcurrent (OC)to system not
DIR TO SYS
transformer itself in MV side
MV DIS PH-N Phase to earth distance(DIS PH-N)
53. 0/1 0
ON in MV side on.
Phase to earth Distance (DIS
MV DIS PH-N
54. 0/1 0 PH-N) direction(DIR) to
DIR TO SYS
system(SYS) in MV side
MV DIS1 PH-PH 1st stage phase to phase distance
55. 0/1 0
ON (DIS1) in MV side on MV
1st stage Phase to phase Distance Backup
MV DIS1 PH-PH
56. 0/1 0 (DIS1) direction(DIR) to Set
DIR TO SYS
system(SYS) in MV side
MV DIS2 PH-PH 2nd stage phase to phase distance
57. 0/1 0
ON (DIS2) in MV side on
2nd stage Phase to phase Distance
MV DIS2 PH-PH
58. 0/1 0 (DIS2) direction(DIR) to
DIR TO SYS
system(SYS) in MV side
1st stage(_1) Neutral Current (NC)
59. MV NC_1 ON 1/0 0
in MV side on
Direction(DIR) detection of 1st
MV NC_1 DIR
60. 1/0 0 stage(_1) Neutral Current (NC) in
ON
MV side on
Direction (DIR) of 1st stage (_1)
MV NC_1 DIR
61. 1/0 0 Neutral Current (NOC)to system
TO SYS
not transformer itself in MV side
2nd stage(_2) Neutral Current (NC)
62. MV NC_2 ON 1/0 0
in MV side on
-71-
CSC-326 Transformer Protection IED Technical Manual
Setting Default
No Setting Title Comment Menu
options setting
Direction(DIR) detection of 2nd
MV NC_2 DIR
63. 1/0 0 stage(_2) Neutral Current (NC) in
ON
MV side on
Direction (DIR) of 2nd stage (_2)
MV NC_2 DIR
64. 1/0 0 Neutral Current (NC)to system not
TO SYS
transformer itself in MV side
MV IDMTL NC IDMTL Neutral Current (NC) in MV
65. 1/0 0
ON side on
Direction(DIR) detection of IDMTL
MV IDMTL NC
66. 1/0 0 Neutral Current (NC) in high
DIR ON
voltage (MV)side on
Direction (DIR) of IDMTL Neutral
MV IDMTL NC
67. 1/0 0 Current (NC)to system not
DIR TO SYS
transformer itself in MV side
68. MV OVLD ON 1/0 0 Overload (LOAD)in MV side on
1st stage(_1) of Overcurrent (OC)
69. LV OC_1 ON 1/0 0
in LV side on
Direction (DIR) detection of 1st
70. LV OC_1 DIR ON 1/0 0 Stage(_1) of Overcurrent(OC) in LV
side
Direction (DIR) of 1st stage (_1)
LV OC_1 DIR TO
71. 1/0 0 Overcurrent (OC)to system not
SYS
transformer itself in LV side
2nd stage(_2) of Overcurrent (OC)
72. LV OC_2 ON 1/0 0
in LV side on
Direction (DIR) detection of 2nd
73. LV OC_2 DIR ON 1/0 0 Stage(_2) of Overcurrent(OC) in LV
side
Direction (DIR) of 2nd stage (_2)
LV OC_2 DIR TO
74. 1/0 0 Overcurrent (OC)to system not
SYS
transformer itself in LV side
LV IDMTL OC IDMTL Overcurrent (OC) in LV side LV
75. 1/0 0
ON on
Backup
LV IDMTL OC Direction (DIR) detection of IDMTL
76. 1/0 0 Set
DIR ON Overcurrent(OC) in LV side
Direction (DIR) of IDMTL
LV IDMTL OC
77. 1/0 0 Overcurrent (OC)to system not
DIR TO SYS
transformer itself in LV side
LV 3U0 ALARM Neutral displacement (3U0) alarm
78. 1/0 0
ON in LV side on
Neutral displacement (3U0) trip in
79. LV 3U0 TRIP ON 1/0 0
LV side on
VT Fail Block LV Neutral
VT Fail Block LV
80. 1/0 0 displacement (3U0)
3U0
1-Block 0-Not Block
81. LV OVLD ON 1/0 0 Overload (LOAD)in LV side on
DI1 ENABLE DI1 trip DO1 on 1-enable,
82. 1/0 0
DO1 0-disable
DI2 ENABLE DI2 trip DO2on 1-enable, Other
83. 1/0 0
DO2 0-disable Set
DI3 ENABLE DI3 trip DO3 on 1-enable,
84. 1/0 0
DO3 0-disable
-72-
CSC-326 Transformer Protection IED Technical Manual
-73-
CSC-326 Transformer Protection IED Technical Manual
-74-
CSC-326 Transformer Protection IED Technical Manual
6 Reports
6.1 Overview
The IED provides quick, complete and reliable information about disturbances in the
system, and about the operation and state of the IED. This information is important to
used for different purposes for operators and engineers in the short term (e.g.
corrective actions) and in the long term (e.g. Functional Analysis).
All information is divided into four types of reports:
event report;
Initiating report;
Alarm report;
Operation report;
-75-
CSC-326 Transformer Protection IED Technical Manual
-76-
CSC-326 Transformer Protection IED Technical Manual
12. MV DEF V/F Trip MV Overexcitation protection(V/F) tripping (Trip) with definite
13. MV IVR V/F Trip (DEF) and inverse(IVR) time characteristic
-77-
CSC-326 Transformer Protection IED Technical Manual
35. LV 3U0 Trip Zero sequence voltage (3U0) protection tripping (Trip) in LV side
36. HV Neu IDMTL HV Neutral current IDMTL
Alarm I is severe alarm. When alarm I happens, the alarm lamp on the front
panel of the device will flash, all of protection function will be switched out of
service and the trip power of protection will be blocked by the device.
Alarm II is other alarm. When alarm II happens, the alarm lamp on the front
panel of the device will light continuously, and the device will alarm the
corresponding abnormal status (for example, the circuit-breaker failure
startup digital input is abnormal), and will not block the trip power of
protection.
-78-
CSC-326 Transformer Protection IED Technical Manual
-79-
CSC-326 Transformer Protection IED Technical Manual
The event reports can be searched and read conveniently on the HMI
or by CSPC software tool, and can be printed automatically if the IED is
connected with a printer, and can be transmit to the substation
automation system automatically through dedicated network.
Number of IED;
2nd row:
Type of IED
Version of Software
3rd row:
-80-
CSC-326 Transformer Protection IED Technical Manual
Bay name
4th row:
-81-
CSC-326 Transformer Protection IED Technical Manual
Number of IED;
2nd row:
-82-
CSC-326 Transformer Protection IED Technical Manual
Last row:
Diagram Section:
X-ordinate:
Y-ordinate:
Number of IED;
2nd row:
Sampling rate;
Sampling times
The designations of bit in the word, which represent the state of binary inputs
and outputs;
-83-
CSC-326 Transformer Protection IED Technical Manual
Data Section:
X-ordinate:
Y-ordinate:
Data:
They are real-time sample values of analogue inputs and word of state of binary
inputs and outputs. The bit will be ―1‖ when the represented binary input or output is
present.
-84-
CSC-326 Transformer Protection IED Technical Manual
8 Operation
NOTE
During the equipment tests and start-up, the general safety
regulations applicable to electrical systems must be complied
with. Failure to comply with these regulations might cause harm
to the working staff and damage to property. All the inspections
and tests must only be carried out by specially trained personnel.
Check all the grounded connections of IED are reliably the related codes and
standards.
Forbid strictly to insert or draw out modules during the IED energized.
Forbid to press optionally the keypad on the front panel of IED during normal
operation.
The human-machine interface is simple and easy to understand – the whole front
-85-
CSC-326 Transformer Protection IED Technical Manual
8.1.2 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs in the CSC series. LCD screens and other details may differ but
the way the keys function is identical. The keys used to operate the IED are described
-86-
CSC-326 Transformer Protection IED Technical Manual
RESET key:
Reset LEDs
Return to normal scrolling display mode directly
RESET
The shortcut keys and functional keys are below the LCD on the front panel. These
keys are designated to execute the frequent menu operations for user‘s convenience.
The keys used to operate the IED are described below in table 8-2
Table 8-2: Shortcut keys and functional keys on the front of the IED
Key function
Report Report key:
Print the latest operation report
Set Setting key:
Print setting of current setting group
Sample Sample key:
Print current sampled data
Version Version key:
Print protection version information and current operating status
+ Plus key:
Switch next setting group forward as active setting group, meaning the number
8.1.4 LED
There are 8 LEDs on the left side of the LCD. The information that the LEDs indicate
-87-
CSC-326 Transformer Protection IED Technical Manual
Not used
Not used
8.1.5 LCD
The LCD on the HMI can display 8 lines with up to 28 characters per line, with blue
background.
The back light will turn on automatically, when one key is pressed or an alarm is
reported, until a set time delay after the last operation or alarm.
8.2 Menu
8.2.1 Introduction
Operating mode
Configuring mode
During the normal service without any operation, the LCD scrolling display the
information listed below:
-88-
CSC-326 Transformer Protection IED Technical Manual
Magnitude of P, Q;
Linkers enabled,
To Press SET to enter into main menu during Normal display mode. The default
operation password is 8888.
This mode is only for manufacturer to complete final configuration of IED before
delivery.
-89-
CSC-326 Transformer Protection IED Technical Manual
-90-
CSC-326 Transformer Protection IED Technical Manual
-91-
CSC-326 Transformer Protection IED Technical Manual
Notes:
In the IED test mode ( when the RELAY TEST binary input is present ),
operating reports are neither transported nor saved, just are printed or
displayed on PC. If disturbance record report need to be printed, but without
PC, only disturbance record data reports can be printed.
-92-
CSC-326 Transformer Protection IED Technical Manual
9.1.3 Check that all items are included in accordance with the delivery documents. Once
the IED has been started make sure that the software functions ordered have been
included in the delivery.
If transport damage is discovered appropriate action must be taken against the latest
carrier and the nearest Sifang office or representative should be informed. Sifang or
his partner should be notified immediately if there are any discrepancies in relation to
the delivery documents.
9.1.5 If the IED is repacked for transport again, the storage packing of the IED must provide
the proper degree of protection against various possible damages, in accordance
with IEC 60255-21-1 class 2 and IEC 60255-21-2 class 1.
9.2 Installation
9.2.1 Insert the IED into the opening (cut-out) in the panel. The bottom of the IED should be
supported on the frame of the panel.
9.2.2 Fix the IED by tightening all four screws against the panel. The IED ought to be fixed
on panel (tank), and every connection screws of the IED must be firmed.
Connect the earthing screw on the rear of the IED unit to the closest possible earthing
point in the cubicle. Electrical codes and standards require that protective earth
cables are green/yellow conductors with a cross section area of at least 2.5 mm2.
The cubicle must be properly connected to the station earthing system. Use a
conductor with a core cross section area of at least 4 mm2.
Use a solid conductor with a cross section area between 2.5-6 mm2 (AWG14-10) or a
stranded conductor with a cross section area between 2.5-4 mm2 (AWG14-12). The
screws used to fasten the conductors should be tightened.
-93-
CSC-326 Transformer Protection IED Technical Manual
Check the protective earthing conductors of IED are connected reliably in accordance
with the related standards and Codes.
Check that the wiring is in strict accordance with the supplied connection diagram.
Do not continue before any errors are corrected.
The CTs must be connected in accordance with the circuit diagram provided with the
IED, both with regards to phases and polarity.
Check that the auxiliary supply voltage remains within the permissible input voltage
range under all operating conditions. Check that the polarity is correct.
Preferably, disconnect the binary input connector from the binary input cards. Check
all connected signals so that both input level and polarity are in accordance with the
IEDs specifications.
Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and polarity are in accordance with IED
specifications.
-94-
CSC-326 Transformer Protection IED Technical Manual
9.3.8.1 Each module should be in the correct slot and be locked reliably to ensure the
connection between the male connector of the module and the female
connector welded on the main back board.
9.3.8.2 The IED is provided with current terminals with automatically operating
contacts for short-circuiting the CT secondary circuits when the transformer
input module is withdrawn from its connector. The short-circuiting contact
should be opened when the transformer input module is inserted into the
connector.
9.3.8.3 The jumpers and short-circuiting wires of each module is set correctly.
9.4.1.1 Energize DC power supply, the relay for loss of power alarm ought to be excited
reliably, and its contacts as X-c16 and X-a16 must be opened reliably.
9.4.1.2 Check the self startup performance of power:When the value of DC power supply is
modified gradually from 0 to 80% rating, contacts of the relay for loss of power alarm
must change from closed state to opened state supervised by versatile meter. Then,
when DC power supply is from off to on, the versatile meter operates as the same
results.
9.4.1.3 Testing of voltage output value and its stability:Every class output voltage must be
maintained stably as shown in Tab.9-4 when the input voltage of DC power supply is
UN.
Tab. 9-4
Test Point X-c14-c12 X-c4-c2 X-a4-a2 X-c26-c24 X10-c2-c8
Rating voltage of DC 5V +12V -12V 24V R24V
outputs
Permissive error 0%~+3% -20%~0% -20%~0% 0%~+5% 0%~+8%
range 5.0~5.15 9.6~12.0 -12.0~-9.6 24.0~25.2 24.0~25.92
-95-
CSC-326 Transformer Protection IED Technical Manual
9.4.1.4 Testing of DC power on and off rapidly: Power on and off rapidly for three times, no
abnormal case occurs for the IED.
9.4.2.1 Before IED energized, insert all modules into the corresponding slot of the IED
according to the configuration figure in the guide book, and connect the flat cable
between faceplate and communication board.
9.4.2.2 Switch on DC power supply; enter into debugging menu, Then enter into the menu of
―CPU setup‖, enable all CPU1 and CPU2,press the key of SET to save. And energize
the IED once again.
9.4.2.3.1 Enter Main Menu-Set Time,use square keyboard to set clock to current time. Then
return to the normal display of LCD, observe whether the running clock is normal or
not. Cut off DC power supply for 5 min, then switch on, check the time and date
displayed in LCD to conform that the clock is running and nicety during power turnoff.
9.4.2.3.3 Enter into Main Menu/Settings/Set Setting,modify and write protection setting of
selected setting group.
Set the address of RS-485 port whose range is 10H~ABH(the address of our IED
must not be repeated).
Examine that ―the address of Ethernet 1‖ and ―that of Ethernet 2‖are not set to be 0.
9.4.2.3.5 Enter into Main Menu/Setup/BayName,input the actual name and serial number of
line by means of ISN(internal statement number)(as shown at appendix) on faceplate
(or directly input by CSPC program).
9.4.2.3.6 Enter into Main Menu/Setup/Timemode to select the time synchronization mode.
If timing mode of minute pulse or second pulse is selected, symbol ―*‖ is displayed at
top right corner of LCD after GPS timing succeeds.
-96-
CSC-326 Transformer Protection IED Technical Manual
If ―Print record automatically‖ is set to ―√‖, record wave will be printed after fault. If it is
set to ―×‖, only fault reports will be printed while record wave will not, and record wave
need to be fetched. If Print control word is set to ―√‖, contents of control word can be
printed, if ―×‖, contents of control word cannot be printed. Print format of record data
can be set to format of ―wave‖ or ―data‖ with 《UP》 and 《DOWN》 keys.
The recommended setup is ―Print record automatically‖, ―Print control word‖ and
―Print format of record data‖ set to wave. If the protection operating results have some
questions, suggest that set ―Print format of record data‖ to ―data‖ at first, then, print a
record wave again(or use shortcut key F1 to directly print the latest one of record
data), after that, equipment testing can be followed. This can avoid losing data, and
causing disadvantage for furthermore analysis.
Testing print function of shortcut key: Use shortcut key on the front plate to
print, the printer ought to print normally.
9.8 Test
Enter into Main Menu-Test Do to perform output test. When output test is made, the
contacts of the corresponding relay ought to operate with lighting signal while other
contacts do not operate. Press button RESET on the faceplate to reset the energized
output. Test results should be consistent with the following table.
-97-
CSC-326 Transformer Protection IED Technical Manual
or analog quantities menu at first, and then enter into analog quantities menu to do it.
If they don‘t meet requirements, regulate them according to the following methods.
Notice to increase the setting value of startup elements.
To regulate zero drift, disconnect the IED with testing instrument or standard source
to ensure not any input in AC terminal of the IED. Enter into Main
Menu—Testing—AdjDrift, select all, and confirm it, then zero drift regulation can be
performed. If regulation succeeds, report ―zero drift regulation success‖. After this,
select Main Menu—Testing—ViewDrift,, current channel must be less than 0.1A
(rated value of TA 5A) or 0.02A (rated value of TA 1A), voltage channel must be less
than 0.1V.
Connect input terminals of voltage UA, UB, UC, employ testing instrument with grade
0.5 and the above whose outputs UA and UN are connected to protection terminals
X1-a11 and b11. Shorting b1-a2,b2-a3,b3-a4 of X1 respectively. Current outputs of
testing instrument are connected to protection terminals X1-a1 and b4. Enter into
Main Menu—Testing—AdjScale, press keys 《up down lst right》 and 《SET》 to
select all, set the regulation value to In and 50V, output AC quantities from testing
instrument to the protection system, then confirm these to execute. If fail to operate,
LCD displays analog channel error and the number of error channel. Check whether
connection, standard value and version are right or not.
After finishing calibration and zero drift regulation, measure linear error using testing
instrument with grade 0.5 and the above, and write down testing result. Requirements:
For secondary rated current 5A of TA, input currents 25A, 10A (the lasting time of the
above two is not allowed to exceed 10s), 2A, 1A and 0.4A respectively. For
secondary rated current 1A of TA, input currents 5A, 2A, 0.5A, 0.2A and 0.08A.
Supply voltage 60V, 30V, 5V, 1V and 0.4V respectively. Observe LCD display or
enter into Main Menu—Testing—ViewScale, ask that the difference between LCD
display value and external meter is less than 0.1V for 0.4V and 1V of voltage channel,
the others are less than 2.5, and current channel error is less than 0.02In for 0.08In
and 0.2In, the others are less than 2.5%.
Short b1~b4 of AC module X1, IA, IB, IC and IN outputs of testing instrument are
connected to terminals X1-a1, X1-a2, X1-a3 and X1-a4 of the IED, input rated current
and three-phase symmetry voltage 50 via a11, a10, b10 and b11 of X1 respectively,
each phase voltage leads each phase current phase angle 60°respectively, check
LCD loop display or enter into Main Menu—Status—measure to view, phase
difference of A-, B-, and C-phase voltage must be 120°, and phase difference of A-,
B-, and C-phase current must be 120°. One phase current must lag the
corresponding phase voltage 60°(angle error ≤ 3°). Otherwise, check the IED of AC
module connection.
Input three-phase symmetry voltage 50V, and rated current only to phase A which
lags phase A voltage 60°, observe the display of amplitude and angle of 3I0 which
must be the same as IA, otherwise, check the IED of AC module connection.
-98-
CSC-326 Transformer Protection IED Technical Manual
9.10.3 After setting the date and time of IED, turn on and off the DC power supply of five
times in short time, and then check the tolerance of the date and time is limited in
permissive scope.
9.10.5 Check, record and print (if a printer is connected) the protection settings item by item
of each group which are possibly employed in the actual operating modes.
9.10.6 Check and record the state of all binary inputs. Particularly ensure that the IED is not
in test mode, meaning there is not a hand type icon displayed at the upright corner of
the LCD, and the binary input, relay test, is not present.
9.10.7 Inject system currents (load current must be larger than 0.08In) and voltages into the
IED, and then check whether the magnitude, phase angle, polarity and phase
sequence of each measuring analog value are correct or not.
9.10.8 Print information and operating condition with the ‖version‖ shortcut key if the IED
have been connected with a printer.
-99-
CSC-326 Transformer Protection IED Technical Manual
10 Maintenance
WARNING
Never disconnect the secondary connection of a current
transformer circuit without short-circuiting the transformer’s
secondary winding. Operating a current transformer with the
secondary winding open will cause a massive potential build up
that may damage the transformer and may cause injuries to
humans.
CAUTION
Never connect or disconnect a wire and/or a connector to or from
a IED during normal service. Hazardous voltages and currents are
present that may be lethal. Operation may be disrupted and IED
and measuring circuitry may be damaged.
NOTE
Instructions from the power network company and other
maintenance directives valid for maintenance of the power
system must be followed. The following items are only for
reference.
NOTE
a) During operation, these manual operations listed below are
forbidden:
-100-
CSC-326 Transformer Protection IED Technical Manual
-101-
CSC-326 Transformer Protection IED Technical Manual
messenger.
When a module is in fault, It should be replaced with the backup module. And send
the faulty module to Sifang for repair.
The user can purchase separate replacement modules.
10.5.1.1 Firstly, confirm the address jumper to be right on CPU module, input and write setting.
10.5.1.2 Check the version and CRC code of CPU module software;
10.5.1.3 After updating or replacing, if alarm ―setting zone error― or ―setting error― is present,
the setting should be written again and the active setting group should be set again.
10.5.1.4 After updating or replacing, if alarm ―logical Linker error― or ―linker error― is present,
the setting should be written again and the active setting group should be set again.
10.5.2.2 Configure again according to the former configuration, or write the former
configuration of MASTER again.
10.5.2.5 Print and check any reports and disturbance record reports
10.5.2.6 Test some binary inputs or outputs to confirm the menu operation can be done well.
-102-
CSC-326 Transformer Protection IED Technical Manual
Test all inputs or outputs on the module and relative external secondary
circuits before IED in service.
The back-up battery should be replaced after ten years of operation or after
alarm signal was sent out.
10.7 Others
There are one test male connector at the up left corner of rear plate, The
connector can be used to test 24V(output), ±12V 、 5V and perform
auto-testing by connection with the internal CAN net.
There are three ways to input settings:(1) Keypad on front panel, (2) employ
CSPC software tool (3) Substation automation system.
Method to select active setting group:Use the functional keys, ―+‖, ―-‖, to
select and switch active setting group.
Use LON net to connect printer via the CSN 010 interface case(the terminal
wiring of printer and cable must be changed).
Connect printer directly with the print series ports of the IED through special
printer cable. If several equipments (the maximum is 4) need use one printer in
common, a CSN-4 interface case is needed.
Except AC terminals, all the other rear plate terminals are located on the female
-103-
CSC-326 Transformer Protection IED Technical Manual
-104-
CSC-326 Transformer Protection IED Technical Manual
Table 36-1
Terminal mark object remark
a1-b1 Current of phase IHV1A,IHV1A polar terminal, Analog
IHV1A‘ not quantities input,
a2-b2 Current of phase IHV1B,IHV1B polar terminal, practical wiring
IHV1B‘ not diagram is
a3-b3 Current of phase IHV1C,IHV1C polar terminal, shown in Fig. 26
IHV1C‘ not and Fig. 27
a4-b4 Current of phase IHV2A,IHV2A polar terminal,
IHV2A‘ not
a5-b5 Current of phase IHV2B,IHV2B polar terminal,
IHV2B‘ not
a6-b6 Current of phase IHV2C,IHV2C polar terminal,
IHV2C‘ not
a7-b7 Neutral current in high voltage side or common
winding, IREFHV polar terminal,IREFHV‘ not
a10 Voltage of phase UHVB, UHVB input
b10 Voltage of phase UHVC, UHVC input
a11 Voltage of phase UHVA, UHVA input
ba12 Shielded grounding, connected to X10-ca32 inside
equipment, need not to be wired again.
Table 36-2
Terminal mark Object Remark
a1-b1 Current of phase IMV1A,IMV1A polar terminal, Analog
IMV1A‘ not quantities input,
-105-
CSC-326 Transformer Protection IED Technical Manual
Table 36-3
Terminal mark Object Remark
a1-b1 Current of phase ILVA,ILVA polar terminal, ILVA‘ Analog
not quantities
a2-b2 Current of phase ILVB,ILVB polar terminal, input, practical
ILVB‘ not wiring diagram
a3-b3 Current of phase ILVC,ILVC polar terminal, is shown in
ILVC‘ not Fig. 26 and
a10 Voltage of phase ULVB, ULVB input Fig. 27
b10 Voltage of phase ULVC, ULVC input
a11 Voltage of phase ULVA, ULVA input
ba12 Shielded grounding, connected to X10-ca32
inside equipment, need not to be wired again.
Table 36-4
-106-
CSC-326 Transformer Protection IED Technical Manual
Ethernet
485-1B 7
485-1A 8
GPS 9
GPSGND 10
LON-2A 11
LON-2B 12
LONGND 13
LON-1A 14
LON-1B 15
Not Used 16
Table 36-5
Terminal mark Object
a2、a28 The a2 has been already installed an input of 24V at the interior of the
IED, and a28 has been already installed an input of 24V earthing. So the
connection exterior is not allowed.
a4 Remote access block-on:When the input is 24V, the controls must be on
site. That means only the local commands can be executed. All the
non-local commands will not be executed, such as the remote switching
connector, setting group, and writing the settings.
a6 Relay test:The relays will be test, when signal DI is given into this
terminal. When test the protections, the IED won‘t send the report, and
won‘t execute the remote commands. While the IED operating, the input
of this terminal must be cancel.
a8 Signal reset:used to reset the signal of flash on the front panel
a12 ―DIFF PROT EN‖. The differential protection is enabled or disabled, it is
125V input.
a14 ―REF PROT EN‖. The REF protection is enabled or disabled, it is 125V
input.
c2、c28 Wirings of these terminals are not allowed for equipment with supply
125V.
c14,c16, c18 Connect separately with DI1~3 trip DO.
Table 36-6
Terminal mark Object Remark
c2-a2 3-Phase Trip 1-1 Fast output
c4-a4 3-Phase Trip 1-2
c6-a6 3-Phase Trip 1-3
c8-a8 3-Phase Trip 1-4
-107-
CSC-326 Transformer Protection IED Technical Manual
Table 36-7
Terminal mark Object Remark
c2-a2 3-Phase Trip 2-1 Fast output
c4-a4 3-Phase Trip 2-2
c6-a6 3-Phase Trip 2-3
c8-a8 3-Phase Trip 2-4
c10-a10 3-Phase Trip 2-5
c12-a12 3-Phase Trip 2-6
c14-a14 3-Phase Trip 2-7
c16-a16 3-Phase Trip 2-8
c18-a18 HV BU OPTD-1
c20-a20 HV BU OPTD-2
c22-a22 MV BU OPTD-1
c24-a24 MV BU OPTD-2
c26-a26 LV BU OPTD-1
c28-a28 LV BU OPTD-2
c30-a30 THERMAL O/L OPTD-1
c32-a32 THERMAL O/L OPTD-2
11.2.1.8 Terminal groups of X10 – output terminals are shown in Table 36-7.
Table 36-8
Terminal mark Object Remark
a2 Signal common terminal 1(+)
c2 Signal common terminal 2(+) Positive supply
a10 Signal common terminal 3(+) output
c10 Signal common terminal 4(+)
a4, a12 DIFF OPTD Signal
a6, a14 REF OPTD
c4, c12 OV/FLUX OPTD
c6, c8 NEU DISP ALM
c8, c16 THERM OC ALM
c18-a18, DO CONFIG DI1 Fast output
c20-a20
c22-a22, DO CONFIG DI2
-108-
CSC-326 Transformer Protection IED Technical Manual
c24-a24
c26-a26, DO CONFIG DI3
c28-a28
11.2.1.9 Terminal groups of X11 – output Terminals are shown in Table 36-9.
Table 36-9
Terminal mark Object Remark
a2, c2 Center signal common terminal (+)
Positive supply
a12, c12 Remote signal common terminal (+)
output
a22, c22 Record signal common terminal (+)
a4, a14, a24 CT FAIL Signal
a6, a16, a26 VT FAIL
c6, c16, c26 OVER LOAD
c8, c18, c28 RUN ALARM
c10, c20, c30 RELAY ALARM
11.2.1.10 Terminal groups of X12 – terminals of power supply are shown in Table
36-10.
Table 36-10
Terminal mark Object Remark
ca2, ca4 24V+ output terminal
ca8, ca10, ca12 24V- output terminal
c14-a14 Contact of DC input Signal of DC input
c16-a16 Contact of loss of DC power supply Signal of loss power
c18-a18
ca20,ca22 1:input terminal of positive power Input for external
ca26,ca28 2:input terminal of negative power power supply
ca32 Shielded ground of equipment:Connected reliably
to the grounding of substation
-109-
CSC-326 Transformer Protection IED Technical Manual
If the IED is to be stored before installation, this must be done in the original transport
casing in a dry and dust free place. The packed IED should be stored in a waterproof
and snow proof place without acid or alkaline or other corrosive gas and explosive
gas. The storage temperature is from -25℃ to +40℃, and the relative humidity does
not exceed 80%. Observe the environmental requirements stated in the technical
data.
12.2 Transportation
The IED can be transported by all means of conveyance such as car, train and ship
etc, but ought to prevent it from rain, snow, vibration, Shock and bump, in order to
ensure perfect performance of the IED.
-110-
CSC-326 Transformer Protection IED Technical Manual
13 Ordering
Manufactured type, name, and quantities
-111-
X6(DI MODULE) X4(MASTER MODULE)
X3(AI MODULE) X2(AI MODULE) X1(AI MODULE)
c a NOT USED 1
14
2 DC+ INPUT R24V+ INPUT
14.1
232-TRAN 2 b a b a b a
4 NOT USED REM ACCESS BLK
232-RECV 3 1 ILVA' ILVA 1 IMV1A' IMV1A 1 IHV1A' IHV1A
6 NOT USED RELAY TEST
232-GND 4 2 ILVB' IMV1B' IMV1B IHV1B'
8 NOT USED RESET ILVB 2 2 IHV1B
485-2B 5
10 NOT USED 3 ILVC' ILVC 3 IMV1C' IMV1C 3 IHV1C' IHV1C
485-2A 6
12 NOT USED DIFF PROT EN 4 4 IMV2A' IMV2A 4 IHV2A' IHV2A
485-1B 7
14 DI1 REF PROT EN IMV2B'
485-1A 8 5 5 IMV2B 5 IHV2B' IHV2B
16 DI2 NOT USED
GPS 9 6 6 IMV2C' IMV2C 6 IHV2C' IHV2C
18 DI3 NOT USED
112
X12(POWER) X11(DO MODULE) X10(DO MODULE) X9(DO MODULE) X8(DO MODULE)
c a c a c a c a c a
2 2 CENTER(COM+) CENTER(COM+) 2 SIG-2(COM+) SIG-1(COM+) 2 3-PHASE TRIP 2-1 2 3-PHASE TRIP 1-1
R24V+ OUT
4 4 PROT ACT CT FAIL 4 OV/FLUX OPTD DIFF OPTD 4 3-PHASE TRIP 2-2 4 3-PHASE TRIP 1-2
6 6 OVER LOAD VT FAIL 6 NEU DISP ALM REF OPTD 6 3-PHASE TRIP 2-3 6 3-PHASE TRIP 1-3
8 8 RUN ALARM NOT USED 8 THERM OC ALM NOT USED 8 3-PHASE TRIP 2-4 8 3-PHASE TRIP 1-4
10 R24V- OUT 10 RELAY ALARM NOT USED 10 SIG-4(COM+) SIG-3(COM+) 10 3-PHASE TRIP 2-5 10 3-PHASE TRIP 1-5
12 12 REMOTE(COM+) REMOTE(COM+) 12 OV/FLUX OPTD DIFF OPTD 12 3-PHASE TRIP 2-6 12 3-PHASE TRIP 1-6
14 DC FAILURE 14 PROT ACT CT FAIL 14 NEU DISP ALM REF OPTD 14 3-PHASE TRIP 2-7 14 3-PHASE TRIP 1-7
16 DC FAILURE 16 OVER LOAD VT FAIL 16 THERM OC ALM NOT USED 16 3-PHASE TRIP 2-8 16 3-PHASE TRIP 1-8
30 30 RELAY ALARM NOT USED 30 NOT USED 30 THERMAL O/L OPTD-1 30 OVFLX MV OPTD-1
Typical connection 1
A
B Transformer
C module AI1
UHVA 11a
UHVB 10a
UHVC 10b
UHVN 11b
UHV0 9a
9b
UHV0N
1a 1b
IHVA
IHVB 2a 2b
IHVC 3a 3b
IREFHV 7a 7b
8a 8b
INBKHV
Transformer
module AI3
1a 1b
ILVA
2a 2b
ILVB
3a 3b
ILVC
ULVA 11a
ULVB 10a
ULVC 10b
A ULVN 11b
B
C
113
Typical connection 2
A
B Transformer
C module AI1
UHA 11a
UHB 10a
UHC 10b
UHN 11b
UH0 9a
UH0N 9b
IHA 1a 1b
IHB 2a 2b
IHC 3a 3b
A
B
Transformer C
module AI2
IH0
4a 4b
IHJX
5a 5b
Transformer
module AI2
IMA 1a 1b
IMB 2a 2b
IMC 3a 3b
IM0 6a 6b
IMJ 7a 7b
11a
UMA
10a
UMB
10b
UMC
11b
UMN
9a
UM0
9b
UM0N
Transformer
module AI3
1a 1b
IL1A
2a 2b
IL1B
3a 3b
IL1C
UL1A 11a
UL1B 10a
UL1C 10b
A UL1N 11b
B
C
114
14.3 Communication protocol
Table 37 Communication protocol
115
14.4 CSC-326 IEC 61850 communication
14.4.1 Overview
This port introduces the data modeling, communication principles that are used
in the IEDs. The purpose of supporting IEC61850 series is to provide
interoperability between devices from different venders.
For some advanced applications, the reader should have intensive knowledge
about IEC61850.
The communication between substation level and bay level uses mainstream
technology, which is an ISO/OSI stack consisting of Ethernet (layers 1 and 2),
TCP/IP (layers 3 and 4) and MMS (layers 5-7). The object models and their
communication services are mapped to the application layer of MMS (layer 7).
The communication between substation level and bay level is of
connection-oriented type. The communication services to access and retrieve
the data are mostly of client/server type.
Note:
MMS: Manufacturing Message Specification.
116
data-reference
buffer-overflow only for BRCB
entryID only for BRCB
conf-rev
segmentation
Can the server send segmented reports Y
Pre-configured RCB attributes that cannot be N
changed online when RptEna = FALSE
(see also the ICD report settings)
Table 38-3 Control specification
Description Value / Clarification
What control modes status-only
are supported SBO-with-enhanced-security
What service error ACCESS-NOT-ALLOWED-IN-CURRENT-STATE
types are supported PARAMETER-VALUE-INAPPROPRIATE
CONTROL-MUST-BE-SELECTED
FAILED-DUE-TO-SERVER-CONSTRAINT
What additional cause BLOCKED-BY-SWITCHING-HIERARCHY
diagnosis are SELECT-FAILED
supported POSITION-REACHED
PARAMETER-CHANGE-IN-EXECUTION
ABORTION-BY-CANCEL
TIME-LIMIT-OVER
Which origin categories Bay-control, station-control, remote-control, automatic-bay,
are supported? What automatic-station, automatic-remote, maintenance, process.
happens if the orCat is When orCat is not supported response failure.
not supported?
Select timeout 60 SECONDS
Operate timeout 30 SECONDS
Table 38-4 Setting group control specification
Description Value / Clarification
What is the number of supported setting As configured in ICD file.
groups for each logical device
What is the effect of when and how the Display setting data and saved information on
non-volatile storage is updated the LCD of IED.
(compare IEC 61850-8-1 $16.2.4)
Table 38-5 File transfer specification
Description Value / Clarification
What is structure of files and directories? Directory name is COMTRADE.
Directory names are separated from the file ―/‖
name by
The maximum file name size including path 255
(recommended 64 chars)
Are directory/file name case sensitive Case sensitive
It is introduced in this part, the layout of the Logical Device, Logical Nodes and
Data Objects. The IEC61850 device model begins with a physical device. There
are several logical devices within each physical device. And there are at least 3
logical nodes within each logical device.
Note:
There are No vender specific Logical Node Class and Common Data Class in
CSC series devices.
117
Table 38-6 Logical Devices Model
LD Name Description Function
LD0 Device related LD Data about device: Self-checking, Alarm etc
PROT Protection LD Data about Protection: Protection Event, Setting
Group. etc
MEAS Measurement LD Data about Measurement
DREC Disturbance Record LD Data about Disturbance Record
Table 38-7 Data set model
Description Value / Clarification
What is the maximum number of data 800
elements in one data set
How many persistent data sets can be FOR ONE LD, THE SUM
created by one or more clients OF CONFIGURED DATE
SETS AND PERSISTENT
DATA SETS IS NO MORE
THAN 20.
M4 Data set C5 C5 Y
M5 Substitution O O N
118
M6 Setting group control O O Y
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm Y Y Y
M7-9 IntgPd N Y Y
M7-10 GI Y Y Y
M8 Unbuffered report M M Y
control
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm Y Y Y
M8-7 IntgPd N Y Y
M8-8 GI N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O N
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File Transfer O O Y
Table 38-10 ACSI service conformance
Client/ Server/ CSC Explanation
subscriber publisher Series
IED
Server
S1 ServerDirectory - M Y
Application association
S2 Associate M M Y
S3 Abort M M Y
S4 Release M M Y
Logical device
S5 LogicalDeviceDirectory M M Y
Logical node
S6 LogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O Y
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
119
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O Y
S14 CreateDataSet O O Y
S15 DeleteDataSet O O Y
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O Y
S20 SetSGValues O O Y
S21 ConfirmEditSGValues O O Y
S22 GetSGValues O O Y
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report C6 C6 Y
S24-1 data-change (dchg) C6 C6 Y
S24-2 qchg-change (qchg) C6 C6 Y
S24-3 data-update (dupd) C6 C6 Y
S25 GetBRCBValues C6 C6 Y
S26 SetBRCBValues C6 C6 Y
Unbuffered report control block (URCB)
S27 Report C6 C6 Y
S27-1 data-change (dchg) C6 C6 Y
S27-2 qchg-change (qchg) C6 C6 Y
S27-3 data-update (dupd) C6 C6 Y
S28 GetURCBValues C6 C6 Y
S29 SetURCBValues C6 C6 Y
c6 – shall declare support for at least one (BRCB or URCB)
Logging
Log control block
S30 GetLCBValues M M N
S31 SetLCBValues O M N
Log
S32 QueryLogByTime C7 M N
S33 QueryLogAfter C7 M N
S34 GetLogStatusValues M M N
c7 – shall declare support for at least one (QueryLogByTime or QueryLogAfter).
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage C8 C8 N
S36 GetGoReference O C9 N
S37 GetGOOSEElementNumber O C9 N
S38 GetGoCBValues O O N
S39 SetGoCBValues O O N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage C8 C8 N
S41 GetGsReference O C9 N
S42 GetGSSEElementNumber O C9 N
S43 GetGsCBValues O O N
S44 SetGsCBValues O O N
c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage).
c9 – shall declare support if TP association is available.
120
S46 GetMSVCBValues O O N
S47 SetMSVCBValues O O N
Unicast SVC
S48 SendUSVMessage C10 C10 N
S49 GetUSVCBValues O O N
S50 SetUSVCBValues O O N
c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage).
Control
S51 Select M M N
S52 SelectWithValue M M N
S53 Cancel O M N
S54 Operate M M Y
S55 Command-Termination M M N
S56 TimeActivated-Operate O O N
File transfer
S57 GetFile O M Y
S58 SetFile O O Y
S59 DeleteFile O O Y
S60 GetFileAttributeValues O M Y
Time
SNTP O
server
SNTP Y
client
T1 Time resolution of internal T1
clock
T2 Time accuracy of internal T0
clock
T3 Supported Timestamp 10
resolution
121
Address:
Building 9, Fourth Avenue, Shangdi Information Industry Base,
Haidian District, Beijing, P.R.China
Zip: 100085
Tel: +8610-62961515,
+8610-62985012 (Marketing Department)
+8610-62986668(Technical Support)
Fax: +8610-62981004
+8610-62978952 (Marketing Department)
E-mail: webinfo@sf-auto.com
Web Site: http://www.sf-auto.com
122