The work includes design, supply, erection, testing & commissioning of the complete Air-conditioning system. The tenderer shall fill in the
columns of Rate, amount and submit the same along with the TECHNICAL details as mentioned in tender document.
All refrigerant piping along with insulation and supports, between indoor &
outdoor units duly insulated with Closed Cell EPE 19mm O Class Nirtile rubber
insulation. All piping inside the room shall be properly supported on hot dip
galvanised perforated trays with hanger and exposed piping shall be properly
1.2 supported. All pipes exposed to atmosphere shall be coated with Anti- Rmt
corrosive Aluminium cladding 24 SWG and laid in closed cable tray duly
powder coated in 22 Micron. Insulation joining shall be made with Nitrile
rubber adhesive.
Note- Total Pipe length Estimated (in pair) However exact pipe sizes , length
to be specified by contractor during the quote. Pipe Sizes As Per
Manufactures specification
1.2.1 1.0 TR
a (3/8") 9.50 mm 450 Rmt 490 220,500 150 67,500
b (1/4 " ) 6.40 mm 450 Rmt 360 162,000 125 56,250
1.2.2 1.30 TR
a (3/8") 9.50 mm 40 Rmt 490 19,600 150 6,000
b (1/4 " ) 6.40 mm 40 Rmt 360 14,400 125 5,000
1.2.3 1.50 TR
a (3/8") 12.70 mm 340 Rmt 490 166,600 150 51,000
b (1/4 " ) 6.40 mm 340 Rmt 360 122,400 125 42,500
1.2.4 2.0 TR
a (3/8") 12.70 mm 200 Rmt 490 98,000 150 30,000
b (1/4 " ) 6.40 mm 200 Rmt 360 72,000 125 25,000
a diffuser size 360x360 ,damper size 225 x225 RO MT2 7,000 1,800
- -
2.8 Supply, receiving, storing, installation, testing & commissioning o RO MT2
Heavy duct flexible double layer Leather canvas connection shall be provided
2.9.1 at the outlet of FCU / CSU units. Size as per indoor unit mouth connection. 7 Nos. 2,000 14,000 1,000 7,000
(Rexins not acceptable).
a 300mm dia 1400 RPM FOR TOILET VENTILATION 6 No 3,200 19,200 500 3,000
3.4 Any other item not specified above but which are necessary for the RO
Job
satisfactory completion of works.
Drain pump for spli ac where there is no slope for AC RO NO 4,000 500
3.4.1 Galvanised cable tray
100 MM RO RMT
150 MM RO RMT
300 MM RO RMT
3.4.2 powder coated cable tray
100 MM RO RMT
150 MM RO RMT
300 MM RO RMT
3 SUB-TOTAL "3.0" VENTILATION WORK 425,050 54,250
2,231,450 234,350