You are on page 1of 1

20-20 INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION

N 4.16.5.3 Automated Valves. 4.16.8.3 Screens shall be removable, or an in situ cleaning


shall be provided.
N 4.16.5.3.1 A listed indicating valve with automated controls
shall be permitted. 4.16.8.4 Below minimum water level, these screens shall have
an effective net area of opening of 1 in.2 for each 1 gpm
N 4.16.5.3.2 The automated water control valve assembly shall
meet the following criteria: (170 mm2 for each 1 L/min) at 150 percent of rated pump
capacity.
(1) Include a reliable position indication
(2) Include a valve supervisory switch and be connected to a 4.16.8.5 Screens shall be so arranged that they can be cleaned
remote supervisory station or repaired without disturbing the suction pipe.
(3) Operate manually as well as automatically 4.16.8.6 Mesh screens shall be brass, copper, Monel, stainless
4.16.5.4 No control valve other than a listed OS&Y valve and steel, or other equivalent corrosion-resistant metallic material
the devices as permitted in 4.29.3 shall be installed in the wire screen of 0.50 in. (12.7 mm) maximum mesh and No. 10
suction pipe within 50 ft (15.3 m) of the pump suction flange. B&S gauge.

4.16.6* Installation. 4.16.8.7 Where flat panel mesh screens are used, the wire
shall be secured to a metal frame sliding vertically at the
4.16.6.1 General. Suction pipe shall be laid carefully to avoid entrance to the intake.
air leaks and air pockets, either of which can seriously affect
the operation of the pump. 4.16.8.8 Where the screens are located in a sump or depres‐
sion, they shall be equipped with a debris-lifting rake.
4.16.6.2 Freeze Protection.
4.16.8.9 Periodically, the system shall be test pumped, the
4.16.6.2.1 Suction pipe shall be installed below the frost line screens shall be removed for inspection, and accumulated
or in frostproof casings. debris shall be removed.
4.16.6.2.2 Where pipe enters streams, ponds, or reservoirs, 4.16.8.10 Continuous slot screens shall be brass, copper,
special attention shall be given to prevent freezing either Monel, stainless steel, or other equivalent corrosion-resistant
underground or underwater. metallic material of 0.125 in. (3.2 mm) maximum slot and
4.16.6.3 Elbows and Tees. profile wire construction.

4.16.6.3.1 Unless the requirements of 4.16.6.3.2 are met, 4.16.8.11 Screens shall have at least 62.5 percent open area.
elbows and tees with a centerline plane parallel to a horizontal 4.16.8.12 Where zebra mussel infestation is present or reason‐
split-case pump shaft shall not be permitted. (See Figure ably anticipated at the site, the screens shall be constructed of a
A.4.16.6.) material with demonstrated resistance to zebra mussel attach‐
4.16.6.3.2 The requirements of 4.16.6.3.1 shall not apply to ment or coated with a material with demonstrated resistance to
elbows and tees with a centerline plane parallel to a horizontal zebra mussel attachment at low velocities.
split-case pump shaft where the distance between the flanges of 4.16.8.13 The overall area of the screen shall be 1.6 times the
the pump suction intake and the elbow and tee is greater than net screen opening area. (See screen details in Figure A.7.2.2.2.)
10 times the suction pipe diameter.
4.16.9* Devices in Suction Piping.
4.16.6.3.3 Elbows and tees with a centerline plane perpendic‐
ular to the horizontal split-case pump shaft shall be permitted 4.16.9.1 No device or assembly, unless identified in 4.16.9.2,
at any location in the pump suction intake. that will stop, restrict the starting of, or restrict the discharge of
a fire pump or pump driver shall be installed in the suction
4.16.6.4 Eccentric Tapered Reducer or Increaser. Where the piping.
suction pipe and pump suction flange are not of the same size,
they shall be connected with an eccentric tapered reducer or 4.16.9.2 The following devices shall be permitted in the
increaser installed in such a way as to avoid air pockets. suction piping where the following requirements are met:

4.16.6.5 Strain Relief. Where the pump and its suction supply (1) Check valves and backflow prevention devices and assem‐
are on separate foundations with rigid interconnecting pipe, blies shall be permitted where required by other NFPA
the pipe shall be provided with strain relief. [See Figure standards or the authority having jurisdiction and in‐
A.6.3.1(a).] stalled in accordance with Section 4.29.
(2) Where the authority having jurisdiction requires positive
4.16.7 Multiple Pumps. Where a single suction pipe supplies pressure to be maintained on the suction piping, a pres‐
more than one pump, the suction pipe layout at the pumps sure sensing line for a low suction pressure control,
shall be arranged so that each pump will receive its propor‐ specifically listed for fire pump service, shall be permitted
tional supply. to be connected to the suction piping.
(3) Devices shall be permitted to be installed in the suction
4.16.8* Suction Screening. supply piping or stored water supply and arranged to acti‐
4.16.8.1 Where the water supply is obtained from an open vate a signal if the pump suction pressure or water level
source such as a pond or wet pit, the passage of materials that falls below a predetermined minimum.
might clog the pump shall be obstructed. (4) Suction strainers shall be permitted to be installed in the
suction piping where required by other sections of this
4.16.8.2 Double intake screens shall be provided at the standard.
suction intake.

2019 Edition Shaded text = Revisions. Δ = Text deletions and figure/table revisions. • = Section deletions. N = New material.

You might also like