Example Detemnie the Disruptive Critical Voltagethe Visual Corona inception voltage, and the power oss inthe line de to corom, bot under fir Weather conditions as wel as stoma weather conditions foe 2 100 km long 3 phase, 132 kV line consisting of conductors of diameter 1.04 cm, arranged in an equilateral triangle configuration with 3 m spacing, The temperature ofthe sumountngs is 40° Cand the prescure is 750 or. ‘The operating frequency is 50 Hz, [The imegularity factors may be taken as m, = 0.85, 72 “The Aic density coection factor is given by __p_ 273420 _0.386 p 760° 27341 27340 750 293 760° 313 !. Disruptive ertcal volage 21.28 mr log, (dt) KV to neutral 21.2.x0.925 x 0.85 x 0.52 x loge (30,0052) 5.1 kV Sinslay, ‘Visual corona voltage = 21.2% 0.925 x 0.72 x 0.52 x log. (310.0052) x_[ 1 + 0.3(0.895 x 0.52)"] = 672kV Power loss under fair weather condition is given by ss1) uo" Jn aig 365 kWiphase Similarly, power loss under stormy weather condition is given by 20. gp), (2 55.1* 0.8 *.100 kWiphase ons \ B J _ : =847 kWiphase