1.

Differential protection relay, tripping contact (O/P contact) to be wired to L2 panel Master
Relay circuit (86), TC1&TC2 Circuits (If Required).
2. L2 panel master relay tripping contact (O/P contact) to be wired to ACB tripping circuit.
3. In HT – 4 Board panels, Require TBs, TTBs for Differential CT connections (HV&LV), REF, SBEF,
PT connections and relay O/P tripping contact, annunciator circuit.
4. Selected Differential relay, Suitable for Differential, over flux, REF & SBEF protections
5. Master trip relay (86) require for L2 panel.
6. For REF protection, we required Resistor & Metrosil for High Impendence protection.
7. HV side of Master trip relay (86HV), o/p contact wiring to Tripping circuit of LV side of
Master trip relay (86LV)- Inter trip. (if Required).
8. 86HV & 86LV supervision circuit wiring to relay / annunciator (if Required)
9. 33kV & 800V side CT polarity need to correct as per M.P scheme.
10. In M.P site 6.3MVA IDT should have Bushing CT for experimental purpose.
11. How we will parallel 12 CTs of LV for differential protection.