I. INTRODUCTION
Fig.1. Vision of Smart Grid Distribution System
Some of the functional managements of smart grid track the voltage magnitude in real time applications. The dq0
distribution system are given below: amplitude is used to initiate the circuit reconfiguration.
1. Distribution Automation: Remotely monitor and control Whenever dq0 amplitude is more than a specified value, the
operations control center detects the fault location and turn-off the
2. Energy Management Systems: Takes the data needs. End electronic switch placed on the feeder section to isolate the
users versions analyze the from various parts of the faulty section and restore the un-faulted section of the feeder
distribution network to create a single picture for [3].
analyzing the loads and forecasting load and energy From
patterns of the industries, offices, commercial and other Upstream
types of loads.
3. Geographical Information Systems: Displays the status of
equipments, position of crews and status of the
functioning of customer’s appliances on maps.
4. Outage Distribution Automation: Remotely monitor and
control operations.
II. POWER ELECTRONIC SWITCHING USED IN SMART III. RESTORATION PROCESS AFTER OCCURANCE OF
DISTRIBUTION SYSTEMS A SUSTAINED FAULT
The sensitive loads of distribution system require a This section describes the process of restoration after
continuous power supply and they must be restored very occurrence of the fault on anon-automated, full automated and
quickly, if at all any interruption takes place. In smart gird smart grid radial feeder.
distribution system, remotely operated high rated power A. Non Automated Feeders
electronic converter switches shown in Fig. 2 are used in the In non-automated feeders all the disconnecting switches are
place of manual operated disconnecting switches [3][4]. manually operated switches.
Under normal operating conditions of the distribution i). The CB will trip if fault occurs on any line segment or
system, the electronic switch is continuously turned on to section. When this happens, a crew travels forward along
work as a normally closed switch to supply the power to the the route of the circuit to find the location of fault.
customers. When a permanent active fault occurs, the voltage ii). After finding the location of fault, they open immediate
magnitude becomes zero, this will be detected in a very short upstream and downstream disconnecting switches to
time and the electronic switches are automatically turned off isolate the faulty section.
by remote operation, to isolate the faulty section and restore iii). They reclose circuit breaker at substation to restore the
the load points under the un-faulted portion of the feeder upstream load points.
iv). They close normally open tie line switch to restore
[5][6].
downstream load points from alternative supply.
The advanced sensors, communication technology and v). The loads under the fault condition are restored after the
information technology used in the smart grid can detect the repair/replacement of fault section.
low voltage amplitudes in a very short time period of one
quarter cycle. Since, the fault detection, isolation and The effect of manual operations is simulated by assuming
restoration takes place in very short period of time of 16.7 ms that the load points in upstream and downstream restored in
for 60 Hz power supply, the reliability of distribution system one hour and load points under the faulted section are restored
increases very rapidly [5]. The dq0 transformation is used to in five hours [7].
ii). The computer system in control center detects fault g) The feeders consist of disconnecting switches on each
location by checking each RTU. feeder section, fuses at the starting point of laterals,
alternate supply and the distribution transformer is restored
iii). When the fault section has been identified, the computer by the repair process.
transmits a control signal to corresponding RTUs to
operate disconnecting switches. h) All the disconnecting switches are 100% reliable.
iv). When the faulted section has been isolated, the computer The reliability indices such as load point indices (average
transmits the control signal to RTUs to close the normally failure rate, average repair time and average outage time) and
open tie-switch (TS) and reclose the circuit breaker, the system performance indices (SAIFI, SAIDI, ENS and ASAI)
load disconnected can be restored. of an RBTS Bus2 distribution system for Non-automated,
Automated and Smart grid distribution system are calculated
v). The loads which are under the fault condition are restored
after the repair/replacement of fault section [8] [7]. The reduction in SAIDI indicates the improvement in
reliability of the distribution system [8][9].
LP4
F LP7
DTr4 Tie- Line Switch 15
11
DTr7
6 LP9
10
5 F
S3 F DTr6 LP6 14
S2 7
LP3
DTr3 F F 9
8
Feeder-1 4 33 kV Feeder-2
DTr5
S413 LP8
12
3 S1 LP5
1
LP2 CB1 11 kV CB2
DTr2 F F
2 CB3
CB4 LP11
DTr1
LP18
16 DTr11
LP1 26
DTr18 19
DTr12
F F
30 18
DTr16
31 F F LP16 S5 20
29 LP12
LP19 F
DTr19 F S8 F 27 17 S6
S9 28 DTr10
DTr17 Feeder-3
Feeder-4 21
32
LP10
F DTr13
33 LP17 DTr21 24
LP20 34 F
F S10 35 F S7 22 LP13
DTr20 F LP21
F
36 25 23
DTr22 DTr15 DTr14
REFERENCES NOMENCLATURE
F: Feeder
[1] James Northcote-Green, Robert Wilson, “Control and Automation of S: Switch
Electric Power Distribution Systems” Second Edition, CRC
Publications, 2006. U: Average Annual Outage (hr/yr)
[2] Brown R.E., “Impact of Smart Grid on Distribution System Design”, λ: Average failure rate (f/yr)
Proceedings of Power and Energy Conference, 20-24 July, 2008. Dtr: Distribution Transformer
[3] Haughton, G.T.Heydt, “Smart Distribution System Design: Automatic SAIFI: System Avg. Interruption Frequency Index (f/yr/cust.)
Reconfiguration For Improved Reliability”, Power and Energy SAIDI: System Avg. Interruption Duration Index (hr/yr/cust.)
conference, 25th -29th, July 2010, pp.1-81-4.
CAIDI: Customer Average Interruption Duration Index (hr/f)