S.No Description Qty Rate Unit Amount
1 SITC of outdoor, all-weather proof, Non-Walk-in type Compact
Secondary Substation of robust construction, vermin & dust proof,
capable of withstanding thermal & mechanical stresses as per the
max Short Circuit rating at 11KV, 50 HZ. The prefabricated
enclosure is to be fabricated out of suitable GI sheet steel &
complying to protection degree of IP54 (LT & HT switchgear
compartment) & IP23 ( for transformer), with suitable MS base
Channel framework for rigidity, necesary covers & doors with
safety interlocking, Earthing arrangement, ventillation
arrangement, Internal light points & fittings, polyurethane painting
and foundation (as per OEM recommendation) etc. complete as per
CPWD specifications whereever applicable, including supplying
& Installation of the following in seperate compartments in the
above CSS.
A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.
B)Transformer:
1000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta-star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.
C) L.T.Compartment:
Incomer: 1600 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1000 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side, with adjustable O/C and E/F setting
, suitable Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and
all required accessories etc. complete as required. - 2 Set
ii) 630 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and with Microprocessor release, for
Protection & isolation of LT side, with suitable Alluminium Bus Bar/
Spreaders, and all required accessories etc. complete as required. - 1
Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
3 Nos..
iv) LED phase indication lamps with fuses - 3 Set
Page 70
S.No Description Qty Rate Unit Amount
D) Outdoor type enclosure having construction of Galvanised Sheet
Steel of thickness 2 mm for Load bearing member and minimum 1.6
mm for Non Load bearing member. The Enclosure shall have IP54
degree of protection for HT & LT switchgear compartment &
IP23 degree of protection for Transformer compartment. The
enclosure exterior shall be Polyuratne painted (Colour Light Gray &
D.A.Gray ). Each compartment will be provided with the door and
pad locking arrangement. The Compartment illumination lamp with
door operated switch shall be provided for MV and LV compartment.
A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.
B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta- star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.
Page 71
S.No Description Qty Rate Unit Amount
C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1600 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side,with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 2 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and with Microprocessor release, for
Protection & isolation of LT side, with suitable Alluminium Bus Bar/
Spreaders, and all required accessories etc. complete as required. - 2
Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
4 Nos..
iv) LED phase indication lamps with fuses - 4 Set
Page 72
S.No Description Qty Rate Unit Amount
(Make: ABB/Schneider Electric/ Siemens) 1 6238601.00 Job 6238601.00
( Near New EMI-EMC Building)
A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of 2 (two) number load
break switches and 1 (one) No. Fixed Manual Vacuum Circuit
Breaker with Microprocessor based self Powered Relay in SF6
insulated stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.
B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta - star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.
C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1600 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side ,with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 1 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side, with adjustable O/C and E/F setting
,with suitable Alluminium Bus Bar/ Spreaders, and all required
accessories etc. complete as required. - 2 Set.
iii) 400 Amp, 415 V, 4 Pole, 50KA, MCCB with Microprocessor
release, for Protection & isolation of LT side,with adjustable O/C and
E/F setting , with suitable Alluminium Bus Bar/ Spreaders, and all
required accessories etc. complete as required. - 1Set.
iV) LED Multifunction meter with Class 1 accuracy with RS485 port -
4 Nos..
v) LED phase indication lamps with fuses - 4 Set
Page 73
S.No Description Qty Rate Unit Amount
D) Outdoor type enclosure having construction of Galvanised Sheet
Steel of thickness 2 mm for Load bearing member and 1.5 m for Non
Load bearing member. The Enclosure shall have IP54 degree of
protection for HT & LT switchgear compartment & IP23 degree
of protection for Transformer compartment. The enclosure exterior
shall be Polyuratne painted (Colour Light Gray & D.A.Gray ). Each
compartment will be provided with the door and pad locking
arrangement. The Compartment illumination lamp with door operated
switch shall be provided for MV and LV compartment.
A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.
B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta-star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.
Page 74
S.No Description Qty Rate Unit Amount
C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1200 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side, with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 2 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side,with adjustable O/C and E/F setting
, with suitable Alluminium Bus Bar/ Spreaders, and all required
accessories etc. complete as required. - 1 Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
3 Nos..
iv) LED phase indication lamps with fuses - 3 Set
Page 75
S.No Description Qty Rate Unit Amount
HT Switchgear-2 in comming and 2 out going : 630 Amps 21kA
for 3 Sec, Outdoor type, VCB Compact Ring Main Unit, Consisting
of 2 Nos (Two) in comming and 2 Nos out going , 3 Pole VC'B's
totally enclosed & fully interlocked, horizontal draw out, horizontal /
Vertical isolation type breaker as per IS 13118, as amended up to date
and additional specifications,single break, trip free mechanism,
manually charged and manually closing breaker suitable for use on 11
KV, 3 phase, 50Hz AC supply with short circuit fault level of 350
MVA, complete with self contained, fully interlocked, rack in and
rack out mechanism, with microprocessor based self powered type
protection relay (3 O/C+1 E/F) with CT's mounted in cable box
etc.,complete as required.
a) 11 KV/ 110 Volts PT class 0.5 accuracy and not less than 100 VA
Burden with 1 no Voltmeter 15 KV Digital / analog type with
selector switch for voltmeter and protection fuses for metering upto
12 KV on Incomer- 1No.
e) Master trip relay and trip circuit healthy supervision relay and
power pack -1 Set
Page 76
S.No Description Qty Rate Unit Amount
h) Annunciator - 1 No.
i) Push buttons for close and trip- 1 Set
j) Space Heater- 1 Set
B) Outgoing -630 Amps VCB- 3 Nos. with the Following
a) 0-100 Amps Dual scale Ammeter ,analog type with Selector switch
-1 No.
d) Master trip relay and trip circuit healthy supervision relay and
power pack -1 Set
g) Annunciator - 1 No.
9 Supplying and laying of following size DWC HDPE pipe ISI marked
along with all accessories like socket, bend, couplers etc. conforming
to IS 14930, Part II complete with fitting and cutting, jointing
etc.direct in ground ( 1-meter below ground level) including
excavation and refilling the trench but excluding sand cushioning and
protective covering etc., complete as required.
Page 77
S.No Description Qty Rate Unit Amount
11.1 3 x 300 Sq. mm 16 11681.00 Each 186896.00
13 Supplying and making cable route marker with cement concrete 1:2:4
( 1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal
size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the
top with a thickness of 10 cm including inscription duly engraved as
required
14 Providing, laying and fixing following dia G.I. pipe (medium class) in
ground complete with G.I. fittings including trenching (75 cm
deep)and re-filling etc as required
Executive Engineer(E)