Name of Work: Providing of H.T network including Compact Sub Station for various labs at CPRI Campus, Bangalore.
S.No Description Qty Rate Unit Amount
1 SITC of outdoor, all-weather proof, Non-Walk-in type Compact
Secondary Substation of robust construction, vermin & dust proof,
capable of withstanding thermal & mechanical stresses as per the
max Short Circuit rating at 11KV, 50 HZ. The prefabricated
enclosure is to be fabricated out of suitable GI sheet steel &
complying to protection degree of IP54 (LT & HT switchgear
compartment) & IP23 ( for transformer), with suitable MS base
Channel framework for rigidity, necesary covers & doors with
safety interlocking, Earthing arrangement, ventillation
arrangement, Internal light points & fittings, polyurethane painting
and foundation (as per OEM recommendation) etc. complete as per
CPWD specifications whereever applicable, including supplying
& Installation of the following in seperate compartments in the
above CSS.

A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.

B)Transformer:
1000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta-star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.

C) L.T.Compartment:
Incomer: 1600 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1000 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side, with adjustable O/C and E/F setting
, suitable Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and
all required accessories etc. complete as required. - 2 Set
ii) 630 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and with Microprocessor release, for
Protection & isolation of LT side, with suitable Alluminium Bus Bar/
Spreaders, and all required accessories etc. complete as required. - 1
Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
3 Nos..
iv) LED phase indication lamps with fuses - 3 Set

Page 70
S.No Description Qty Rate Unit Amount
D) Outdoor type enclosure having construction of Galvanised Sheet
Steel of thickness 2 mm for Load bearing member and minimum 1.6
mm for Non Load bearing member. The Enclosure shall have IP54
degree of protection for HT & LT switchgear compartment &
IP23 degree of protection for Transformer compartment. The
enclosure exterior shall be Polyuratne painted (Colour Light Gray &
D.A.Gray ). Each compartment will be provided with the door and
pad locking arrangement. The Compartment illumination lamp with
door operated switch shall be provided for MV and LV compartment.

Internal Earthing connection with Minimum 50 x 6 mm Aluminium


strips.

E) Interconnection Between HT switchgear & Transformer using 1C


x 3R x 95 Sq.mm XLPE Single core cable & Interconnection
between Transformer & LT switchgear using Al. Busbars. Internal
earthing connections including Transformer neutral shall be using 50
x 6 mm GI strips. Required Bus connections, interlocking
arrangements within unit, Transportation & Crane hoisting etc.
as required- - 1 SET

(Make: ABB/Schneider Electric/ Siemens)


Compact Sub Station Complete as above ( Near Central Store)
1 3591289.00 Job 3591289.00

2 SITC of outdoor, all-weather proof, Non-Walk-in type Compact


Secondary Substation of robust construction, vermin & dust proof,
capable of withstanding thermal & mechanical stresses as per the
max Short Circuit rating at 11KV, 50 HZ. The prefabricated
enclosure is to be fabricated out of suitable GI sheet steel &
complying to protection degree of IP54 (LT & HT switchgear
compartment) & IP23 ( for transformer), with suitable MS base
Channel framework for rigidity, necesary covers & doors with
safety interlocking, Earthing arrangement, ventillation
arrangement, Internal light points & fittings, polyurethane painting
and foundation( as per OEM recommondation) etc. complete as per
CPWD specifications whereever applicable, including supplying
& Installation of the following in seperate compartments in the
above CSS.

A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.

B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta- star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.

Page 71
S.No Description Qty Rate Unit Amount
C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1600 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side,with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 2 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and with Microprocessor release, for
Protection & isolation of LT side, with suitable Alluminium Bus Bar/
Spreaders, and all required accessories etc. complete as required. - 2
Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
4 Nos..
iv) LED phase indication lamps with fuses - 4 Set

D) Outdoor type enclosure having construction of Galvanised Sheet


Steel of thickness 2 mm for Load bearing member and 1.5 m for Non
Load bearing member. The Enclosure shall have IP54 degree of
protection for HT & LT switchgear compartment & IP23 degree
of protection for Transformer compartment. The enclosure exterior
shall be Polyuratne painted (Colour Light Gray & D.A.Gray ). Each
compartment will be provided with the door and pad locking
arrangement. The Compartment illumination lamp with door operated
switch shall be provided for MV and LV compartment.

Internal Earthing connection with Minimum 50 x 6 mm Aluminium


strips.

E) Interconnection Between HT switchgear & Transformer using 1C


x 3R x 95 Sq.mm XLPE Single core cable & Interconnection
between Transformer & LT switchgear using Al. Busbars. Internal
earthing connections including Transformer neutral shall be using 50
x 6 mm GI strips. Required Bus connections, interlocking
arrangements within unit, Transportation & Crane hoisting etc.
as required- - 1 SET

Page 72
S.No Description Qty Rate Unit Amount
(Make: ABB/Schneider Electric/ Siemens) 1 6238601.00 Job 6238601.00
( Near New EMI-EMC Building)

3 SITC of outdoor, all-weather proof, Non-Walk-in type Compact


Secondary Substation of robust construction, vermin & dust proof,
capable of withstanding thermal & mechanical stresses as per the
max Short Circuit rating at 11KV, 50 HZ. The prefabricated
enclosure is to be fabricated out of suitable GI sheet steel &
complying to protection degree of IP54 (LT & HT switchgear
compartment) & IP23 ( for transformer), with suitable MS base
Channel framework for rigidity, necesary covers & doors with
safety interlocking, Earthing arrangement, ventillation
arrangement, Internal light points & fittings, polyurethane painting
and foundation (as per OEM recommondation) etc. complete as per
CPWD specifications whereever applicable, including supplying
& Installation of the following in seperate compartments in the
above CSS.

A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of 2 (two) number load
break switches and 1 (one) No. Fixed Manual Vacuum Circuit
Breaker with Microprocessor based self Powered Relay in SF6
insulated stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.

B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta - star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.

C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1600 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side ,with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 1 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side, with adjustable O/C and E/F setting
,with suitable Alluminium Bus Bar/ Spreaders, and all required
accessories etc. complete as required. - 2 Set.
iii) 400 Amp, 415 V, 4 Pole, 50KA, MCCB with Microprocessor
release, for Protection & isolation of LT side,with adjustable O/C and
E/F setting , with suitable Alluminium Bus Bar/ Spreaders, and all
required accessories etc. complete as required. - 1Set.
iV) LED Multifunction meter with Class 1 accuracy with RS485 port -
4 Nos..
v) LED phase indication lamps with fuses - 4 Set

Page 73
S.No Description Qty Rate Unit Amount
D) Outdoor type enclosure having construction of Galvanised Sheet
Steel of thickness 2 mm for Load bearing member and 1.5 m for Non
Load bearing member. The Enclosure shall have IP54 degree of
protection for HT & LT switchgear compartment & IP23 degree
of protection for Transformer compartment. The enclosure exterior
shall be Polyuratne painted (Colour Light Gray & D.A.Gray ). Each
compartment will be provided with the door and pad locking
arrangement. The Compartment illumination lamp with door operated
switch shall be provided for MV and LV compartment.

Internal Earthing connection with Minimum 50 x 6 mm Aluminium


strips.

E) Interconnection Between HT switchgear & Transformer using 1C


x 3R x 95 Sq.mm XLPE Single core cable & Interconnection
between Transformer & LT switchgear using Al. Busbars. Internal
earthing connections including Transformer neutral shall be using 50
x 6 mm GI strips. Required Bus connections, interlocking
arrangements within unit, Transportation & Crane hoisting etc.
as required- - 1 SET

Compact Sub Station Complete as above (Behind old LED LAB)


1 6115173.00 Job 6115173.00

4 SITC of outdoor, all-weather proof, Non-Walk-in type Compact


Secondary Substation of robust construction, vermin & dust proof,
capable of withstanding thermal & mechanical stresses as per the
max Short Circuit rating at 11KV, 50 HZ. The prefabricated
enclosure is to be fabricated out of suitable GI sheet steel &
complying to protection degree of IP54 (LT & HT switchgear
compartment) & IP23 ( for transformer), with suitable MS base
Channel framework for rigidity, necesary covers & doors with
safety interlocking, Earthing arrangement, ventillation
arrangement, Internal light points & fittings, polyurethane painting
and foundation (as per OEM recommondation), etc. complete as per
CPWD specifications whereever applicable, including supplying
& Installation of the following in seperate compartments in the
above CSS.

A) HT Switchgear :
11kV 630Amps, 21 kA for 3 Sec. Indoor type SF6 insulated Non-
Extensible Compact switchgear consisting of two number load
break switches and one No. Fixed Manual Vacuum Circuit Breaker
with Microprocessor based self Powered Relay in SF6 insulated
stainless steel enclosure, with series trip, self powered
microprocessor based numerical over current relay (IDMTL+ Inst.)
protection and Air Insulated Metering Module of Class -1.0.
Interconnection between HT switchgear and transformer
etc.complete as required as per detailed specification.- 1 Set.

B)Transformer:
2000 KVA Continuous rating, copper wound cast resin dry type,
11/0.433 KV, hermatically sealed, delta-star Transformer suitable
for indoor & outdoor in suitable enclosure, with rotary type off-load
tap changer for adjustment of HV in 4 equal steps varying from +5%
to - 5%, etc complete as per detailed specification. - 1 Set.

Page 74
S.No Description Qty Rate Unit Amount
C) L.T.Compartment:
Incomer: 3200 Amps capacity 4 strip suitable Alluminium Bus Bar
(100% for phase and 50% for Neutral) and all required accessories
etc. complete as required. - 1 Set.
Out Going:
i) 1200 Amp, 415 V, 4 Pole, 50KA, fixed manual type Air Circuit
Breaker with Microprocessor release, for Protection & isolation of
LT side, with adjustable O/C and E/F setting , with suitable
Alluminium Bus Bar/ Spreaders, DMC/SMC insulator and all
required accessories etc. complete as required. - 2 Set
ii) 800 Amp, 415 V, 4 Pole, 50KA, MCCB ( Ics =100%Icu) with
Rotary operating Meachanism and Microprocessor release, for
Protection & isolation of LT side,with adjustable O/C and E/F setting
, with suitable Alluminium Bus Bar/ Spreaders, and all required
accessories etc. complete as required. - 1 Set.
iii) LED Multifunction meter with Class 1 accuracy with RS485 port -
3 Nos..
iv) LED phase indication lamps with fuses - 3 Set

D) Outdoor type enclosure having construction of Galvanised Sheet


Steel of thickness 2 mm for Load bearing member and 1.6 mm
minimum for Non Load bearing member. The Enclosure shall have
IP54 degree of protection for HT & LT switchgear compartment
& IP23 degree of protection for Transformer compartment. The
enclosure exterior shall be Polyuratne painted (Colour Light Gray &
D.A.Gray ). Each compartment will be provided with the door and
pad locking arrangement. The Compartment illumination lamp with
door operated switch shall be provided for MV and LV compartment.

Internal Earthing connection with Minimum 50 x 6 mm Aluminium


strips.
E) Interconnection Between HT switchgear & Transformer using 1C
x 3R x 95 Sq.mm XLPE Single core cable & Interconnection
between Transformer & LT switchgear using Al. Busbars. Internal
earthing connections including Transformer neutral shall be using 50
x 6 mm GI strips. Required Bus connections, interlocking
arrangements within unit, Transportation & Crane hoisting etc.
as required- - 1 SET

Compact Sub Station Complete as above ( Near new IP LAB)


1 6046421.00 Job 6046421.00

Out -Door VCB Based RMU for Existing Substation


5 SITC of Outdoor 11 KV VCB type extensible and motorized 4 way
smart Ring Main Unit (RMU), all-weather proof, Non-Walk-in type
of robust construction, vermin & dust proof, capable of withstanding
thermal & mechanical stresses as per the max Short Circuit rating.
The prefabricated enclosure is to be fabricated out of suitable GI
sheet steel & complying to protection degree of IP54 (HT
switchgear compartment) with suitable MS base Channel framework
for rigidity, necesary covers & doors with safety interlocking,
Earthing arrangement, ventillation arrangement polyurethane painting
and foundation (As per OEM recommondation) etc.complete as per
CPWD specifications.

Page 75
S.No Description Qty Rate Unit Amount
HT Switchgear-2 in comming and 2 out going : 630 Amps 21kA
for 3 Sec, Outdoor type, VCB Compact Ring Main Unit, Consisting
of 2 Nos (Two) in comming and 2 Nos out going , 3 Pole VC'B's
totally enclosed & fully interlocked, horizontal draw out, horizontal /
Vertical isolation type breaker as per IS 13118, as amended up to date
and additional specifications,single break, trip free mechanism,
manually charged and manually closing breaker suitable for use on 11
KV, 3 phase, 50Hz AC supply with short circuit fault level of 350
MVA, complete with self contained, fully interlocked, rack in and
rack out mechanism, with microprocessor based self powered type
protection relay (3 O/C+1 E/F) with CT's mounted in cable box
etc.,complete as required.

RMU Accessories:- Standard ammeter,voltmeter, manometer, right


angled cable boots suitable for 1 Run x 3 x 300 Sq.mm, Operating
handle and 12 Volts 12 Ah Battery - 2 Nos. with charger of 5 Amp.

(Make: ABB/Schneider Electric/ Siemens) 1 1077459.00 Job 1077459.00

6 OUTDOOR TYPE MAIN HT PANEL


Supplying, installation, testing & commissioning of Out-door type
Pedestal mounted metal clad, 11KV VCB panel with 4 Nos.VCBs( 1
Nos-I/c & 3 No O/g) totally enclosed & fully interlocked, horizontal
draw out, horizontal isolation type breaker as per IS 13118, as amended
up to date and additional specifications, having capacities as mentioned
below, single break, trip free mechanism, manually charged and manually
closing breaker suitable for use on 11 KV, 3 phase, 50Hz AC supply with
short circuit fault level of 350 MVA, complete with self contained, fully
interlocked, rack in and rack out mechanism, air insulated but
encapsulated copper bus bars of 630A capacity, breaker featured with
mechanical ON / OFF indicator with hand trip device, spring release coil,
shunt trip coil and auxiliary switch of 4 NO + 4 NC and equipped with
following switch gears and complying to protection degree of IP54
(HT switchgear compartment) with suitable MS base Channel framework
for rigidity, necesary covers & doors with safety interlocking, Earthing
arrangement, ventillation arrangement polyurethane painting and
foundation(As per OEM recommendation), etc.complete as per CPWD
specifications along with all accessories i/c connections with suitable for
3 x 300 sq.mm XLPE 11 KV cable (cable entry from bottom), end
termination with heat shrinkable jointing material etc. as required. (Note-
Cost of end termination not included in this item)

A) Incoming- 630 Amps VCB- 1 No. with the Following

a) 11 KV/ 110 Volts PT class 0.5 accuracy and not less than 100 VA
Burden with 1 no Voltmeter 15 KV Digital / analog type with
selector switch for voltmeter and protection fuses for metering upto
12 KV on Incomer- 1No.

b) 0-100 Amps Digital Ammeter with Selector switch -1 No.

c) Microprocessor based numerical relay with O/L,E/F, S/C


Protection- 1No.

d) Dual core dual ratio 3 CTS 100/50/5/5 A of 15 VA burden and


accuracy class -0.5 for metering and class5P 10 for protection -1 Set.

e) Master trip relay and trip circuit healthy supervision relay and
power pack -1 Set

f) Phase Indicating lamps with MCB's-1 Sets.


g) Indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING
CHARGED, TRIP CIRCUIT HEALTHY- 1 Set.

Page 76
S.No Description Qty Rate Unit Amount
h) Annunciator - 1 No.
i) Push buttons for close and trip- 1 Set
j) Space Heater- 1 Set
B) Outgoing -630 Amps VCB- 3 Nos. with the Following

a) 0-100 Amps Dual scale Ammeter ,analog type with Selector switch
-1 No.

b) Microprocessor based numerical relay with O/L,E/F, S/C


Protection- 1No.

c) Dual core dual ratio 3 CTS 100/50/5/5 A of 15 VA burden and


accuracy class -0.5 for metering and class5P 10 for protection -1 Set.

d) Master trip relay and trip circuit healthy supervision relay and
power pack -1 Set

e) Phase Indicating lamps with MCB's-1 Sets.

f) Indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING


CHARGED, TRIP CIRCUIT HEALTHY- 1 Set.

g) Annunciator - 1 No.

h) Push buttons for close and trip- 1 Set

i) Space Heater- 1 Set 1 2690171.00 Job 2690171.00

7 Supplying of following size 11 KV, HT Unearthed, XLPE insulated


armoured Aluminium Conductor Cable confirming to IS 7098(Part II)
amended upto date as per CPWD specifications. etc complete as
required.

7.1 3 x 300 Sq.mm. 2500 2073.00 Meter 5182500.00

8 Laying of one number PVC insulated and PVC sheated / XLPE


power cable of 11 KV grade of following size in the existing RCC/
HUME/ METAL pipe as required.

8.1 Above 120 sq. mm and upto 400 sq. mm


112.00
2350 Meter 263200.00

9 Supplying and laying of following size DWC HDPE pipe ISI marked
along with all accessories like socket, bend, couplers etc. conforming
to IS 14930, Part II complete with fitting and cutting, jointing
etc.direct in ground ( 1-meter below ground level) including
excavation and refilling the trench but excluding sand cushioning and
protective covering etc., complete as required.

9.1 200 mm dia (OD-200 mm & ID-175 mm nominal)


2200 598.00 Meter 1315600.00

10 Drilling with Horizontal Direct Drilling method(HDD), suitable for


drawing of 150 mm dia G.I pipe as per IS: 4984 pipe minimum
depth of 1 Mtr below ground level complete with all equipments,
tools and materials including drawing the G.I pipe as required for the
work. (work to be carried for road crossing)

150 1375.00 Meter 206250.00

11 Supplying and making indoor cable end termination with heat


shrinkable jointing kit complete with all accessories including lugs
suitable for following size of 3 core, XLPE aluminium conductor
cable of 11 KV grade as required :

Page 77
S.No Description Qty Rate Unit Amount
11.1 3 x 300 Sq. mm 16 11681.00 Each 186896.00

12 Supplying and making straight through cable jointing with heat


shrinkable jointing kit complete with all accessories including
ferrules suitable for following size of 3 core, XLPE aluminium
conductor cable of 11 KV grade as required :

12.1 3 x 300 Sq. mm 12 19314.00 Each 231768.00

13 Supplying and making cable route marker with cement concrete 1:2:4
( 1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal
size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the
top with a thickness of 10 cm including inscription duly engraved as
required

100 530.00 Each 53000.00

14 Providing, laying and fixing following dia G.I. pipe (medium class) in
ground complete with G.I. fittings including trenching (75 cm
deep)and re-filling etc as required

14.1 150 mm dia 150 1687.00 Mtrs. 253050.00

15 Construction of following size Brick Masanory Manhole chamber in


cement mortor 1:4 ( 1 cement : 4 coarse sand ) with RCC top slab for
UG Cable Trench for drawing out the cable at the time of cable faults
i/c excavation and refiling the same etc., complete as required. ( The
size of the chamber shall be not less than 1.0 mtr x 1.0 mtr x 1.0 mtr
deep ).

25 9820.00 Job 245500.00

16 Earthing with copper earth plate 600 mm X 600 mm X 3 mmthick


including accessories, and providing masonry enclosurewith cover
plate having locking arrangement and watering pipeof 2.7 meter long
etc. with charcoal/ coke and salt as required. ( For Both Body &
Neutral Earthing )

20 11794.00 Set 235880.00

17 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.


pipe from earth electrode including connection with brassnut, bolt,
spring, washer excavation and re-filling etc. as required.

100 1224.00 Mtr 122400.00

18 Providing and fixing 32 mm X 6 mm copper strip in 50 mm dia G.I.


pipe from earth electrode including connection with brassnut, bolt,
spring, washer excavation and re-filling etc. as required.( For Neutral
earthing of Transformer above 1600 KVA capacity.)

80 1623.00 Mtr 129840.00

19 Providing and fixing 25 mm X 5 mm copper strip on surface or in


recess for connections etc. as required
50 1009.00 Mtr 50450.00

20 Providing and fixing 32 mm X 6 mm copper strip on surface or in


recess for connections etc. as required
20 1161.00 Mtr 23220.00
Total 34258668.00

Executive Engineer(E)
BCED-I, CPWD, Bangalore.