You are on page 1of 94

User’s

Manual
EJX and EJA-E Series

Differential Pressure and


Pressure Transmitters
Installation Manual

IM 01C25A01-01E

Contents
1. Introduction
1.1 For Safe Use of Product.....................................2
1.2 Warranty..........................................................4
1.3 ATEX Documentation........................................ 5
2. Handling Cautions
2.1 Model and Specifications Check..........................7
2.2 Selecting the Installation Location....................... 7
2.3 Pressure Connection......................................... 7
2.4 Installation of an Explosion-Protected Instrument. .7
2.5 EMC Conformity Standards...............................27
2.6 Pressure Equipment Directive (PED)..................28
2.7 Safety Requirement Standards..........................29
3. Installation
3.1 Mounting........................................................ 30
3.2 Mounting the Diaphragm Seals..........................30
3.3 Diaphragm Seals Installation Consideration........31
3.4 Mounting the Flushing Connection Ring..............32
3.5 Affixing the Teflon Film.....................................33
3.6 Rotating Transmitter Section.............................34
3.7 Changing the Direction of Integral Indicator.........34
4. Installing Impulse Piping
4.1 Impulse Piping Installation Precautions...............35
4.2 Impulse Piping Connection Examples................37
4.3 Process Piping Installation Precautions (EJ115).38

5. Wiring
5.1 Wiring Precautions...........................................40
5.2 Connections of External Wiring to Terminal Box.. 40
5.3 Wiring............................................................ 43
5.4 RTD Cable Connection (EJX910A/EJX930A)......45
5.5 Grounding.......................................................47
5.6 Power Supply Voltage and Load Resistance.......47
6. Operation
6.1 Preparation for Starting Operation..................... 48
6.2 Zero Point Adjustment......................................48
6.3 Local Parameter Setting...................................49
7. Errors and Countermeasures

IM 01C25A01-01E
12th Edition
<1. Introduction>
1

1. Introduction
This installation manual provides the basic guidelines for [EJX series Communication Manual]
installation and wiring procedures of the DPharp EJX Models Document No. Style
series and EJA-E series transmitters with BRAIN and DPharp HART 5/HART 7 IM 01C25T01-06EN —
HART protocols and is composed of the information Communication Type
extracted from the product users’ manuals as listed in DPharp FOUNDATION Fieldbus IM 01C25T02-01E —
Communication Type
Table 1.1. It does not provide the information including
DPharp BRAIN Communication IM 01C25T03-01E —
wiring procedures of the transmitters with FOUNDATION
Type
Fieldbus, Profibus and Modbus protocols, product DPharp PROFIBUS PA IM 01C25T04-01EN —
specific functional specifications and explanations, Communication Type
operation, maintenance and trouble-shooting. EJX910A and EJX930A HART IM 01C25R02-01E —
Communication Type
For EJXC40A Digital Remote Sensor, as this EJX910A and EJX930A IM 01C25R03-01E —
Installation Manual does not cover the product, Fieldbus Communication Type
please refer to the dedicated manual for EJXC40A. EJX910A and EJX930A Modbus IM 01C25R05-01E —
Communication Type

WARNING [EJA-E series Hardware Manual]


To ensure correct and safe use of the instrument, Models Document No. Style
obtain the manuals applicable to designated EJA110E, EJA120E
models and specifications as listed Table 1.1, EJA130E, EJA310E, EJA430E IM 01C25B01-01E S1
and EJA440E
read them thoroughly and fully understand how to
EJA210E IM 01C25C01-01E S1
operate the instrument before operating it. EJA510E and EJA530E IM 01C25F01-01E S1
EJA118E and EJA438E IM 01C25H01-01E S1
Users’ manual for each product consists of a hardware EJA115E IM 01C25K01-01E S1
EJAC80E and EJAC50E IM 01C25W01-01EN —
manual describing installation, wiring, operation,
maintenance and specification including detailed
model and suffix code information, and a [EJA-E series Communication Manual]
communication manual describing information specific Models Document No. Style
to each communication protocol type, including safety DPharp HART 5/HART 7 IM 01C25T01-06EN —
Communication Type
manual for safety instrumented system.
DPharp FOUNDATION Fieldbus IM 01C25T02-01E —
These manuals can be downloaded from the Communication Type
website of Yokogawa or purchased from the DPharp BRAIN Communication IM 01C25T03-01E —
Yokogawa representatives. Type
DPharp PROFIBUS PA IM 01C25T04-01EN —
Website address: http://www.yokogawa.com/fld/ Communication Type

Note: An exclusive User’s Manual might be attached for the


products whose suffix codes or optional codes contain
Table 1.1 PDF Manual List and Applicable Style Code code “Z”. Please read it along with the standard manuals.

[EJX series Hardware Manual]


Models Document No. Style
EJX110A S3
EJX120A IM 01C25B01-01E S1
EJX130A, EJX310A, EJX430A S2
and EJX440A
EJX210A IM 01C25C01-01E S2
EJX510A and EJX530A IM 01C25F01-01E S2
EJX610A and EJX630A S1
EJX118A and EJX438A IM 01C25H01-01E S2
EJX115A IM 01C25K01-01E S1
EJX910A IM 01C25R01-01E S2
EJX930A S1
EJXC80A and EJXC50A IM 01C25W01-01EN —
EJXC40A IM 01C25W05-01EN —

12th Edition: Feb. 2017 (YK) IM 01C25A01-01E

All Rights Reserved, Copyright © 2009, Yokogawa Electric Corporation


<1. Introduction>
2
 Regarding This Manual
IMPORTANT
• This manual should be passed on to the end user.
Indicates that operating the hardware or software in
• The contents of this manual are subject to
this manner may damage it or lead to system failure.
change without prior notice.
• All rights reserved. No part of this manual may
be reproduced in any form without Yokogawa’s
written permission. NOTE
• Yokogawa makes no warranty of any kind with
Draws attention to information essential for
regard to this manual, including, but not limited to,
understanding the operation and features.
implied warranty of merchantability and fitness for
a particular purpose.
Direct current
• If any question arises or errors are found, or if any
information is missing from this manual, please
inform the nearest Yokogawa sales office. Functional grounding terminal
• The specifications covered by this manual are
limited to those for the standard type under the Caution
specified model number break-down and do not This symbol indicates that the operator must
cover custom-made instruments. refer to an explanation in the user’s manual in
• Please note that changes in the specifications, order to avoid the risk of injury or death of
construction, or component parts of the instrument personnel or damage to the instrument.
may not immediately be reflected in this manual at
the time of change, provided that postponement of 1.1 For Safe Use of Product
revisions will not cause difficulty to the user from a
For the protection and safety of the operator and the
functional or performance standpoint.
instrument or the system including the instrument, please
• Yokogawa assumes no responsibilities for this
be sure to follow the instructions on safety described
product except as stated in the warranty.
in this manual when handling this instrument. In case
• If the customer or any third party is harmed by the the instrument is handled in contradiction to these
use of this product, Yokogawa assumes no instructions, Yokogawa does not guarantee safety.
responsibility for any such harm owing to any Please give your attention to the followings.
defects in the product which were not predictable,
or for any indirect damages. (a) Installation
• When describing the model name like EJ110 in
this manual, it shows the applicability for both
EJX110A and EJA110E. The same representations WARNING
are used for the other models, too.
• The instrument must be installed by an expert
• The following safety symbol marks are used in engineer or a skilled personnel. The procedures
this manual: described about INSTALLATION are not
permitted for operators.
• In case of high process temperature, care should
WARNING be taken not to burn yourself because the surface
of body and case reaches a high temperature.
Indicates a potentially hazardous situation which, if
• The instrument installed in the process is
not avoided, could result in death or serious injury.
under pressure. Never loosen the process
connector bolts to avoid the dangerous
spouting of process fluid.
• During draining condensate from the pressure
CAUTION detector section, take appropriate care to avoid
Indicates a potentially hazardous situation which, if not contact with the skin, eyes or body, or inhalation
avoided, may result in minor or moderate injury. It may of vapors, if the accumulated process fluid may
also be used to alert against unsafe practices. be toxic or otherwise harmful.
• When removing the instrument from
hazardous processes, avoid contact with the
fluid and the interior of the meter.
• All installation shall comply with local installation
requirement and local electrical code.
IM
01C25A01-
01E
<1. Introduction>
3
(b) Wiring (e) Explosion Protected Type Instrument

WARNING WARNING
• The instrument must be installed by an expert • Users of explosion proof instruments should refer
engineer or a skilled personnel. The first to section 2.4 (Installation of an Explosion
procedures described about WIRING are not Protected Instrument) of this manual.
permitted for operators. • For TIIS flameproof type instruments, be sure
• Please confirm that voltages between the to read “INSTALLATION AND OPERATING
power supply and the instrument before PRECAUTIONS FOR TIIS FLAMEPROOF
connecting the power cables and that the EQUIPMENT” at the end of this manual.
cables are not powered before connecting. • The use of this instrument is restricted to
those who have received appropriate
training in the device.
(c) Operation • Take care not to create sparks when accessing
the instrument or peripheral devices in a
hazardous location.
WARNING
• Wait 5 min. after power is turned off,
(f) Modification
before opening the covers.
• Do not open the cover in wet weather or
humid environment. If the cover is opened,
stated enclosure protection is not applicable.
WARNING
• Yokogawa will not be liable for malfunctions or
damage resulting from any modification made
(d) Maintenance to this instrument by the customer.

WARNING (g) Product Disposal


• Please do not carry out except being written The instrument should be disposed of in accordance
to maintenance descriptions. When these with local and national legislation/regulations.
procedures are needed, please contact
nearest YOKOGAWA office.
(h) Authorized Representative in EEA
• Care should be taken to prevent the build up In relation to the CE Marking, The authorized
of drift, dust or other material on the display representative for this product in the EEA (European
glass and name plate. In case of its Economic Area) is:
maintenance, soft and dry cloth is used. Yokogawa Europe B.V.
Euroweg 2, 3825 HD Amersfoort,The Netherlands
IM
01C25A01-
01E
<1. Introduction>
4
(i) Control of Pollution Caused by the Product
This is an explanation for the product based on “Control of Pollution caused by Electronic
Information Products” in the People’s Republic of China. The information is valid only in China.

产品中有害物质或元素的名称及含量
有害物质
型号 部件名称 铅 汞 镉 六价铬 多溴联苯 多溴二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB) (PBDE)
壳体 × ○ ○ ○ ○ ○
EJX/EJA-E/ 膜盒组件 × ○ ○ ○ ○ ○
EJA/EJA-A Series 基板组件 × ○ ○ × ○ ○
差压/压力变送器
电源连接线 × ○ ○ ○ ○ ○
FVX110 壳体 × ○ ○ ○ ○ ○
基板组件 × ○ ○ × ○ ○
现场总线网段指示器
电源连接线 × ○ ○ ○ ○ ○

○:表示该部件的所有均质材料中的有害物质的含量均在 GB/T26572 标准中所规定的限量以下。

×:表示至少该部件的某些均质材料中的有害物质的含量均在 GB/T26572 标准中所规定的限量以上。

环保使用期限:

该标识适用于 SJ /T11364 中所述,在中华人民共和国销售的电子电气产品的环保使用期限。

注)该年数为“环保使用期限”,并非产品的质量保证期。

1.2 Warranty - Failure or damage due to improper handling, use


or storage which is out of design conditions.
• The warranty shall cover the period noted on the - Use of the product in question in a location not
quotation presented to the purchaser at the time of conforming to the standards specified by
purchase. Problems occurred during the warranty Yokogawa, or due to improper maintenance of
period shall basically be repaired free of charge. the installation location.
• In case of problems, the customer should contact the - Failure or damage due to modification or
Yokogawa representative from which the instrument repair by any party except Yokogawa or an
approved representative of Yokogawa.
was purchased, or the nearest Yokogawa office.
- Malfunction or damage from improper relocation
• If a problem arises with this instrument, please inform
of the product in question after delivery.
us of the nature of the problem and the circumstances
- Reason of force majeure such as fires,
under which it developed, including the model
earthquakes, storms/floods, thunder/lightening,
specification and serial number. Any diagrams,
or other natural disasters, or disturbances, riots,
data and other information you can include in
warfare, or radioactive contamination.
your communication will also be helpful.
• Responsible party for repair cost for the  Trademarks:
problems shall be determined by Yokogawa • ‘DPharp’, ‘EJX’, ‘EJA’, ‘FieldMate’ and ‘BRAIN
based on our investigation. TERMINAL’ are registered trademarks of Yokogawa
• The Purchaser shall bear the responsibility for Electric Corporation. Company names and product
repair costs, even during the warranty period, if names used in this material are registered trademarks
or trademarks of their respective owners.
the malfunction is due to:
• In this manual, trademarks or registered
- Improper and/or inadequate maintenance by
trademarks are not marked with ™ or ®.
the purchaser.

IM
01C25A01-
01E
<1. Introduction>
5
1.3 ATEX Documentation
This is only applicable to the countries in European Union.

GB SK

CZ
DK

I LT

E LV

EST
NL

PL

SF

SLO P

BG

RO

S
M

GR
IM
01C25A01-
01E
<2. Handling Cautions>
6

2. Handling Cautions
When the transmitter is delivered, visually check them EJ110 B
to make sure that no damage occurred during EJ120 1 D
shipment. Also check that all transmitter mounting EJ130 -  2  - G
EJ310 3 J
hardware shown in Figure 2.1 is included. If the
EJ430 4 K
transmitter was ordered without the mounting bracket EJ440 M
or without the process connector, the transmitter B 1
mounting hardware is not included.
2
Table 2.1 Applicable Model Code for Mounting 1 D 3
Hardware EJX910A -  2  - G 4
EJX930A 3 J
Applicable Suffix code Part name Qty B
4 K C
model M D
EJ110 Process Process connector bolt 4
EJ120 Process connector 2 1
EJ130 connections EJ210 -  2  - 
Process connector
EJX910A 1,2,3 and 4 2 3
EJX930A gasket 4
EJ510
EJ210 Process Process connector bolt 2
EJ530 F
EJ310 connections Process connector 1
EJX610A -  -  L
EJ430 Process connector
1,2,3 and 4 1 EJX630A
EJ440 gasket
EJ118 B
EJ110 U-bolt 1
EJ120 EJ438
EJ130 -  -  J
EJ310 Mounting bracket U-bolt nut 2 B
EJ430
D
EJ440 B,D,G,J,K and EJ115 -  -  J
Mounting bracket
EJ118 M* 1 K
EJ438 (L or flat type) F0201.ai
EJ115 Transmitter mounting
EJX910A 4 Cable gland and RTD cable
EJX930A bolt
(EJX910A and EJX930A only)
Mounting U-bolt 1 Bolt
bracket M (For U-bolt nut 2
EJ110 measurement Mounting bracket 1 Process connector
span code other Process connector
Transmitter mounting 2
than F) bolt Gasket

EJ510 Mounting bracket U-bolt (L and S) 1 ea. U-bolt


EJ530 U-bolt nut (L and S) 2 ea.
EJX610A F and L Mounting bracket 1
EJX630A
External
temperature input RTD cable 1 Mounting bracket
EJX910A B, C and D (Flat type)
EJX930A External Mounting bracket
temperature input Cable gland 2 (L type)
1, 2, 3 and 4 U-bolt nut
EJ210 Option code /TF1 Teflon film 1 Transmitter mounting bolt U-bolt
EJ438 Fluorinated oil 1 nut (L)
EJ118 Option code /TF1 Teflon film 2 Teflon film
Fluorinated oil 2
*: For measurement span code F.
Fluorinated oil

Mounting bracket

U-bolt nut (S)


U-bolt (S)

U-bolt (L)
F0202.ai

Figure 2.1 Transmitter Mounting Hardware


IM
01C25A01-
01E
<2. Handling Cautions>
7

2.1 Model and Specifications 2.3 Pressure Connection


Check
The model name and specifications are indicated on WARNING
the name plate attached to the case. • Never loosen the process connector bolts when an
instrument is installed in a process. The device is
under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluid.
• When draining toxic process fluids that have
condensed inside the pressure detector, take
appropriate steps to prevent the contact of
such fluids with the skin or eyes and the
inhalation of vapors from these fluids.

The following precautions must be observed in order


F0203.ai
to safely operate the transmitter under pressure.
Figure 2.2 Name Plate
(a) Make sure that the process connector bolts
are tightened firmly.
2.2 Selecting the (b) Make sure that there are no leaks in the
impulse piping.
Installation Location (c) Never apply a pressure higher than the
The transmitter is designed to withstand severe specified maximum working pressure.
environmental conditions. However, to ensure that it
will provide years of stable and accurate
performance, take the following precautions when
2.4 Installation of an Explosion-
selecting the installation location. Protected Instrument
(a) Ambient Temperature If a customer makes a repair or modification to an
Avoid locations subject to wide temperature variations intrinsically safe or explosionproof instrument and the
or a significant temperature gradient. If the location is instrument is not restored to its original condition, its
exposed to radiant heat from plant equipment, provide intrinsically safe or explosionproof construction may be
adequate thermal insulation and/or ventilation. compromised and the instrument may be hazardous to
(b) Ambient Atmosphere operate. Please contact Yokogawa before making any
Do not install the transmitter in a corrosive repair or modification to an instrument.
atmosphere. If this cannot be avoided, there must
be adequate ventilation as well as measures to
prevent the leaking of rain water and the presence
CAUTION
of standing water in the conduits. This instrument has been tested and certified as being
intrinsically safe or explosionproof. Please note that
(c) Shock and Vibration
severe restrictions apply to this instrument’s
Although the transmitter is designed to be relatively
construction, installation, external wiring, maintenance
resistant to shock and vibration, an installation site
and repair. A failure to abide by these restrictions could
should be selected where this is kept to a minimum.
make the instrument a hazard to operate.
(d) Installation of Explosion-protected Transmitters An
explosion-protected transmitters is certified for
installation in a hazardous area containing specific
gas types. See subsection 2.4 “Installation of an WARNING
Explosion-Protected Instrument.” Maintaining the safety of explosionproof
equipment requires great care during mounting,
wiring, and piping. Safety requirements also place
restrictions on maintenance and repair. Please
read the following sections very carefully.
IM
01C25A01-
01E
<2. Handling Cautions>
8

WARNING
The range setting switch must not be used
in a hazardous area.

IMPORTANT
For combined approval types
Once a device of multiple approval type is installed,
it should not be re-installed using any other
approval types. Apply a permanent mark in the
check box of the selected approval type on the
certification label on the transmitter to distinguish it
from unused approval types.

2.4.1 FM Approval

a. FM Intrinsically Safe/Nonincendive
for HART/BRAIN Protocol Type
(Except for EJX90A)

Note 1. EJX/EJA-E Series pressure transmitters


with optional code /FS1 are applicable for
use in hazardous locations.
• Applicable Standard:
Class 3600:2011, Class 3610:2010, Class
3611:2004, Class 3810:2005 ANSI/ISA-
60079-0:2009, ANSI/ISA-60079-11:2009
NEMA 250:1991
• Rating
Intrinsically Safe for Class
I, II, III Division 1, Groups
A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC
T4 Nonincendive for
Class I, II, III Division 2
Groups A, B, C, D, F, G T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –60 to 60°C
• Enclosure: Type 4X
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM022-A12.
Note 3. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Intrinsically safe and
Nonincendive Approval.
IM
01C25A01-
01E
<2. Handling Cautions>
9
b. FM Intrinsically Safe/Nonincendive for
Fieldbus Type (Except for EJX90A)
EJX/EJA-E Series pressure transmitters with
optional code /FS15 are applicable for use in
hazardous locations.
Note 1.
• Applicable Standard:
Class 3600:2011, Class 3610:2010, Class
3611:2004, Class 3810:2005 ANSI/ISA-
60079-0:2009, ANSI/ISA-60079-11:2009
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO
for Class I, II, III Division 1,
Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO
for Class I, II Division 2
Groups A, B, C, D, F, G T4
Class III Division 1 T4 Class
I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection:
1/2 NPT female, M20 female
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM024-A12.
IM
01C25A01-
01E
<2. Handling Cautions>
10

c. FM Intrinsically Safe/Nonincendive
for Fieldbus Type for EJX90A
EJX multivariable transmitter with optional code
/FS15 are applicable for use in hazardous locations.
Note 1.
• Applicable Standard:
Class 3600:2011, Class 3610:2010, Class
3611:2004, Class 3810:2005 ANSI/ISA-60079-
0:2009, ANSI/ISA-60079-11:2009, ANSI/ISA-
60079-27:2006
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO for Class I, II,
III Division 1 Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO for Class I,
II Division 2 Groups A, B, C, D, F, G T4
Class III Division 1 T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection: 1/2 NPT female,
M20 female
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM026-A12.
IM
01C25A01-
01E
<2. Handling Cautions>
11
IM
01C25A01-
01E
<2. Handling Cautions>
12
d. FM Explosionproof
Caution for FM explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /FF1 or /V1F are
applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3615,
FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division
1, Groups E, F and G.
• Enclosure: Type 4X
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus
and PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
9 to 30 V dc, 250 mW (RS485
Modbus Communication Type)
• Output signal: 4 to 20 mA
15 mA (FOUNDATION Fieldbus and PROFIBUS
PA type)
1 to 5 V (Low Power type)
RS485 Modbus (RS485 Modbus Communication
Type)
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED.”
• Wiring connection for output signal code Q (Low
Power type) shall follow the diagram below.
Pressure Transmitters
SUPPLY+
Voltmeter
A Power Supply

+ +
– –

SUPPLY–

Three-Wire Connection
Pressure Transmitters

SUPPLY+
Voltmeter
A Power Supply

+ +
– –

SUPPLY–

F0218.ai
Four-Wire Connection
IM
01C25A01-
01E
<2. Handling Cautions>
13
Note 3. Operation • Intrinsically Safe for Class I, Division 1, Groups
• Keep the “WARNING” nameplate attached to A, B, C & D, Class II, Division 1, Groups E, F &
the transmitter. G, Class III, Division 1
WARNING: OPEN CIRCUIT BEFORE • Nonincendive for Class I, Division 2, Groups A, B,
REMOVING COVER. FACTORY SEALED, C & D, Class II, Division 2, Groups F & G, Class III,
CONDUIT SEAL NOT REQUIRED. INSTALL IN Division 1
ACCORDANCE WITH THE USERS MANUAL • Enclosure: Type 4X
IM 01C25. • Temp. Code: T4
• Take care not to generate mechanical sparking • Amb. Temp.: –50* to 60°C
when accessing to the instrument and peripheral * –15°C when /HE is specified.
devices in a hazardous location. • Process Temperature: 120°C max.
[For CSA E60079]
Note 4. Maintenance and Repair • Applicable Standard: CAN/CSA E60079-11,
• The instrument modification or parts replacement
CAN/CSA E60079-15, IEC 60529:2001
by other than authorized representative of
• Ex ia IIC T4, Ex nL IIC T4
Yokogawa Electric Corporation is prohibited and • Ambient Temperature: –50 to 60°C
will void Factory Mutual Explosionproof Approval. • Max. Process Temp.: 120°C
e. FM Intrinsically Safe and Explosion • Enclosure: IP66/IP67
Proof Combination for HART/BRAIN Note 2. Entity Parameters
Protocol Type • Intrinsically safe ratings are as follows:
EJX/EJA-E Series pressure transmitters with Maximum Input Voltage (Vmax/Ui) = 30 V
optional code /FU1 or /V1U1 can be selected the Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
type of protection (FM Intrinsically Safe or FM
Maximum Internal Capacitance (Ci) = 10 nF
Explosionproof) for use in hazardous locations.
Maximum Internal Inductance (Li) = 0 µH
Note 1. For the installation of this transmitter, once • Type "n" or Nonincendive ratings are as
a particular type of protection is selected, follows: Maximum Input Voltage (Vmax/Ui) =
any other type of protection cannot be 30 V Maximum Internal Capacitance (Ci) = 10
used. The installation must be in nF Maximum Internal Inductance (Li) = 0 µH
accordance with the description about the • Installation Requirements
type of protection in this instruction manual. Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Note 2. In order to avoid confusion, unnecessary Co ≥ Ci + Ccable, Lo ≥ Li +
marking is crossed out on the label other Lcable Voc ≤ Vmax, Isc ≤ Imax,
than the selected type of protection when Ca ≥ Ci + Ccable, La ≥ Li + Lcable
the transmitter is installed. Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La
are parameters of barrier.
2.4.2 CSA Certification
Note 3. Installation
a. CSA Intrinsically Safe for HART/BRAIN • In any safety barreir used output current
must be limited by a resistor 'R' such that
Protocol Type (Except for EJX90A)
Io=Uo/R or Isc=Voc/R.
Caution for CSA Intrinsically safe and • The safety barrier must be CSA certified.
nonincendive type. (Following contents refer to • Input voltage of the safety barrier must be
“DOC No. ICS013-A13”) less than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian
Note 1. EJX/EJA-E Series pressure transmitters
Electrical Code Part I and Local Electrical Code.
with optional code /CS1 are applicable for
• Dust-tight conduit seal must be used when
use in hazardous locations.
installed in Class II and III environments.
Certificate: 1606623
• The instrument modification or parts replacement
[For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, by other than authorized representative of
C22.2 No.25, C22.2 No.94, C22.2 No.157, Yokogawa Electric Corporation and Yokogawa
C22.2 No.213, C22.2 No.60079-0, Corporation of America is prohibited and will void
C22.2 No.61010-1 , C22.2 No.61010-2-030 Canadian Standards Intrinsically safe and
nonincendive Certification.
IM
01C25A01-
01E
<2. Handling Cautions>
14
[Intrinsically Safe]  Caution for CSA Intrinsically Safe
Hazardous Location Nonhazardous Location Type. (Following Contents Refer to
Group IIC, Zone 0 “DOC. No. ICS018)
Class I, II, III, Division 1, General
Groups A, B, C, D, E, F, G
Installation Diagram for Intrinsically
Purpose
Pressure Transmitters Safety Barrier Equipment
Safe (Division 1 Installation)
+ + + + Terminator
Supply – – – –
F0206.ai
+ Pressure
– Transmitter

[Nonincendive] +
– Field Instruments
Hazardous Location Nonhazardous Location
Group IIC, Zone 2
+
Class I, II, Division 2, CSA Certified – Field Instruments
Groups A, B, C, D, F, Equipment
G Class III, Division 1. ([nL] or
Pressure Transmitters nonincendive) Hazardous Location
+ + Non-Hazardous Location
Terminator
Supply – –
Not Use + –
Safety Barrier Safety Barrier
F0207.ai
+ F0229.ai

b. CSA Intrinsically Safe for Fieldbus
Type (Except for EJX90A) Note 1. The safety barrier must be CSA certified.

EJX/EJA-E Series pressure transmitters with Note 2. Input voltage of the safety barrier must be
optional code /CS15 are applicable for use in less than 250Vrms/Vdc.
hazardous locations.
Note 3. Installation should be in accordance
• Certificate: 1689689
with Canadian Electrical Code Part I
• Applicable standard: C22.2 No.0, C22.2 No.0.4,
and local Electrical Code.
C22.2 No.25, C22.2 No.94, C22.2 No.157,
C22.2 No.213, C22.2 No.61010-1, Note 4. Do not alter drawing without authorization
C22.2 No.61010-2-030, C22.2 No.60079-0, from CSA.
CAN/CSA E60079-0, CAN/CSA E60079-11,
Electrical Data:
CAN/CSA E60079-15, IEC 60529
• CSA Intrinsically Safe Approval • Rating 1 (Entity)
Class I, Division 1, Groups A, B, C, & D; Class For Groups A, B, C, D, E, F, and G or Group IIC
II, Division 1, Groups E, F & G; Class III; Ex ia Ui (vmax) = 24 V dc
IIC T4 Ambient Temperature: –40* to 60°C (– Ii (Imax) = 250 mA
40* to 140°F) Encl. Type 4X, IP66/IP67 Pi (Pmax) = 1.2 W
* –15°C when /HE is specified. Ci = 3.52 nF
• CSA Nonincendive Approval Li = 0 μH
Class I, Division 2, Groups A, B, C, & D; Class II, or
Division 2, Groups F & G; Class III; Ex nL IIC T4 • Rating 2 (FISCO)
Ambient Temperature: –40* to 60°C (–40* to For Groups A, B, C, D, E, F, and G or Group IIC
140°F) Encl. Type 4X, IP66/ IP67 Ui (vmax) = 17.5 V dc
* –15°C when /HE is specified.
Ii (Imax) = 380 mA
Pi (Pmax) = 5.32 W
Ci = 3.52 nF
Li = 0 μH
or
IM
01C25A01-
01E
<2. Handling Cautions>
15
• Rating 3 (FISCO) c. CSA Explosionproof Type
For Groups C, D, E, F, and G or Group
Caution for CSA explosionproof type.
IIB Ui (vmax) = 17.5 V dc
Ii (Imax) = 460 mA Note 1. EJX/EJA-E Series pressure transmitters
Pi (Pmax) = 5.32 with optional code /CF1 or /V1F are
W Ci = 3.52 nF applicable for use in hazardous locations.
Li = 0 μH • Certificate: 2014354
Installation requirements; • Applicable Standard: C22.2 No.0,
Po ≤ Pi Uo ≤ Ui Io ≤ Ii, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
Co ≥ Ci + Ccable Lo ≥ Li + C22.2 No.30, C22.2 No.94, C22.2 No.61010-1,
Lcable Vmax ≥ Voc Imax ≥ Isc C22.2 No.61010-2-030, C22.2 No.60079-0,
Ca ≥ Ci + Ccable La ≥ Li + Lcable C22.2 No.60079-1
Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are • Explosion-proof for Class I, Groups B, C and D.
parameters of barrier. • Dustignition-proof for Class II/III, Groups E, F and
G.
 Caution for CSA Non-incendive
• Enclosure: Type 4X
Type. (Following contents refer to • Temperature Code: T6...T4
“DOC. No. ICS018) • Ex d IIC T6...T4
Installation Diagram for Non-incendive or Type • Enclosure: IP66/IP67
of protection “n” (Division 2 Installation) • Maximum Process Temperature: 120°C
(T4), 100°C (T5), 85°C (T6)
Terminator • Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
+
SUPPLY * –15°C when /HE is specified.

Pressure • Supply Voltage: 42 V dc max.
Transmitter 32 V dc max. (FOUNDATION Fieldbus
+ and PROFIBUS PA type)
Transmitter
– 9 to 28 V dc, 27 mW (Low Power type)
9 to 30 V dc, 250 mW (RS485
Modbus Communication Type)
• Output Signal: 4 to 20 mA dc
+
– Transmitter 15 mA (FOUNDATION Fieldbus and PROFIBUS
PA type)
1 to 5 V (Low Power type)
Hazardous location RS485 Modbus (RS485 Modbus Communication
Type)
Non-Hazardous location
Terminator Note 2. Wiring
• All wiring shall comply with Canadian Electrical
+ –
Code Part I and Local Electrical Codes.
CSA Certified • In hazardous location, wiring shall be in conduit
Equipment [nL] as shown in the figure.
+ –
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN 50cm
F0230.ai
OF THE ENCLOSURE.
Note 1. Installation should be in accordance UN SCELLEMENT DOIT ÊTRE INSTALLÉ
with Canadian Electrical Code Part I À MOINS DE 50cm DU BOÎTIER.
and local Electrical Code. • WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
Note 2. Dust-tight conduit seal must be used when NOT REQUIRED.
installed in class II and III environments. UNE FOIS INSTALLÉ DANS CL I, DIV 2,
Note 3. Do not alter drawing without authorization AUCUN JOINT N'EST REQUIS.
from CSA.
Electrical Data:
• Rating (including FNICO)
Ui or Vmax = 32 V
Ci = 3.52 nF
Li = 0 μH
IM
01C25A01-
01E
<2. Handling Cautions>
16
Non-Hazardous Hazardous Locations Division 1 Note 3. Operation
Locations • WARNING:
AFTER DE-ENERGIZING, DELAY 5
Non-hazardous 50 cm Max. MINUTES BEFORE OPENING.
Location Equipment
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
• WARNING:
42 V DC Max. Sealing Fitting Conduit
4 to 20 mA DC WHEN AMBIENT TEMPERATURE ≥ 65°C,
Signal Transmitter USE THE HEAT-RESISTING CABLES ≥ 90°C.
F0208.ai QUAND LA TEMPÉRATURE AMBIANTE ≥
65°C, UTILISEZ DES CÂBLES RÉSISTANTES
Non-Hazardous Hazardous Locations Division 2 Á LA CHALEUR ≥ 90°C.
Locations
• Take care not to generate mechanical sparking
Non-hazardous
when accessing to the instrument and peripheral
Location Equipment
devices in a hazardous location.
Note 4. Maintenance and Repair
42 V DC Max. • The instrument modification or parts replacement
4 to 20 mA DC Sealing Fitting
Signal Transmitter by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
F0209.ai
Corporation of America is prohibited and will void
• All wiring shall comply with local installation Canadian Standards Explosionproof Certification.
requirements and local electrical code. d. CSA Intrinsically Safe and Explosion-
• In hazardous locations, the cable entry devices
proof Combination for HART/BRAIN
shall be of a certified flameproof type, suitable
for the conditions of use and correctly installed. Protocol Type (Except for EJX90A)
• Unused apertures shall be closed with suitable EJX/EJA-E Series pressure transmitters with
flameproof certified blanking elements. (The optional code /CU1 or /V1U1 can be selected the
plug attached is flameproof certified.) type of protection (CSA Intrinsically Safe or CSA
• Wiring connection for output signal code Q (Low Explosionproof) for use in hazardous locations.
Power type) shall follow the diagram below.
Note 1. For the installation of this transmitter, once a
Pressure Transmitters
SUPPLY+ Voltmeter particular type of protection is selected, any
other type of protection cannot be used. The
A
Power Supply installation must be in accordance with the
+
+ description about the type of protection in this
– instruction manual.

SUPPLY– Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
Three-Wire Connection
than the selected type of protection when
Pressure Transmitters the transmitter is installed.
SUPPLY+ Voltmeter 2.4.3 ATEX Certification
A
Power Supply
+ (1) Technical Data
+

– a. ATEX Intrinsically Safe for HART/BRAIN
SUPPLY– Protocol Type (Except for EJX90A)
Four-Wire Connection Caution for ATEX Intrinsically safe type.
F0219.ai
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /KS21 for potentially
explosive atmospheres.
• No. DEKRA 11ATEX0228 X
• Applicable Standard:
EN 60079-0:2012+A11:2013
EN 60079-11:2012

IM 01C25A01-01E
<2. Handling Cautions>
17
• Type of Protection and Marking Note 5. Special Conditions for Safe Use
code: Ex ia IIC T4 Ga
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
• Group: II WARNING
• Category: 1G, 2D
• When the enclosure of the Pressure Transmitter is
• Ambient Temperature for EPL
made of aluminum, if it is mounted in an area
Ga: –50 to 60°C
where the use of category 1G equipment is
• Ambient Temperature for EPL
required, it must be installed such, that, even in
Db: –30* to 60°C
* –15°C when /HE is specified. the event of rare incidents, ignition sources due to
• Process Temperature (Tp.): 120°C max. impact and friction sparks are excluded.
• Maximum Surface Temperature for EPL • Electrostatic charges on the coated parts
Db: T85°C (Tp.: 80°C) of Pressure Transmitter shall be avoided.
T100°C (Tp.: 100°C) • Electrostatic charge may cause an exlosion
T120°C (Tp.: 120°C) hazard. Avoid any actions that cause the
• Enclosure: IP66 / IP67 generation of electrostatic charge, such as rubbing
To satisfy IP66 or IP67, apply waterproof glands with a dry cloth on coating face of the product.
• In case of the enclosure of the Pressure
to the electrical connection port.
Transmitter with paint layers, if it is mounted in
Note 2 Electrical Data an area where the use of category 2D
• In type of explosion protection intrinsic safety Ex equipment is required, it shall be installed in
ia IIC or Ex ia IIIC, only for connection to a such a way that the risk from electrostatic
certified intrinsically safe circuit with following discharges and propagating brush discharges
maximum values:
caused by rapid flow of dust is avoided.
Ui = 30 V Ii =
200 mA Pi =
0.9 W (Linear b. ATEX Intrinsically Safe for Fieldbus
Source)
Type (Except for EJX90A)
Maximum internal capacitance; Ci = 27.6 nF
Caution for ATEX Intrinsically safe type.
Maximum internal inductance; Li = 0 µH
When the lightning protector option is specified, Note 1. EJX/EJA-E series pressure transmitters
the apparatus is not capable of withstanding the with optional code /KS26 are applicable for
500V insulation test required by EN60079-11. use in hazardous locations.
This must be taken into account when installing • No. KEMA 04ATEX1116 X
• Applicable Standard:
the apparatus.
EN 60079-0:2012+A11:2013
Note 3. Installation
EN 60079-11:2012
• Refer to the control drawing. All wiring shall
comply with local installation requirements. Note 2. Ratings
Type of Protection and Marking Code:
[Control Drawing]
Ex ia IIC/IIB T4 Ga
Hazardous Location Nonhazardous Location Ex ia IIIC T85°C T100°C T120°C Db
Pressure Transmitters Group: II
+ + Category: 1G, 2D
*1
Supply Safety Barrier Ambient Temperature for EPL Ga: –40 to 60°C
– – Ambient Temperature for EPL Db: –30* to 60°C
* –15°C when /HE is specified.
Maximum Process Temperature (Tp.): 120°C
Maximum Surface Temperature for EPL Db.
F0210.ai T85°C (Tp.: 80°C)
*1: Any safety barriers must be a linear power source T100°C (Tp.: 100°C)
whose output current is resistively limited. T120°C (Tp.: 120°C)
Ambient Humidity:
Note 4. Maintenance and Repair
• The instrument modification or parts replacement 0 to 100% (No condensation)
Degree of Protection of the Enclosure:
by other than authorized representative of
IP66 / IP67
Yokogawa Electric Corporation is prohibited and
will void DEKRA Intrinsically safe Certification.
IM
01C25A01-
01E
<2. Handling Cautions>
18
Electrical Data Note 6. Installation Instructions
• When combined with Trapezoidal and Rectangular [Installation Diagram]
output characteristic FISCO model IIC barrier
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32
Terminator
W, Ci = 3.52 nF, Li = 0 μH
• When combined with Linear characteristic
+ Pressure
barrier Ui = 24 V, Ii = 250 mA, Pi = 1.2 W, − SUPPLY
Transmitter
Ci = 3.52 nF, Li = 0 μH
• When combined with Trapezoidal or Rectangular + Transmitter
output characteristic FISCO model IIB barrier Ui −
= 17.5 V, Ii = 460 mA, Pi = 5.32 W, + Transmitter
Ci = 3.52 nF, Li = 0 μH

Note 3. Installation
• All wiring shall comply with local installation
Hazardous Location Non-
requirements. (Refer to the installation diagram)
Hazardous Location
Note 4. Maintenance and Repair Terminator
• The instrument modification or parts replacement
by other than authorized representative of + −
Yokogawa Electric Corporation is prohibited and Safety Barrier
+ −
will void DEKRA Intrinsically safe Certification. F0231.ai

Note 5. Special Conditions for Safe Use • In the rating 1(*1), the output current of the barrier
must be limited by a resistor ‘Ra’ such that Io = Uo/
Ra.
WARNING • In the rating 2(*2), the output of the barrier must
be the characteristics of the trapezoid or the
• In the case where the enclosure of the
rectangle and this transmitter can be connected
Pressure Transmitter is made of aluminium, if
to Fieldbus equipment which are in according to
it is mounted in an area where the use of
the FISCO model.
category 1 G apparatus is required, it must be
• The terminators may be built in by a barrier.
installed such, that even in the event of rare
• More than one transmitter may be connected
incidents, ignition sources due to impact and
to the power supply line.
friction sparks are excluded.
• The terminator and the safety barrier shall
• Electrostatic charge may cause an explosion
be certified.
hazard. Avoid any actions that cause the
Electrical data:
generation of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product. Maximum Input Voltage Ui: 24 V
• In the case where the enclosure of the Pressure Maximum Input Current Ii: 250 mA *1:
Transmitter is made of aluminum, if it is mounted Maximum Input Power Pi: 1.2 W
Rating 1
in an area where the use of category 2D Maximum Internal Capacitance Ci: 3.52 nF
apparatus is required, it shall be installed in such Maximum Internal Inductance Li: 0 μH
a way that the risk from electrostatic discharges or
and propagating brush discharges caused by Maximum Input Voltage Ui: 17.5 V
rapid flow of dust is avoided. Maximum Input Current Ii: 380 mA
• To satisfy IP66 or IP67, apply waterproof glands Maximum Input Power Pi: 5.32 W
to the electrical connection port. Maximum Internal Capacitance Ci: 3.52 nF
• When the lightning protector option is specified, Maximum Internal Inductance Li: 0 μH *2:
the apparatus is not capable of withstanding the or
Rating 2
500V insulation test required by EN60079-11. Maximum Input Voltage Ui: 17.5 V
This must be taken into account when Maximum Input Current Ii: 460 mA
installing the apparatus. Maximum Input Power Pi: 5.32 W
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH

IM
01C25A01-
01E
<2. Handling Cautions>
19
c. ATEX Intrinsically Safe for Fieldbus Note 4. Maintenance and Repair
Type for EJX90A • The instrument modification or parts replacement
by other than authorized representative of
Caution for ATEX Intrinsically safe type.
Yokogawa Electric Corporation is prohibited and
Note 1. EJX multivariable transmitter with optional will void DEKRA Intrinsically safe Certification.
code /KS26 are applicable for use in
Note 5. Special Conditions for Safe Use
hazardous locations:
• No. KEMA 06ATEX0278 X
• Applicable Standard:
EN 60079-0:2012+A11:2013
WARNING
EN 60079-11:2012 • In the case where the enclosure of the Pressure
Transmitter is made of aluminium, if it is mounted in
Note 2. Ratings an area where the use of category 1G apparatus is
Type of Protection and Marking Code: required, it must be installed such, that even in the
Ex ia IIC/IIB T4 Ga event of rare incidents, ignition sources due to
Ex ia IIIC T85°C T100°C T120°C Db impact and friction sparks are excluded.
Group: II • Electrostatic charge may cause an explosion
Category: 1G, 2D hazard. Avoid any actions that cause the
Ambient Temperature for EPL Ga: generation of electrostatic charge, such as rubbing
–40 to 60°C with a dry cloth on coating face of the product.
Ambient Temperature for EPL Db:
• In the case where the enclosure of the Pressure
–30* to 60°C
* –15°C when /HE is specified.
Transmitter is made of aluminum, if it is
Maximum Process Temperature (Tp.): 120°C mounted in an area where the use of category
Maximum Surface Temperature for EPL Db. 2D apparatus is required, it shall be installed in
such a way that the risk from electrostatic
T85°C (Tp.: 80°C)
discharges and propagating brush discharges
T100°C (Tp.: 100°C)
caused by rapid flow of dust is avoided.
T120°C (Tp.: 120°C)
• To satisfy IP66 or IP67, apply waterproof glands
Ambient Humidity:
to the electrical connection port.
0 to 100% (No condensation)
• When the lightning protector option is specified,
Degree of Protection of the Enclosure:
the apparatus is not capable of withstanding the
IP66/IP67
500V insulation test required by EN60079-11.
Electrical Data
This must be taken into account when
• When combined with Trapezoidal or Rectanglar
output characteristic FISCO model IIC barrier installing the apparatus.
[Supply circuit (terminals + and -)]
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32
Note 6. Installation instructions
W, Ci = 3.52 nF, Li = 0 µH
[Installation Diagram]
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008
W, Co = 4.8 µF, Lo = 100 mH Terminator RTD
• When combined with Linear characteristic Pt100.3wire
barrier [Supply circuit (terminals + and -)] + Pressure
Ui = 24 V, Ii = 250 mA, Pi = 1.2 − SUPPLY Transmitter
W, Ci = 3.52 nF, Li = 0 µH + Transmitter
[Sensor circuit] −
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 + Transmitter
W, Co = 4.8 µF, Lo = 100 mH
• When combined with Trapezoidal or Rectanglar

output characteristic FISCO model IIB barrier
[Supply circuit (terminals + and -)]
Hazardous Location
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32
W, Ci = 3.52 nF, Li = 0 µH Non-Hazardous Location
[Sensor circuit] Terminator
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008
W, Co = 4.8 µF, Lo = 100 mH + −
Safety Barrier
Note 3. Installation + − F0232.ai

• All wiring shall comply with local installation


requirements. (Refer to the installation diagram)

IM
01C25A01-
01E
<2. Handling Cautions>
20
• In the rating 1(*1), the output current of the barrier • Category: 2G, 2D
must be limited by a resistor ‘Ra’ such that Io = Uo/ • Enclosure: IP66 / IP67
Ra. • Temperature Class for gas-
• In the rating 2(*2), the output of the barrier must poof: T6, T5, and T4
be the characteristics of the trapezoid or the • Ambient Temperature for gas-proof: –
rectangle and this transmitter can be connected 50 to 75°C (T6), –50 to 80°C (T5),
to Fieldbus equipment which are in according to and –50 to 75°C (T4)
the FISCO model. • Process Temperature (Tp.) for gas-
• The terminators may be built in by a barrier. proof: –50 to 85°C (T6), –50 to 100°C
• More than one transmitter may be connected (T5), and –50 to 120°C (T4)
to the power supply line. • Maximum Surface Temperature for dust-proof:
• The terminator and the safety barrier shall T85°C (Tamb.: –30* to 75°C, Tp.: –30* to 85°C)
be certified. * –15°C when /HE is specified.
Electrical data: Note 2. Electrical Data
Supply circuit • Supply voltage: 42 V dc max.
Maximum Input Voltage Ui: 24 V 32 V dc max. (FOUNDATION Fieldbus
Maximum Input Current Ii: 250 mA *1: and PROFIBUS PA type)
Maximum Input Power Pi: 1.2 W 9 to 28 V dc, 27 mW (Low Power type)
Rating 1
Maximum Internal Capacitance Ci: 3.52 nF 9 to 30 V dc, 250 mW (RS485
Maximum Internal Inductance Li: 0 μH Modbus Communication Type)
or • Output signal: 4 to 20 mA
Maximum Input Voltage Ui: 17.5 V 15 mA (FOUNDATION Fieldbus and PROFIBUS
Maximum Input Current Ii: 380 mA PA type)
Maximum Input Power Pi: 5.32 W 1 to 5 V (Low Power type)
Maximum Internal Capacitance Ci: 3.52 nF RS485 Modbus (RS485 Modbus Communication
Maximum Internal Inductance Li: 0 μH *2: Type)
or
Rating 2 Note 3. Installation
Maximum Input Voltage Ui: 17.5 V
• All wiring shall comply with local
Maximum Input Current Ii: 460 mA
installation requirement.
Maximum Input Power Pi: 5.32 W • Cable glands, adapters and/or blanking
Maximum Internal Capacitance Ci: 3.52 nF elements with a suitable IP rating shall be of Ex
Maximum Internal Inductance Li: 0 μH d IIC/Ex tb IIIC certified by ATEX and shall be
Sensor circuit installed so as to maintain the specific degree
of protection (IP Code) of the equipment.
Maximum Output Voltage Uo: 7.63 V • Wiring connection for output signal code Q (Low
Maximum Output Current Io: 3.85 mA Power type) shall follow the diagram below.
Maximum Output Power Po: 0.008 W
Pressure Transmitters
Maximum Internal Capacitance Co: 4.8 μF
SUPPLY+
Maximum Internal Inductance Lo: 100 mH Voltmeter
A Power Supply

• RTD sensor is prepared by the user. + +


The sensor signal line must suited a test voltage of – –
500Vac.
SUPPLY–
d. ATEX Flameproof Type
Three-Wire Connection
Caution for ATEX flameproof type. Pressure Transmitters
Note 1. EJX/EJA-E Series pressure transmitters SUPPLY+
with optional code /KF22 or /V1F are Voltmeter
A Power Supply
applicable for use in hazardous locations.
• No. KEMA 07ATEX0109 X + +
• Applicable Standard: – –
EN 60079-0:2012+A11:2013
SUPPLY–
EN 60079-1:2007, EN60079-31:2014
• Type of Protection and Marking Code: Ex Four-Wire Connection F0220.ai

d IIC T6...T4 Gb, Ex tb IIIC T85°C Db


• Group: II

IM 01C25A01-01E
<2. Handling Cautions>
21
Note 4. Operation  ATEX Intrinsically Safe Ex ic
• Keep the “WARNING” label attached to
Caution for ATEX intrinsically safe Ex ic
the transmitter.
WARNING: AFTER DE-ENERGIZING, DELAY 5
• Applicable Standard:
EN 60079-0:2012+A11:2013
MINUTES BEFORE OPENING. WHEN THE
EN 60079-11:2012
AMBIENT TEMP.≥65°C, USE HEAT-RESISTING
CABLE AND CABLE GLAND ≥90°C.
• Type of Protection and Marking
• Take care not to generate mechanical sparking Code: II 3G Ex ic IIC T4 Gc
• Ambient Temperature: –30* to +60°C
when accessing to the instrument and peripheral * –15°C when /HE is specified.
devices in a hazardous location. • Ambient Humidity:
Note 5. Specific Conditions of Use 0 to 100% (No condensation)
• Maximum Process Temperature: 120°C
• IP Code: IP66
WARNING • Ambient pollution degree: 2
• Overvoltage category: I
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the Note 1. Electrical Data
generation of electrostatic charge, such as rubbing Ui = 30 V
with a dry cloth on coating face of the product. Ci = 27.6 nF
• In the case where the enclosure of the Pressure Li = 0 µH
Transmitter is made of aluminium, if it is mounted in
Note 2. Installation
an area where the use of category 2D apparatus is • All wiring shall comply with local installation
required, it shall be installed in such a way requirements. (refer to the control drawing)
that the risk from electrostatic discharges • Cable glands, adapters and/or blanking elements
and propagating brush discharges caused shall be of Ex “n”, Ex “e” or Ex “d” and shall be
by rapid flow of dust is avoided.
installed so as to maintain the specified degree of
• The instrument modification or parts replacement
protection (IP Code) of the transmitters.
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and Note 3. Maintenance and Repair
will void the certification. • The instrument modification or parts replacement
• The fasteners used to fasten the transmitter by other than authorized representative of
enclosure onto the sensor capsule is special Yokogawa Electric Corporation is prohibited and
fastener, and the property class of it is A2- will void ATEX intrinsically safe.
50(A4-50) or more. [Control Drawing]

Hazardous Area Nonhazardous Area


Pressure + Associated
e. ATEX Intrinsically Safe and ATEX
Flameproof Combination for HART/BRAIN
Transmitters – Apparatus
Protocol Type (Except for EJX90A)
EJX/EJA-E Series pressure transmitters with
optional code /KU22 or /V1U1 can be selected the
type of protection ATEX Flameproof, Intrinsically F0212.ai

Safe. Ex ia, or Ex ic for use in hazardous area.


Note 4. Specific Conditions of Use
Note 1. For the installation of this transmitter, once
a particular type of protection is selected,
any other type of protection cannot be WARNING
used. The installation must be in
• Electrostatic charge may cause an explosion
accordance with the description about the
hazard. Avoid any actions that cause the
type of protection in this user’s manual.
generation of electrostatic charge, such as rubbing
Note 2. For combined approval types with a dry cloth on coating face of the product.
Once a device of multiple approval type is • When the lightning protector option is specified,
installed, it should not be re-installed using any the apparatus is not capable of withstanding the
other approval types. Apply a permanent mark 500V insulation test required by EN60079-11.
in the check box of the selected approval type This must be taken into account when installing
on the certification label on the transmitter to the apparatus.
distinguish it from unused approval types.

IM 01C25A01-01E
<2. Handling Cautions>
22
f. ATEX Intrinsically Safe Ex ic for Note 4. Specific Conditions of Use
Fieldbus Type (Except for EJX90A)
Caution for ATEX Intrinsically safe Ex ic. EJX/EJA-
E Series pressure transmitters with optional
WARNING
code /KN26 are applicable for use in hazardous • Electrostatic charge may cause an explosion
locations. hazard. Avoid any actions that cause the
• Applicable Standard: gerenation of eletrostatic charge, such as rubbing
EN 60079-0:2012+A11:2013 with a dry cloth on coating face of the product.
EN 60079-11:2012 • When the lightning protector option is specified,
• Type of Protection and Marking the apparatus is not capable of withstanding the
Code: II 3G Ex ic IIC T4 Gc 500V insulation test required by EN60079-11.
• Ambient Temperature: –30* to +60°C This must be taken into account when installing
* –15°C when /HE is specified. the apparatus.
• Maximum Process Temperature: 120°C
• Ambient Humidity:
0 to 100% (No condensation) (2) Electrical Connection
• IP Code: IP66
A mark indicating the electrical connection type
• Ambient pollution degree: 2
is stamped near the electrical connection port.
• Overvoltage category: I
These marks are as followed.
Note 1. Electrical Data
Screw Size Marking
Ui = 32 V
ISO M20 × 1.5 female M
Ci = 3.52 nF
Li = 0 µH ANSI 1/2 NPT female N or W

Note 2. Installation
• All wiring shall comply with local installation
requirements. (refer to the control drawing)
• When installing the transmitter in “ic” FISCO
system or FNICO system, follow the
installation requirements of each system. Location of the mark
• Cable glands, adapters and/or blanking elements
F0214.ai
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
installed so as to maintain the specified degree of (3) Installation
protection (IP Code) of the transmitters.
Note 3. Maintenance and Repair
• The instrument modification or parts replacement WARNING
by other than authorized representative of • All wiring shall comply with local installation
Yokogawa Electric Corporation is prohibited and requirements and the local electrical code.
will void ATEX intrinsically safe. • There is no need for conduit seal in Division 1
[Control Drawing] and Division 2 hazardous locations because
Hazardous Area Nonhazardous Area this product is sealed at the factory.
+ Associated

Transmitter –
Apparatus
(4) Operation

WARNING
F0233.ai
• OPEN CIRCUIT BEFORE REMOVING
• Above drawing shows the installation of COVER. INSTALL IN ACCORDANCE WITH
Entity system. THIS USER’S MANUAL
When installing the transmitters in “ic” FISCO • Take care not to generate mechanical
system or FNICO system, follow the sparking when access to the instrument and
installation requirements of each system. peripheral devices in a hazardous location.
IM
01C25A01-
01E
<2. Handling Cautions>
23
(5) Maintenance and Repair  Tag plate for intrinsically safe Ex ia for Fieldbus
No. KEMA 04ATEX1116 X
Ex ia IIC/IIB T4 Ga Ta:-40 to 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) to 60°C
MAX PROCESS TEMP.(Tp.):120°C

WARNING
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Enclosure: IP66/IP67
FISCO field device(IIC/IIB)
Entity parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0μH

The instrument modification or parts replacement


by other than an authorized Representative of *3 D
Yokogawa Electric Corporation is prohibited and WARNING

will void the certification.


POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

 Tag plate for intrinsically safe Ex ic for Fieldbus


(6) Name Plate Ex ic IIC T4 Gc
IP66
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C

 Name plate Ui=32V, Ci=3.52nF, Li=0µH

WARNING

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

[EJX90A]
 Tag plate for flameproof type No. KEMA 07ATEX0109 X
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Enlcosure : IP66/IP67 T6 T5 T4
 Tag plate for intrinsically safe Ex ia for Fieldbus
TEMP. CLASS -50 TO °C
PROCESS TEMP.(Tp.) 85 100 120 No. KEMA 06ATEX0278 X
Tamb. (for GAS) -50 TO 75 80 75 °C Ex ia IIC/IIB T4 Ga Ta: -40 to 60°C
T85°C(Tamb.: -30(-15) TO 75°C, Tp.:-30(-15) TO 85°C)(for Dust) Ex ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°C
MAX PROCESS TEMP.(Tp.): 120°C
T85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C)
ENCLOSURE: IP66/IP67
Supply circuit
FISCO field device(IIC/IIB)
*3 D Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH
Sensor circuit
Uo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH
WARNING

AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE *3


OPENING.
WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE
HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C
POTENTIAL ELECTROSTATIC CHARGING HAZARD -SEE THE USER’S MANUAL

F0215-1.ai POTENTIAL ELECTROSTATIC CHARGING HAZARD-SEE USER'S MANUAL.

F0215-3.ai
[Except for EJX90A]
 Tag plate for intrinsically safe Ex ia for HART/BRAIN MODEL: Specified model code.
No. DEKRA 11ATEX 0228 X
STYLE: Style code.
Ex ia IIC T4 Ga Ta: -50 TO 60°C SUFFIX: Specified suffix code.
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
IP66/IP67 120°C
MAX. PROCESS TEMP.(Tp.)
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C) SUPPLY: Supply voltage.
Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
OUTPUT: Output signal.
MWP: Maximum working pressure.
*3 D
WARNING
CAL RNG: Specified calibration range.
NO.: Serial number and year of production*1.
POTENTIAL ELECTROSTATIC
TOKYO 180-8750 JAPAN:
CHARGING HAZARD
- SEE USER’S MANUAL The manufacturer name and the address*2.
 Tag plate for intrinsically safe Ex ic for HART/BRAIN *1: The first number in the second block of “NO.” column
Ex ic IIC T4 Gc
IP66 is the last one number of the production year.
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=30V, Ci=27.6nF, Li=0µH

second block
WARNING

NO. 91K819857 132 7


POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL The year 2011
F0215-2.ai
*2: “180-8750” is a zip code which represents
the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identification number of Notified Body.
IM
01C25A01-
01E
<2. Handling Cautions>
24
2.4.4 IECEx Certification Note 3. Installation
• In any safety barrier used output current must
Model EJX Series pressure transmitters with
be limited by a resistor ‘R’ such that Io=Uz/R.
optional code /SU21 can be selected the type of
• The safety barrier must be IECEx certified.
protection (IECEx Intrinsically Safe Ex ia, Ex ic or
• Input voltage of the safety barrier must be
flameproof) for use in hazardous locations.
EJX Series pressure transmitters with optional less than 250 Vrms/Vdc.
code /SS26 can be selected the type of protection • The instrument modification or parts replacement
(IECEx intrinsically safe Ex ia or Ex ic) for use in by other than authorized representative of
hazardous locations. Yokogawa Electric Corporation is prohibited and
EJX Series pressure transmitters with will void IECEx certification.
optional code /SU2 can be selected the type of [Ex ia]
protection (IECEx Intrinsically Safe/type n or Hazardous Location Nonhazardous Location
flameproof) for use in hazardous locations. Group IIC, Zone 0
Note 1. For the installation of this transmitter, once EJX/EJA-E Series IECEx certified
a particular type of protection is selected, Pressure Transmitters Safety Barrier
any other type of protection cannot be + +
used. The installation must be in Supply – –
accordance with the description about the
type of protection in this instruction manual.
Note 2. For combined approval types, once a device of (*1)
*1: When using non isolation barrier,
multiple approval type is installed, it should connect (*1) to IS barrier system. F0236.ai

not be re-installed using any other approval


types. Apply a permanent mark in the check Note 4. Specific Condition of Use
box of the selected approval type on the
certification label on the transmitter to
distinguish it from unused approval types. WARNING
a. IECEx Intrinsically Safe Ex ia for HART/ • Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
BRAIN Protocol Type (Except for EJX90A)
generation of electrostatic charge, such as rubbing
Caution for IECEx Intrinsically safe Ex ia. with a dry cloth on coating face of the product.
Note 1. EJX/EJA-E series pressure transmitters • When the enclosure of the pressure transmitter
with optional code /SU21 are applicable for is made of aluminum, if it is mounted in an area
use in hazardous locations where the use of EPL Ga equipment is
• No. IECEx DEK 11.0081X required, it must be installed such, that, even in
• Applicable Standard: IEC 60079- the event of rare incidents, ignition sources due
0:2011, IEC 60079-11:2011 to impact and friction sparks are excluded.
• Ex ia IIC T4 Ga • Electrostatic charges on the coated parts
• Ambient Temperature: –50 to 60°C of Pressure Transmitter shall be avoided.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
To satisfy IP66 or IP67, apply waterproof glands b. IECEx Intrinsically Safe Ex ic for HART/
to the electrical connection port. BRAIN Protocol Type (Except for EJX90A)
Note 2. Electrical Data Caution for IECEx Intrinsically safe Ex ic.
Maximum Input Voltage (Ui) = 30 V Note 1. EJX/EJA-E series pressure transmitters
Maximum Input Current (Ii) = 200 mA with optional code /SU21 are applicable for
Maximum Input Power (Pi) = 0.9 W (linear source)
use in hazardous locations
Maximum Internal Capacitance (Ci) = 27.6 nF • No. IECEx DEK 13.0061X
Maximum Internal Inductance (Li) = 0 μH • Applicable Standard: IEC 60079-
When the lightning protector option is specified, the 0:2011, IEC 60079-11:2011
apparatus is not capable of withstanding the 500V • Ex ic IIC T4 Gc
insulation test required by IEC60079-11. This must be • Ambient Temperature: –30* to 60°C
* -15 °C when /HE is specified.
taken into account when installing the apparatus.
• Max. Process Temp.: 120°C
• IP Code: IP66
• Overvoltage Category: I
IM
01C25A01-
01E
<2. Handling Cautions>
25
Note 2. Electrical Data Note 2. Electrical Data
Maximum Input Voltage (Ui) = 30 V Maximum • Intrinsically safe ratings are as
Internal Capacitance (Ci) = 27.6 nF Maximum follows: [Entity]
Internal Inductance (Li) = 0 μH Maximum Input Voltage (Ui) = 24 V Maximum
Input Current (Ii) = 250 mA Maximum Input
Note 3. Installation
Power (Pi) = 1.2 W Maximum Internal
• The pressure transmitter is allowed to be
Capacitance (Ci) = 3.52 nF Maximum Internal
installed in “nL” systems, on condition that the
Inductance (Li) = 0 μH
output parameters of “nL” source (associated
[FISCO IIC]
energy-limited apparatus) are suitable to the
Maximum Input Voltage (Ui) = 17.5 V
above mentioned input parameters of the
Maximum Input Current (Ii) = 380 mA
pressure transmitter and the cable parameters.
Maximum Input Power (Pi) = 5.32 W
• Cable glands, adapters and/or blanking elements
Maximum Internal Capacitance (Ci) = 3.52 nF
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
Maximum Internal Inductance (Li) = 0 μH
installed so as to maintain the specified degree of
[FISCO IIB]
protection of the equipment.
Maximum Input Voltage (Ui) = 17.5 V
• The instrument modification or parts replacement
Maximum Input Current (Ii) = 460 mA
by other than authorized representative of
Maximum Input Power (Pi) = 5.32 W
Yokogawa Electric Corporation is prohibited and
Maximum Internal Capacitance (Ci) = 3.52 nF
will void IECEx certification.
Maximum Internal Inductance (Li) = 0 μH
[Ex ic]
Hazardous Location Nonhazardous Location Note 3. Installation
[Ex ia]
EJX/EJA-E Series Associated apparatus
Pressure Transmitters Terminator
Supply + +

– – + Pressure
– Transmitter

F0237.ai +
– Field Instruments
Note 4. Specific Condition of Use
+
– Field Instruments
WARNING
• Electrostatic charge may cause an explosion
Hazardous Location
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing Non-Hazardous Location
Terminator
with a dry cloth on coating face of the product.
• The apparatus is not capable of dielectric strength + –
tests required by IEC 60079-11. Safety Barrier
F0238.ai
This must be taken into account when + –
installing the apparatus.
• In the rating 1(*1), the output current of the barrier
must be limited by a resistor ‘Ra’ such that Io = Uo/
c. IECEx Intrinsically Safe Ex ia for Fieldbus Ra.
Type (Except for EJX90A) • In the rating 2(*2), the output of the barrier must
Caution for IECEx Intrinsically safe Ex ia. be the characteristics of the trapezoid or the
rectangle and this transmitter can be connected
Note 1. EJX/EJA-E Series pressure transmitters to Fieldbus equipment which are in according to
with optional code /SS26 are applicable for the FISCO model.
use in hazardous locations. • The terminators may be built in by a barrier.
• No. IECEx DEK 12.0016X • More than one transmitter may be connected
• Applicable Standard: IEC 60079-0:2011, to the power supply line.
IEC 60079-11:2011, IEC 60079-26: 2006 • The terminator and the safety barrier shall
• Ex ia IIC/IIB T4 Ga be certified.
• Ambient Temperature: –40 to 60°C
• Max. Process Temp.: 120°C
IM
01C25A01-
01E
<2. Handling Cautions>
26
Electrical data: Note 2. Electrical Data
Maximum Input Voltage Ui: 24 V • Intrinsically safe ratings are as follows:
Maximum Input Current Ii: 250 mA *1: Maximum Input Voltage (Ui) = 32 V Maximum
Maximum Input Power Pi: 1.2 W Internal Capacitance (Ci) = 3.52 nF Maximum
Rating 1
Maximum Internal Capacitance Ci: 3.52 nF Internal Inductance (Li) = 0 μH
Maximum Internal Inductance Li: 0 μH Note 3. Installation
or • The instrument modification or parts replacement
Maximum Input Voltage Ui: 17.5 V by other than authorized representative of
Maximum Input Current Ii: 380 mA Yokogawa Electric Corporation and will void IECEx
Maximum Input Power Pi: 5.32 W Intrinsically safe and type n certification.
Maximum Internal Capacitance Ci: 3.52 nF • The pressure transmitter is allowed to be
Maximum Internal Inductance Li: 0 μH *2: installed in “nL” systems, on condition that the
or output parameters of “nL” source (associated
Rating 2
Maximum Input Voltage Ui: 17.5 V energy-limited apparatus) are suitable to the
Maximum Input Current Ii: 460 mA above mentioned input parameters of the
Maximum Input Power Pi: 5.32 W pressure transmitter and the cable parameters.
Maximum Internal Capacitance Ci: 3.52 nF • When installing the transmitter in “ic” FISCO
Maximum Internal Inductance Li: 0 μH system or FNICO system, follow the
Note 4. Specific Condition of Use installation requirements of each system.
• Cable glands, adapters and/or blanking elements
WARNING shall be of Ex “n”, Ex “e” or Ex “d” and shall be
installed so as to maintain the specified degree of
protection of the equipment.
• Electrostatic charge may cause an explosion • For multiple types of protection, the selected
hazard. Avoid any actions that cause the Ex marking on the marking plate shall be
generation of electrostatic charge, such as rubbing checked at the time of installation.
with a dry cloth on coating face of the product. [Ex ic]
• In the case where the enclosure of the pressure
Hazardous Location Nonhazardous Location
transmitter is made of aluminum, if it is mounted in
an area where the use of EPL Ga equipment is EJX/EJA-E Series Associated apparatus
required, it shall be installed in such a way that , Pressure Transmitters
even in the event of rare incidents, ignition sources Supply + +
due to impact and friction sparks are excluded. – –
• When the lightning protector option is specified,
the apparatus is not capable of withstanding the
F0237.ai
500 V insulation test required by IEC 60079-11.
This must be taken into account when installing • Above drawing shows the installation of entity
the apparatus. system. When installing the transmitter in “ic”
FISCO system or FNICO system, follow the
installation requirements of each system.
d. IECEx Intrinsically Safe Ex ic for
Note 4. Specific Condition of Use
Fieldbus Type (Except for EJX90A)
Caution for IECEx Intrinsically safe Ex ic.
WARNING
Note 1. EJX/EJA-E Series pressure transmitters • Electrostatic charge may cause an explosion
with optional code /SS26 are applicable for hazard. Avoid any actions that cause the
use in hazardous locations. generation of electrostatic charge, such as rubbing
• No. IECEx DEK 13.0064X with a dry cloth on coating face of the product.
• Applicable Standard: IEC 60079- • When the lightning protector option is specified,
0:2011, IEC 60079-11:2011
the apparatus is not capable of withstanding the
• Ex ic IIC T4 Gc
500 V insulation test required by IEC 60079-11.
• Ambient Temperature: –30* to 60°C
* -15 °C when /HE is specified. This must be taken into account when installing
• Max. Process Temp.: 120°C the apparatus.
• IP Code: IP66
• Overvoltage Category: I
IM
01C25A01-
01E
<2. Handling Cautions>
27
e. IECEx Flameproof Type Note 3. Operation
• WARNING:
Caution for IECEx flameproof type.
AFTER DE-ENERGIZING, DELAY 5
Note 1. EJX/EJA-E Series pressure transmitters MINUTES BEFORE OPENING.
with optional code /SF2 or /SU21 are • WARNING:
applicable for use in hazardous locations: WHEN THE AMBIENT TEMP.≥65°C, USE HEAT-
• No. IECEx CSA 07.0008 RESISTING CABLE AND CABLE GLAND ≥90°C.
• Applicable Standard: IEC60079- • Take care not to generate mechanical sparking
0:2011, IEC60079-1:2007-4 when accessing to the instrument and peripheral
• Flameproof for Zone 1, Ex d IIC T6...T4 Gb devices in a hazardous location.
• Enclosure: IP66/IP67 • Electrostatic charge may cause an explosion
• Maximum Process Temperature: 120°C hazard. Avoid any actions that cause the
(T4), 100°C (T5), 85°C (T6) generation of electrostatic charge, such as rubbing
• Ambient Temperature: –50 to 75°C (T4), with a dry cloth on coating face of the product.
–50 to 80°C (T5), –50 to 75°C (T6)
Note 4. Maintenance and Repair
• Supply Voltage: 42 V dc max.
• The instrument modification or parts replacement
32 V dc max. (FOUNDATION Fieldbus
by other than authorized representative of
and PROFIBUS PA type)
Yokogawa Electric Corporation is prohibited and
9 to 28 V dc, 27 mW (Low Power type)
will void IECEx Certification.
9 to 30 V dc, 250 mW (RS485
• Electrical Connection
Modbus Communication Type)
A mark indicating the electrical connection type
• Output Signal: 4 to 20 mA dc
is stamped near the electrical connection port.
15 mA (FOUNDATION Fieldbus and PROFIBUS
PA type) These marks are as followed.
1 to 5 V (Low Power type) Screw Size Marking
RS485 Modbus (RS485 Modbus Communication ISO M20 × 1.5 female M
Type)
ANSI 1/2 NPT female N or W
Note 2. Wiring
• In hazardous locations, the cable entry devices
shall be of a certified flameproof type, suitable
for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable
flameproof certified blanking elements. Location of the mark
• Wiring connection for output signal code Q (Low
Power type) shall follow the diagram below. F0222.ai
Pressure Transmitters
SUPPLY+ Voltmeter
A 2.5 EMC Conformity Standards
Power Supply
+ EN 61326-1 Class A, Table 2 (for use in
+
– industrial locations)
– EN 61326-2-3
SUPPLY– EN 61326-2-5 (for Fieldbus)

Three-Wire Connection
Pressure Transmitters CAUTION
SUPPLY+ Voltmeter To meet EMC regulations, Yokogawa recommends
A that customers run signal wiring through metal
Power Supply
+ conduits or use shielded twisted-pair cabling when
+
– installing EJX/EJA-E Series transmitters in a plant.

SUPPLY–

Four-Wire Connection
F0221.ai

IM
01C25A01-
01E
<2. Handling Cautions>
28

2.6 Pressure Model Capsule PS*


1
V(L) PS.V Category*
2
code (bar) (bar.L)
Equipment EJ510 A,B,C 100 0.1 10 Article 4,
Directive (PED) EJX610A D 700 0.1 70
Paragraph 3
(SEP)
EJ510,
(1) General EJX610A D 700 0.1 70 III
with code /
• EJX/EJA-E Series pressure transmitters are PE3
categorized as piping under the pressure accessories EJ530, A,B,C 100 0.1 10 Article 4,
section of directive 2014/68/EU, which corresponds to EJX630A Paragraph 3
D 700 0.1 70 (SEP)
Article 4, Paragraph 3 of PED, denoted as Sound
Engineering Practice (SEP). EJ530,
EJX630A D 700 0.1 70 III
• EJX110A-MS, EJX110A-HS, EJX110A-VS, with code /
EJA110E with /HG, EJ130, EJ440, PE3
EJ510-D, EJ530-D, EJX610A-D, L 160 0.01 1.6 Article 4,
and EJX630A-D can be used above 200 bar and EJX910A Paragraph 3
M, H 250 0.01 2.5 (SEP)
therefore considered as a part of a pressure
EJX910A
retaining vessel where category III, Module H
with code / M, H 250 0.01 2.5 III
applies. These models with option code /PE3 PE3
conform to that category. Article 4,
EJX930A M, H 500 0.01 5.0 Paragraph 3
(2) Technical Data (SEP)
• Models without /PE3 EJX930A
with code / M, H 500 0.01 5.0 III
Article 4, Paragraph 3 of PED, denoted as Sound PE3
Engineering Practice (SEP).
*1: PS is maximum pressure for vessel itself based on
• Models with Pressure Equipment Directive 2014/68/EU. Refer to
/PE3 Module: H General Specification for maximum working pressure
Type of Equipment: Pressure Accessory-Vessel of a transmitter.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
Type of fluid: Liquid and Gas
on Pressure Equipment Directive 2014/68/EU.
Group of fluid: 1 and 2
1 (3) Operation
Model Capsule PS* V(L) PS.V 2
Category*
code (bar) (bar.L)
EJA110E M,H,V 160 0.01 1.6
CAUTION
EJ110 F, L Article 4,
• The temperature and pressure of fluid
EJX110A Paragraph 3 should be maintained at levels that are
(SEP)
EJA110E M,H,V 250 0.01 2.5 consistent with normal operating conditions.
with code • The ambient temperature should be
/HG
maintained at a level that is consistent with
EJ110 M,H,V 250 0.01 2.5 III
with code / normal operating conditions.
PE3 • Please take care to prevent water hammer and the
Article 4, like from inducing excessive pressures in pipes and
EJ130 M, H 500 0.01 5.0 Paragraph 3 valves. If phenomena are likely, install a safety
(SEP)
valve or take some other appropriate measure to
EJ130 M, H 500 0.01 5.0 III
with code /
prevent pressure from exceeding PS.
PE3 • Take appropriate measures at the device or
Article 4, system level to protect transmitters if they are to
EJ310 L,M,A,B 160 0.01 1.6 Paragraph 3 be operated near an external heat source.
(SEP)
Article 4,
EJ430 H,A,B 160 0.01 1.6 Paragraph 3
(SEP)
Article 4,
EJ440 C, D 500 0.1 5.0 Paragraph 3
(SEP)
EJ440 C, D 500 0.1 5.0 III
with code /
PE3
IM
01C25A01-
01E
<2. Handling Cautions>
29
2.7 Safety Requirement
Standards
Applicable standard: EN 61010-1, EN 61010-2-30,
C22.2 No.61010-1, C22.2 No.61010-2-030

(1) Pollution Degree 2


"Pollution degree" describes the degree to which
a solid, liquid, or gas which deteriorates dielectric
strength or surface resistivity is adhering. " 2 " applies
to normal indoor atmosphere. Normally, only non-
conductive pollution occurs. Occasionally, however,
temporary conductivity caused by condensation must
be expected.

(2) Installation Category I


"Overvoltage category(Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation for
impulse withstand voltage. " I " applies to electrical
equipment which is supplied from the circuit when
appropriate transient overvoltage control means
(interfaces) are provided.

(3) Altitude of installation site:


Max. 2,000 m above sea level

(4) Indoor/Outdoor use


IM
01C25A01-
01E
<3. Installation>
30

3. Installation
Vertical pipe mounting Vertical pipe mounting
IMPORTANT (Process connector upside) (Process connector downside)

• When welding piping during construction, take


care not to allow welding currents to flow Mounting
through the transmitter. bracket
• Do not step on this instrument after installation. 50 mm
(2-inch) pipe
• For EJ430, EJ440 and EJ438, the
atmospheric opening is located on the low U-bolt nut
U-bolt
pressure side cover flange. For EJ530 and
EJX630A whose capsule code is A, B, or C,
the pipe of the atmospheric opening is located Transmitter
on the pressure detecting section. These mounting bolt
F0303.ai
openings must not face upward.
Figure 3.3 Transmitter Mounting
(Vertical Impulse Piping Type)

Vertical pipe mounting Horizontal pipe mounting


Pipe Zero-adjustment screw 50 mm
(backside of the instrument)
  Capsule code U-bolt nut (L) (2-inch) pipe

6  F00301.ai

Figure 3.1 EJ530 and EJX630A Horizontal


Mounting Position
U-bolt
nut (S) U-bolt (L)
Mounting
3.1 Mounting bracket U-bolt (S) F0304.ai

■ The transmitter can be mounted on a nominal


Figure 3.4 EJ510 and EJ530
50 mm (2-inch) pipe using the mounting bracket Mounting
supplied, as shown in Figure 3.2 and 3.3. Tighten
the (four) bolts that hold the transmitter with a
torque of approximately 39 N·m {4 kgf·m}.
3.2 Mounting the Diaphragm Seals

Transmitter IMPORTANT
mounting bolt
• Please use a gasket with an inside diameter (ød)
that is greater than the diameter of the diaphragm
seal. If a gasket with a smaller inside diameter is
used, the diaphragm may not function correctly.
U-bolt nut
• During the diaphragm seal installation, ensure
Mounting bracket U-bolt as far as possible that no seal liquid head
F0302.ai
pressure is applied to the diaphragm seals.
50 mm(2-inch) pipe
• Exercise care so as not to damage diaphragm
Figure 3.2 Transmitter Mounting (Horizontal surfaces. Since the diaphragm protrudes approx.
Impulse Piping Type) 1 mm from the flange surface, do not place the
pressure detector section face down on a
surface as this can damage the diaphragm.
• Do not sharply bend or twist capillary tube or
apply excessive stress to them.
• Never loosen the four bolts securing the cover
flange or the screws at the joints between the
capillary tube and cover flanges. If the seal
liquid leaks, the transmitter cannot be used.

IM 01C25A01-01E
<3. Installation>
31
3.2.1 EJ210 3.3 Diaphragm Seals
The transmitter is mounted on a process using its high Installation Consideration
pressure side flange as shown in Figure 3.5. The
customer should prepare the mating flange, gasket,
stud bolts and nuts.
IMPORTANT
• When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
Gasket level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.7).
• Correctly install the diaphragm seals on the
high and low pressure sides of the process,
checking the label on each seal.
• To avoid measuring error duets temperature
Stud bolt difference between the two diaphragm seals,
Nut F0305.ai capillary tube must be bound together. The
Figure 3.5 EJ210 Mounting capillary tube must be securely fixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
3.2.2 EJ118 and EJ438 extra tube portion (coil diameter of 300 mm or
Mount the diaphragm seals using the flanges as shown more) and secure the coiled tube with a clamp.
in Figure 3.6. The mating flange, gasket, bolts and nuts
Low
are to be procured by the customer.
IMPORTANT pressure
Flange side
Diaphragm Nut
Bolt Install the sealed diaphragm
so that the shank positions
downward.

ød Minimum
High liquid level
Gasket
pressure
The product is
side 50 mm minimum
shipped with these Correctly install the diaphragm
parts assembled. seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW).
F0306.ai The transmitter should
be installed as low as
Figure 3.6 Mounting the Diaphragm Seals
possible below the
position where the high
pressure side
diaphragm seal is
installed.
F0307.ai

Figure 3.7 Installing the Diaphragm Seals to a


Tank
IM
01C25A01-
01E
<3. Installation>
32

Low pressure side


IMPORTANT
The transmitter should be installed at least 600 mm below
the high pressure (HP) process connection to ensure a P
positive head pressure of fill fluid. Pay special attention to h

High
vacuum applications. pressure
(+) side
If it can not be installed at least 600 mm below the HP
process connection, please use the equation below: 0
h= (P–P0) × 0.102 [mm] (–)
ds
h: Vertical height between the HP process
connection and the transmitter (mm) F0308.ai

h≤0: Install the transmitter at least h (mm) below the Figure 3.8 Example of Installation to
HP process connection Tank (Caution on Installation)
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of the transmitter
3.4 Mounting the
(Pa abs) See below table. Flushing
[For fill fluid code A, B, C, D, E] Connection Ring
Wetted parts Capillary Process connection size
material code 3.4.1 Mounting to Pressure
length
code 2, 8 3 4,W
SW 1 to 5m 6790 3190 Detector Section
6 to 10m 10030 3520 The flushing connection ring is mounted to the
SE 1 to 5m 6790 3190
6 to 10m 10030 3520 pressure detector section as shown in Figure 3.9.
SY 1 to 5m 3190 At the factory shipment, the flushing connection ring
6 to 10m 3520 is already assembled and attached to process
HW 1 to 5m 19150 6140
6 to 10m 8290 detector section.
TW 1 to 5m 9620 3620 Pressure-detector section
6 to 10m 4210
UW 1 to 5m 9540 4750
6 to 10m 6050 Ring
[For fill fluid code 1, 2, 4] Spiral gasket
Wetted parts Capillary Process connection size
material code
length
code 2, 8 3 4,W Groove for Ring holder
SW 1 to 5m 2570 320
6 to 10m 4680 530 installing
1 to 5m 2570 320 spiral gasket
SE
6 to 10m 4680 530 View from pressure Vent/Drain plug
SY 1 to 5m 320
6 to 10m 530 detector section
F0309.ai
HW 1 to 5m 10220 2050
6 to 10m 3450 Figure 3.9 Mounting to Pressure Detector Section
TW 1 to 5m 4270 570
6 to 10m 960
(1) Mount the ring holder on the ring and loosely
ds: Specific gravity of fill fluid (at 25°C). See below table. tighten the mounting screws.
Fill fluid A,1,4 B C, 2 D E (2) Place the spiral gasket in the ring groove. With the
code ring correctly aligned and flush with the face of the
ds: Specific 1.07 0.94 1.09 1.90 to 1.09 pressure detector, securely tighten each ring
gravity 1.92 holder’s mounting screws.
(3) Position the ring so that the vent/drain plugs
are aligned straight up and down.
IM
01C25A01-
01E
<3. Installation>
33
3.4.2 Mounting to Process Flange 3.5 Affixing the Teflon Film
Tighten the bolts to completely close the gap between the
IMPORTANT
ring and the pressure detector section.
The mating flange, gasket, stud bolts and nuts are to The FEP Teflon option includes a teflon film and
procured by the customer.
fluorinated oil. Before mounting the transmitter to the
process flange, affix the teflon film as follows:
Mating flange Spiral gasket 1) Position the diaphragm seal so that the diaphragm
is in an upward position.
Ring 2) Pour the fluorinated oil on the diaphragm and
gasket area covering it completely and evenly. Be
careful not to scratch the diaphragm or change the
its shape.
3) Affix the teflon film over the diaphragm and gasket
area.
Diaphragm 4) Next, carefully inspect the cover and try to identify
any entrapped air between the diaphragm and
Gasket Pressure-detector the teflon film. The air must be removed to ensure
section optimum performance. If air pockets are present,
use your fingers to remove the air by starting at the
center of the diaphragm and work your way out.
5) Position the gasket on the Teflon film.
6) Mount the transmitter onto the process flange.

F0310.ai
Teflon film
Figure 3.10 Mounting to Process Flange PART No.
EJ210 F9347YD
2 inch EJ118 F9347YA
EJ438
IMPORTANT 3 inch F9347XA
Fluorinated oil
• Confirm that there is no gap between the ring [PART No. : F9145YN]
and the process-detector section after they are Diaphragm
mounted on the process flange. A gap can lead to
a sudden, explosive release of process fluids. Gasket area
• When mounting or removing the ring, take care not F0311.ai
to tilt the pressure detector downward as the ring Figure 3.11 Affixing the Teflon Film
can slip off and cause injury.
• When re-mounting the ring, use the new spiral
gasket as shown in below table.

Table 3.1 Spiral Gasket for Pressure Detector


Section Side*
Part number Size Description
F9350SV ø100×ø120×t4.5 For 3-inch flange
F9970XF ø100×ø120×t4.5 For 3-inch flange**
F9350ST ø70×ø90×t4.5 For 2-inch flange
F9970XD ø70×ø90×t4.5 For 2-inch flange**
F9346ZH ø60×ø75×t4.5 For 1 1/2-inch flange
F9970XB ø60×ø75×t4.5 For 1 1/2-inch flange**
*: Material; 316SST (Hoop), PTFE Teflon (Filler)
**: For oil-prohibited use (Option code: /K1, /K2, /K5, /K6)

IM
01C25A01-
01E
<3. Installation>
34

3.6 Rotating Transmitter Section 3.7 Changing the Direction


The transmitter section can be rotated approximately of Integral Indicator
360° (180° to either direction or 360° to one direction
from the original position at shipment, depending on
the configuration of the instrument.) It can be fixed at
IMPORTANT
any angle within above range. Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area before
1) Remove the two setscrews that fasten the
disassembling and reassmbling an indicator.
transmitter section and capsule assembly, using
the Allen wrench.
2) Rotate the transmitter section slowly and stop it An integral indicator can be installed in the
at designated position. following three directions.
3) Tighten the two setscrews to a torque of 1.5 N·m.

IMPORTANT
Do not rotate the transmitter section more than
F0313.ai
the above limit.
Figure 3.13 Integral Indicator Direction
Vertical impulse piping type

Pressure-detector section
IMPORTANT
Stopper
The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on ATEX flameproof type
Rotate 0 to ±180° segments
transmitters. When the shrouding bolt is driven
clockwise by an Allen wrench, it is going in and
cover lock is released, and then the cover can be
opened. When a cover is closed it should be
locked by a shrouding bolt without fail. Tighten the
Conduit connection shrouding bolt to a torque of 0.7 N·m.

1) Remove the cover.


Transmitter section
2) While supporting the integral indicator with one
hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU
Horizontal impulse piping type assembly. When doing this, carefully pull the LCD
board assembly straight forward so as not to damage
Transmitter section the connector pins between it and the CPU assembly.
Rotate 0 to ±180° segments 4) After rotating the LCD, align both the LCD board
assembly and CPU assembly connectors and
engage them.
5) Insert and tighten the two mounting screws.
6) Replace the cover.
Conduit connection

CPU assembly
Zero-adjustment screw

Integral 90°
indicator 90°
Pressure-detector section

F0312.ai

Figure 3.12 Rotating Transmitter Section LCD board assembly


(Left Side High Pressure Type) Mounting screw

Amplifier cover
F0314.ai

Figure 3.14 Rotating Integral Indicator


IM
01C25A01-
01E
<4. Installing Impulse Piping>
35

4. Installing Impulse Piping


4.1 Impulse Piping (3) Tightening the Process
Connector Mounting Bolts
Installation Precautions
After connecting an impulse line, tighten the
The impulse piping that connects the process outputs to
the transmitter must convey the process pressure process connector mounting bolts uniformly.
accurately. If, for example, gas collects in a liquid-filled (4) Removing the Impulse Piping
impulse line, or the drain of a gas-filled impulse line
Connecting Port Dustproof Cap
becomes plugged, it will not convey the pressure
accurately. Since this will cause errors in the The impulse piping connecting port on the transmitter
measurement output, select the proper piping method for is covered with a plastic cap to keep out dust. This cap
the process fluid (gas, liquid, or steam). Pay careful must be removed before connecting the line. (Be
attention to the following points when routing the impulse careful not to damage the threads when removing this
piping and connecting the impulse piping to a transmitter. cap. Never insert a screwdriver or other tool between
the cap and port threads to remove the cap.)
4.1.1 Connecting Impulse Piping to
the Transmitter (5) Connecting the Transmitter and 3-
Valve Manifold (for differential
(1) Check the High and Low Pressure
pressure transmitters)
Connections on the Transmitter (Figure 4.1)
A 3-valve manifold consists of two stop valves to block
Symbols “H” and “L” have been placed on the capsule process pressure and an equalizing valve to equalize
assembly to indicate high and low pressure side. With
the pressures on the high and low pressure sides of
differential pressure transmitters, connect the high
the transmitter. Such a manifold makes it easier to
pressure side impulse line to the “H” side, and the low
disconnect the transmitter from the impulse piping, and
pressure side impulse line to the “L” side.
is convenient when adjusting the transmitter zero point.
With gauge/absolute pressure transmitters, connect
the impulse line to the ‘H’ side. There are two 3-valve manifold typs: the pipe-
mounting type and the direct-mounting type; care
Differential Pressure Transmitter should be taken with respect to the following points
when connecting the manifold to the transmitter.
Process “H” and “L” are shown
Process connection
connection  Pipe-Mounting Type 3-Valve Manifold
Process connector

Bolt F0401.ai Impulse piping Nipple


Vent plug
3-valve
Figure 4.1 “H” and “L” Symbols on a (optional) manifold Ball head
Capsule Assembly
Stop valve lock nut
(2) Changing the Process Connector (low pressure side)
Equalizing valve Pipes Pipe
Piping Connections (for differential
pressure transmitters) (balancing)
Ball head
The impulse piping connection distances can be Stop valve lock nut
changed between 51 mm, 54 mm and 57 mm by Nipple
changing the orientation of the process connectors. (high pressure side)
This is convenient for aligning the impulse line 50 mm(2-inch) pipe Process Process
with a process connectors. connector
connector bolts
F0403.ai

Figure 4.3 3-Valve Manifold (Pipe-Mounting Type)

57 mm 54 mm 51 mm
F0402.ai

Figure 4.2 Process Connector Impulse


Piping
Connection Distances
IM
01C25A01-
01E
<4. Installing Impulse Piping>
36
1) Screw nipples into the connection ports on the 4.1.2 Routing the Impulse Piping
transmitter side of the 3-valve manifold, and into
the impulse piping connecting ports on the process (1) Process Pressure Tap Angles
connectors. (To maintain proper sealing, wind
sealing tape around the nipple threads.) If condensate, gas, sediment or other extraneous
2) Mount the 3-valve manifold on the 50 mm (2-inch) material in the process piping gets into the impulse
pipe by fastening a U-bolt to its mounting bracket. piping, pressure measurement errors may result. To
Tighten the U-bolt nuts only lightly at this time. prevent such problems, the process pressure taps
3) Install the pipe assemblies between the 3-valve must be angled as shown in Figure 4.5 according to
manifold and the process connectors and lightly the kind of fluid being measured.
tighten the ball head lock nuts. (The ball-shaped
ends of the pipes must be handled carefully, since
they will not seal properly if the ball surface is
NOTE
scratched or otherwise damaged.) • If the process fluid is a gas, the taps must be
4) Now tighten the nuts and bolts securely in vertical or within 45° either side of vertical.
the following sequence: • If the process fluid is a liquid, the taps must
Process connector bolts → transmitter-end ball head be horizontal or below horizontal, but not
lock nuts → 3-valve manifold ball head lock nuts → more than 45° below horizontal.
3-valve manifold mounting bracket U-bolt nuts • If the process fluid is steam or other condensing
vapor, the taps must be horizontal or above
 Direct-Mounting Type 3-Valve Manifold horizontal, but not more than 45° above horizontal.
[Gas] [Liquid] [Steam]
1) Mount the 3-valve manifold on the transmitter.
Pressure 45° 45°
(When mounting, use the two gaskets and the four
taps 45° 45°
bolts provided with the 3-valve manifold. Tighten
the bolts evenly.) Process 45° 45°
2) Mount the process connectors and gaskets on the piping
top of the 3-valve manifold (the side on which the F0405.ai

impulse piping will be connected.) Figure 4.5 Process Pressure Tap Angle
(For Horizontal Piping)
Bolts Impulse
Process Stop valve piping
connector 3-valve
Equalizing manifold
(2) Position of Process Pressure Taps
Gasket
valve and Transmitter
Stop valve If condensate (or gas) accumulates in the impulse piping,
it should be removed periodically by opening the drain (or
Equalizing valve vent) plugs. However, this will generate a transient
disturbance in the pressure measurement, and therefore
it is necessary to position the taps and route the impulse
piping so that any extraneous liquid or gas generated in
Stop valve
the leadlines returns naturally to the process piping. • If
Impulse
piping the process fluid is a gas, then as a rule the
Bolts transmitter must be located higher than the process
Gasket
pressure taps.
Process Stop valve 3-valve
connector manifold • If the process fluid is a liquid or steam, then as a
F0404.ai rule the transmitter must be located lower than the
Figure 4.4 3-Valve Manifold (Direct-Mounting Type) process pressure taps.

(3) Impulse Piping Slope


The impulse piping must be routed with only an upward or
NOTE downward slope. Even for horizontal routing, the impulse
After completing the connection of the transmitter piping should have a slope of at least 1/10 to prevent
and 3-valve manifold, be sure to CLOSE the low condensate (or gases) from accumulating in the pipes.
pressure and high pressure stop valves, OPEN the
equalizing valve, and leave the manifold with the
equalizing valve OPEN.
You must do this in order to avoid overloading
the transmitter from either the high or the low
pressure side when beginning operation.
IM
01C25A01-
01E
<4. Installing Impulse Piping>
37
(4) Temperature Difference Between 4.2 Impulse Piping
Impulse Piping (for differential pressure
transmitters)
Connection Examples
Figure 4.6, 4.7, and 4.8 shows examples of typical
If there is a temperature difference between the high
impulse piping connections. Before connecting the
and low impulse lines, the density difference of the
transmitter to the process, study the transmitter
fluids in the two lines will cause an error in the
installation location, the process piping layout, and the
measurement pressure. When measuring flow,
characteristics of the process fluid (corrosiveness,
impulse lines must be routed together so that there is
toxicity, flammability, etc.), in order to make appropriate
no temperature difference between them.
changes and additions to the connection configurations.
(5) Condensate Pots for Steam Flow
Note the following points when referring to these
Measurement (for differential
piping examples.
pressure transmitters)
• If the impulse line is long, bracing or supports
If the liquid in the impulse piping repeatedly should be provided to prevent vibration.
condenses or vaporizes as a result of changes in the • The impulse piping material used must be
ambient or process temperature, this will cause a compatible with the process pressure, temperature,
difference in the fluid head between the high pressure and other conditions.
and low pressure sides. To prevent measurement • A variety of process pressure tap valves (main valves)
errors due to these head differences, condensate pots are available according to the type of connection
are used when measuring steam flow. (flanged, screwed, welded), construction (globe, gate,
(6) Preventing Wind Speed Effects in Very or ball valve), temperature and pressure. Select the
Low Differential Pressure Measurement type of valve most appropriate for the application.
(for differential pressure transmitters)
Liguid Gas Steam
Tap valve Orifice Condensate pot
IMPORTANT
Union
When using a differential pressure transmitter to or flange
measure very low pressures (draft pressure), the
low pressure connection port is left open to
atmospheric pressure (the reference pressure).
Any wind around the differential pressure transmitter Tee
will therefore cause errors in the measurement. To
3-valve
prevent this, it will be necessary either to enclose the
manifold
transmitter in a box, or to connect a impulse line to
the low pressure side and insert its end into a wind
excluding pot (cylindrical with a base plate). Drain valve
Drain plug
F0406.ai
(7) Preventing Freezing
Figure 4.6 Impulse Piping Connection Examples
If there is any risk that the process fluid in the impulse (for differential pressure transmitters)
piping or transmitter could freeze, use a steam jacket or
heater to maintain the temperature of the fluid. Open Tank Closed Tank Tap valve
Union or flange

NOTE Vent plug

After completing the connections, close the valves Tee


on the process pressure taps (main valves), the
valves at the transmitter (stop valves), and the
impulse piping drain valves, so that condensate,
sediment, dust and other extraneous material
cannot enter the impulse piping.

Drain valve

Drain plug
Pipe (opened to atmosphere
at low pressure side)
F0407.ai

Figure 4.7 Impulse Piping Connection Examples


(EJ210)
IM
01C25A01-
01E
<4. Installing Impulse Piping>
38
Liquid Gas Steam (3) Removing the Process Connector
Tap valve Union or flange Port Dustproof Cap
The process connector port threads are covered with
Union or flange
a plastic cap to exclude dust. This cap must be
Drain plug Tap valve removed before connecting the piping. (Be careful
Drain valve not to damage the threads when removing this cap.
Never insert a screwdriver or other tool between the
Union or
cap and port threads to remove the cap.)

flange Tee Tee Tee 4.3.2 Routing the Process Piping

Union or flange (1) Relationship between Process Fluid


and Manifold Locations (For the
Tap valve vertical impulse piping type)
Drain valve Drain valve
If condensate (or gas) generated in the process piping
Drain plug Drain plug were allowed to accumulate, then it would be necessary to
F0408.ai
remove it periodically by opening the drain (or vent) plug.
Figure 4.8 Impulse Piping Connection However, this would generate a transient disturbance in
Examples (for gauge/absolute the pressure measurement. Therefore, the process piping
pressure transmitters) must be routed so that any condensate (or gas) generated
in the process piping will not accumulate in the pressure-
sensing assembly of the transmitter.
4.3 Process Piping Installation
Precautions (EJ115) NOTE
• If the process fluid is a gas, then as a rule the
4.3.1 Connecting Process Piping to
manifold must be located at the downside of
the Transmitter the pressure-sensing assembly.
• If the process fluid is a liquid, then as a rule
(1) Confirming the Process Fluid Flow
the manifold must be located at the upside
Direction
of the pressure-sensing assembly.
The mark “ ” on the manifold indicates the direction in (2) Pipe Size for Process Piping
which the process fluid is flowed (from right to left). When
connecting the process piping to the process connector, Use a 15 mm (1/2-inch) pipe for process
confirm the process fluid flow direction. piping connection to the process connector.
Flow direction (from right to left) Orifice name plate (3) Preventing Freezing
Process connection Manifold Process connection
If there is any risk that the process fluid in the
(outflow side) (inflow side) transmitter pressure-sensing assembly could freeze
or solidify, use a steam jacket or heater to maintain
the temperature of the fluid.
(4) Process Piping Connection Examples
Process connector Process connector
Figure 4.10 shows examples of typical process piping
(low pressure side) (high pressure side)
F0409.ai connections. Before connecting the transmitter to the
process, study the transmitter installation location, the
Figure 4.9 Manifold and Flow Direction Indication
process piping layout, and the characteristics of the
process fluid (corrosiveness, toxicity, flammability,
(2) Tightening the Process etc.), in order to make appropriate changes and
Connector Mounting Bolts additions to the connection configurations.
The transmitter is shipped with the process connector Note the following points when referring to these
mounting bolts only loosely tightened. After connecting the piping examples.
process piping, tighten these bolts uniformly to prevent • The process piping material used must be
leaks with a torque of 39 to 49 N·m {4 to 5 kgf·m}. compatible with the process pressure, temperature,
and other conditions.

IM
01C25A01-
01E
<4. Installing Impulse Piping>
39
• A variety of process piping-mounted stop valves
are available according to the type of connection
(flanged, screwed, welded), construction (globe,
gate, or ball valve), temperature and pressure.
Select the type of valve most appropriate for
the application.

Gas flow measurement Union or flange

Stop valve
Manifold

Process piping
Liquid flow measurement

Manifold
Union or flange Stop valve

Process piping
F0410.ai

Figure 4.10 Process Piping Connection Examples


(EJ115)
IM
01C25A01-
01E
<5. Wiring>
40

5. Wiring
5.2 Connections of External
NOTE
Wiring to Terminal Box
For FOUNDATION Fieldbus, PROFIBUS PA, and
Mod bus communication types, please refer to ● Terminal Configuration
each communication manual. RTD cable connection*

5.1 Wiring Precautions

IMPORTANT
Terminal 4 [B]*
• Lay wiring as far as possible from electrical
Terminal 1 Terminal 3 [A]
noise sources such as large capacity
transformers, motors, and power supplies.
• Remove electrical connection dust cap Terminal 2
before wiring. *For EJX9A only. F0527.ai

• All threaded parts must be treated with


waterproofing sealant. (A non-hardening ● Terminal Wiring for 4 to 20 mA output
silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal + 1 Power supply and output terminals
SUPPLY – 2
and power cables through the same ducts. CHECK + 3 External indicator (ammeter) terminals*1*2
• Explosion-protected instruments must be wired or – 2 or
in accordance with specific requirements (and, ALARM + 3 Status contact output terminals*2
– 2 (when /AL is specified)
in certain countries, legal regulations) in order
Ground terminal
to preserve the effectiveness of their explosion-
protected features. *1: When using an external indicator or check meter, the
• The terminal box cover is locked by an Allen internal resistance must be 10 Ω or less. A check meter
or indicator cannot be connected when /AL option is
head bolt (a shrouding bolt) on ATEX specified.
flameproof type transmitters. When the *2: Not available for FOUNDATION Fieldbus and PROFIBUS
shrouding bolt is driven clockwise using an Allen PA communication types.
wrench, it gose in. The cover lock can then be
released and the cover can be opened by hand. ● Terminal Wiring for 1 to 5 V output
When a cover is closed it should be locked by + 1 Power supply terminals
SUPPLY – 2
a shrouding bolt without fail. Tighten the + 3 1 to 5 V DC with HART communication
VOUT
shrouding bolt to a torque of 0.7 N·m. – 2 terminals
Ground terminal

Shrouding Bolt ● Terminal Wiring for 4 to 20 mA output


Shrouding Bolt [EJX9A]
F0501.ai
+ 1 Power supply and output terminals
SUPPLY – 2
Figure 5.1 Shrouding Bolt 3 *1*2
CHECK + External indicator (ammeter) terminals
– 2
• Plug and seal an unused conduit connection. *2
PULSE + 4 Pulse or status contact output terminals
– 2

Ground terminal
*1: When using an external indicator or check meter, the
internal resistance must be 10Ω or less.
*2: Not available for FOUNDATION Fieldbus communication
type.
F0528.ai

Figure 5.2 Terminal


IM
01C25A01-
01E
<5. Wiring>
41
5.2.1 Power Supply Wiring Connection 5.2.3 Status Output Connection
When option code /AL is specified, connect the
external wiring as shown in Figure 5.7.
IMPORTANT
To configure and activate the process alarm function and
Connecting with the commercial AC power supply
status output, it is necessary to set some parameters.
will damage the device. Be sure to use the DC
Refer to each communication manual for procedures.
power supply in the predetermined range.
Transmitter 24V DC
terminal box Shielded cable
Connect the power supply wiring to the SUPPLY + +
Distributor
and – terminals. – 250Ω

Transmitter terminal box


+
Magnetic
Power supply valve
External power
– supply 30V DC,
Load resistance is not 120mA max
F0502.ai Use two-wire separately shielded cables. AC power supply
necessary for 1 to 5 V output.
F0504.ai
Figure 5.3 Power Supply Wiring Connection
Figure 5.7 Status Output Connection

5.2.2 Configuration Tool Connection

■ 4 to 20 mA output, BRAIN / HART


Connect the configuration tool to the SUPPLY +
and – terminals. (Use hooks.)

Transmitter terminal box Power supply


+
USB –
FieldMate Modem Ignore the polarity since
the configuration tool is
AC-coupled to the
F0503.ai
PC/FieldMate terminal box.

Figure 5.4 Configuration Tool Connection

■ 1 to 5 V output, HART
Connect the HART communicator or configuration
tool to the SUPPLY - and VOUT (+) terminals. (Use
hooks.)
Voltmeter
Power supply Transmitter terminal box
+ +
USB
– –
FieldMate Modem

F0532.ai
PC/FieldMate

Figure 5.5 Four wire connection

Transmitter terminal box Power supply


+
USB –
FieldMate Modem
+Voltmeter
PC/FieldMate –
F0533.ai

Figure 5.6 Three wire connection


IM
01C25A01-
01E
<5. Wiring>
42
5.2.4 Connection Example for EJX910A and EJX930A
Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART protocol type)

Connection Description
Analog Output Transmitter Electrical Terminal + Distributor

In this case, SUPPLY 24V DC


Communication is
+
possible (up to a distance – 250Ω
of 2km when a CEV cable B* –
is used.) PULSE * Either B or +

Pulse Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
In this case, Shielded Cable
SUPPLY +
E
No communication is
possible.
– *1
PULSE B * *2 R
Electric counter
* Either B or +

Status Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
Shielded Cable
E
In this case,
SUPPLY + Relay

No communication is –
possible. PULSE B* Mognetic

* Either B or + External Power supply valve

30V DC, 120mA max


(Contact Rating)
AC power supply

Simultaneous When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to

example 1 to 3. Distributor (or communication medium : ex. EP card)


Analog
*3 Shielded Cable 24V DC For the shielded cables in this example of
-Pulse Output
flowmeter installation, use two-wire separately
Example 1 SUPPLY + shielded cables.
In this case, Communica – *2 R
250Ω
This supply voltage requires a power sourse
-tion is possible(up to a PULSE B
*
E(10.5 to 30V DC)
distance of 2km when a with a maximum output current of no less than
Counting input
CEV cable is used). * Either B or + Common E/R.
Transmitter Electrical Terminal Electric counter *1(or communication medium : ex. EP card)
Example 2 For the shielded cables in this
Recorder or
example of flowmeter installation,
In this case, Communica Shielded Cable other instrument
use two-wire separately shielded
-tion is possible (up to a
distance of 200m when a
+ 250Ω
E(16.4 to 30V DC)
cables.
SUPPLY *2 This supply voltage requires a power
CEV cable is used) and R
= 1kΩ). – R Counting input sourse with a maximum output current
* Common of no less than E/R+25mA.
PULSE B The supply voltage requires output
* Either B or + Electric counter *1 impedance no more than 1/1000 of R
Transmitter Electrical Terminal (load resistance).
Recorder or
Example 3 other instrument
250Ω
In this case, No communi E(16.4 to 30V DC) This supply voltage requires
-cation is possible (when
SUPPLY +
shielded cable is not used). R *2 a power sourse with a
– Counting input maximum output current of
* Common no less than E/R+25mA.
PULSE B
* Either B or + *1
Electric counter
Transmitter Electrical Terminal

The range of load The load resistance of pulse output should be used to 1k Ω, 2W.
If no translation of the pulse output possible by the cable length or the frequency of the pluse output,
resistance R for the load resistance should be selected by calculation as shown below.
the pulse output. E (V) ≤ R (kΩ) ≤ 0.1 Example of CEV cable capacitance
120 C ( µF ) × f ( kHz ) 0.1µF/km

E2 (V) Where
E = Supply voltage (V) C = Cable capacitance (µF)

P (mW) = R (kΩ) f = Frequency of pulse output (kHz) P = Power ratio of the load resistance
R = Value of load resistance (kΩ) (mW)
F0531.ai
*1: To avoid the influence of external noise, use an electric counter which fits to the pulse frequency.
*2: Resistor is not necessary in case of an electric counter which can receive contact pulse signal directly.
*3: When using analog and pulse output simultaneously, the HART communication may be influenced by noise comparing analog output
only. Take countermeasure for noise shown above, e.g. use shield cable etc.
IM
01C25A01-
01E
<5. Wiring>
43
5.2.5 External Temperature Connection • Pulse output and Alarm, Status Output or
(for EJX910A and EJX930A) Simultaneous Analog-Pulse Output
Connect the RTD cable assembly to the Juck Terminal. (for EJX910A and EJX930A)
Hazardous Location Nonhazardous Location
Transmitter terminal box Distributor
(Power supply unit)

Receiver
F0505.ai
instrument
Figure 5.8 External Temperature Connection

5.3 Wiring
Receiver
5.3.1 Loop Configuration instrument

Since the DPharp uses a two-wire transmission F0507.ai

system for 4 to 20 mA output, signal wiring is also Figure 5.10 Connection between Transmitter
used as power wiring. and Distributor
DC power is required for the transmitter loop. The
transmitter and distributor are connected as shown (2) Intrinsically Safe Type (4 to 20 mA output)
below. For details of the power supply voltage and load
With the intrinsically safe type, a safety barrier must
resistance, see Section 5.6.
be included in the loop.
For 1 to 5 V output, three or four wire system is used.
See (4). Hazardous Location Nonhazardous Location

(1) General-use Type and Flameproof Type Transmitter terminal box


Distributor
(4 to 20 mA output) (Power supply unit)
• Analog Output
Receiver
Hazardous Location Nonhazardous Location
instrument
Transmitter terminal box Distributor

(Power supply unit)


F0508.ai
Receiver Safety barrier

Figure 5.11 Connection between Transmitter


instrument and Distributor

F0506.ai
(3) Intrinsically Safe Type (for EJX910A
Figure 5.9 Connection between Transmitter
and EJX930A)
and Distributor
• Analog Output
Hazardous Location Nonhazardous Location

Transmitter terminal box Receiver instrument


Safety barreir (and power supply)
(Isolation type)
Power
supply
Anaolg input
F0509.ai
IM
01C25A01-
01E
<5. Wiring>
44
• Simultaneous Analog-Pulse Output • Four wire connection
Fasten the negative side wiring of both power
Hazardous Location Nonhazardous Location
supply and signal line to the SUPPLY - terminal.
Transmitter terminal box Safety barrier I/O module
Hazardous Location Nonhazardous Location
(Isolated type)
Power Transmitter terminal box Distributor

supply (Power supply unit)


Analog input

Power

supply
Safety barrier Pulse input
Receiver
instrument

(Isolated type)
F0530.ai
F0510.ai

Figure 5.12 Connection between Figure 5.14 Connection between Transmitter,


Transmitter, Distributor and Receiver
barrier and receiver

(4) 1 to 5 V output 5.3.2 Wiring Installation


Either three or four wire system can be used.
(1) General-use Type and Intrinsically
Power supply line and 1 to 5 V signal line commonly
use the SUPPLY - terminal. Safe Type
With the cable wiring, use a metallic conduit or
NOTE waterproof glands.

With three wire connection, the cable length may • Apply a non-hardening sealant to the terminal
affect the measurement accuracy of the output box connection port and to the threads on the
signal. In either three-wire or four-wire connection, flexible metal conduit for waterproofing.
recommended wiring distance is 200 m or less, and
the use of shielded cable is recommended.

• Three wire connection


Flexible metal conduit
A negative wiring shall be commonly used for
power supply and signal line. Wiring metal Apply a non-hardening
conduit sealant to the threads for
Hazardous Location Nonhazardous Location waterproofing.

Transmitter terminal box Distributor


Tee

(Power supply unit) Drain plug


F0511.ai

Figure 5.15 Typical Wiring Using Flexible Metal


Conduit

Receiver
instrument

F0529.ai

Figure 5.13 Connection between Transmitter,


Distributor and Receiver

IM 01C25A01-01E
<5. Wiring>
45
(2) Flameproof Type • RTD connection components: EJX multivariable
transmitter, two cable glands, and RTD cable.
Wire cables through a flameproof packing adapter, or
Two cable glands are attached.
use a flameproof metal conduit.
Electrical connection
 Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box
Cable gland
connection port and to the threads on the
flameproof packing adapter for waterproofing. RTD cable
with connector

Flameproof Detail of connector


packing adapter
Transmitter
Flexible metal conduit

Wiring metal F0514.ai


Apply a non-hardening
conduit
sealant to the threads for • Magnified view of the RTD connector in
waterproofing.
the transmitter's terminal box.
Tee

F0512.ai
Drain plug

Figure 5.16 Typical Cable Wiring Using


Flameproof Packing Adapter

 Flameproof metal conduit wiring


ALARM ALARM

• A seal fitting must be installed near the terminal


box connection port for a sealed construction. Protection Cap Connecting Port
• Apply a non-hardening sealant to the threads of F0515.ai
the terminal box connection port, flexible metal
The RTD cable connecting port is covered with a cap to
conduit and seal fitting for waterproofing.
keep out dust. The cap should not be removed until you
Gas sealing device are ready to install the cable.
Non-hazardous area • Components for the cable gland
The cable gland assembly consists of an entry, seal,
Flameproof flexible running coupler, and backnut. Confirm that the seal
metal conduit is attached inside the entry and that the thread size
Hazardous area of the cable gland is the same as that for the RTD
Flameproof Apply a non-hardening
electrical connection.
heavy-gauge sealant to the threads of
steel conduit these fittings for 1/2NPT Type
waterproofing Entry with Seal Running Backnut
Coupler
Tee
Seal fitting
After wiring, impregnate the fitting
Drain plug
with a compound to seal tubing.
F0513.ai

Figure 5.17 Typical Wiring Using Flameproof


Metal Conduit Running
M20 Type
Gasket Entry with Seal Coupler Backnut
5.4 RTD Cable Connection
(EJX910A/EJX930A)
Connection of the RTD cable is always required to
measure external temperature. Follow the procedures F0516.ai

below to connect a cable when a cable gland or a


conduit is used.
CAUTION
5.4.1 Connecting Shielded Cable with
Input/output signal is non-isolated.
Cable Gland (External temperature Do not turn on power supply until you complete all
input code: -1, -2, -3, and -4) the wiring work.
IM
01C25A01-
01E
<5. Wiring>
46
Procedure (7) Rotate the running coupler another half turn to

(1) Disassemble the cable gland: loosen the running securely tighten the seal on the RTD cable.
coupler to separate the backnut from the entry. (8) Use a protection conduit, if necessary.
(2) Remove the protection cap over the transmitter In this case, insert the cable through the conduit
electrical connection and install the entry on the and attach it to the Backnut.
electrical connection. Note that a non-hardening
sealant should be applied to the threads for a 1/2
NPT connection and a gasket should be used for
CAUTION
an M20 connection. After the cable is secured as explained above, do
not tighten the running coupler any further; to do so
could damage the RTD connection.
Do not pull the cable or subject it to
excessive mechanical shock.

5.4.2 Connecting Shielded Cable for Con-


duit Use (External temperature input
F0517.ai
code: -B, -C, and -D)
(3) Pass the RTD cable through the running coupler • RTD connection components: EJX
and backnut assembly. multivariable transmitter and RTD cable

F0518.ai

(4) Insert the RTD cable and firmly plug its connector into
the connecting port in the transmitter's terminal box.

F0522.ai

Procedure
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.

F0519.ai

(5) Align the running coupler on the entry.

F0523.ai

(2) Remove the cap protecting the connecting port.


Then insert the RTD cable and firmly plug the
connector into the connecting port in the
F0520.ai
transmitter's terminal box.
(3) Insert the cable through the conduit and attach it
(6) Turn the running coupler until the seal in the
to the RTD electrical connection.
entry comes into contact with the RTD cable.

CAUTION
Do not pull the cable or subject it to
excessive mechanical shock.

F0521.ai
IM
01C25A01-
01E
<5. Wiring>
47
5.4.3 Cable Connection RTD Terminal 5.5 Grounding
Box Side Grounding is always required for the proper operation of
EJX multivariable transmitter RTD I/F is for 3-wire transmitters. Follow the domestic electrical requirements
Type RTD, Pt100. as regulated in each country. For a transmitter with a
Heed the following when wiring an RTD of the 2- or 4- built-in lightning protector, grounding should satisfy
wire type. ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of
NOTE the terminal box. Either of these terminals may be used.
Please note that a temperature error will occur
when you use a 2-wire RTD because of wiring
resistance. Please do not ground the shield on
the RTD side of the cable.
Ground terminal
(inside)
CAUTION
Ground terminal
Please use only the cables provided with
(outside)
this instrument.
When wiring, be sure not to damage the
cable's insulation or its core. F0525.ai

All the cable cores must have sufficient Figure 5.19 Ground Terminals
insulation around them.
Do not let the signal line contact the shield line.
Do not allow the shield line or the signal line to
5.6 Power Supply Voltage
come the earth potential voltage.
and Load Resistance
2-Wire 3-Wire 4-Wire For 4 to 20 mA output only.
When configuring the loop, make sure that the external
load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

A BA BbAa Bb
F0524.ai 600
External R= E–10.5 Communication
Figure 5.18 The Method of Wiring for the RTD Side
Table 5.2 The Method of Wiring for the RTD Side
load 0.0244
resistance applicable range
RTD Terminal BRAIN and HART
R (Ω)
RTD Terminal A a B b 250

2-Wire White - Blue1 and Blue2 -


0 10.5 16.6 25.2 42
3-Wire White - Blue1 Blue2
4-Wire White open Blue1 Blue2

NOTE Power supply voltage E (V DC)


F0526.ai

The color display in the table shows the white line Figure 5.20 Relationship between Power Supply
of the cable. Voltage and External Load Resistance
The cable color could change depending on the
cable type.
Blue 1 and blue 2 allow changing places.
For 2-wire Type, connect either which is blue1
or blue2, and give other side as OPEN.
IM
01C25A01-
01E
<6. Operation>
48

6. Operation

NOTE Burnout direction switch

For FOUNDATION Fieldbus, PROFIBUS PA and Modbus Slide switch BO H L


communication types and for the transmitter operating WR E D

confirmation and zeroing by any communication CPU assembly Write protection switch
method, refer to each communication manual.
Burnout direction switch (BO)
Burnout Direction H L H L

6.1 Preparation for Switch Position


Burnout Direction HIGH LOW
Starting Operation
Hardware write protection switch (WR)

 Confirming that Transmitter is Operating Write Protection H L H L


Properly Switch Position E D E D
On the integral indicator Write Protection NO YES

(Write enabled) (Write disabled)


• If the wiring system is faulty, the display stays blank.
F0602.ai

• If the transmitter is faulty, an error code is displayed.


Figure 6.1 Burn-out Direction and Hardware Write
Protection Slide Switch

Self-diagnostic error
on the integral indicator
(Faulty transmitter) 6.2 Zero Point Adjustment
After completing preparations for operating
F0601.ai
the transmitter, adjust the zero point.

 Verify and Change Transmitter Zero point adjustment can be done by turning the
transmitter’s zero-adjustment screw or by using the
Parameter Setting and Values communicator. This section describes the procedure
The parameters related to the following items are set for the zero-adjustment screw. For the zero-
at factory as specified in order. adjustment via communication, procedure, please
• Calibration range refer to each communication manual.
• Integral indicator display
• Output mode
• Software damping (optional)
IMPORTANT
Other parameters like following are shipped with Do not turn off the power to the transmitter
the default setting. immediately after performing a zero point
• Low-cut adjustment. Powering off within 30 seconds of
• Process alarm setting performing this procedure will return the zero point
• Static pressure range to its previous setting.
• Signal characterizer
• Write protection
To confirm or change the values, please refer to 6.2.1 Adjusting Zero Point for
each communication manual. Differential Pressure Transmitters
Before adjusting zero point, make sure that the
 Output Status Setting at CPU Failure
equalizing valve is open.
and Hardware Write Protection
Set the switches as shown in the figure below to set
the burn-out direction and write protection. The
Burnout switch is set to the H side for delivery (unless
option code /C1 or /C2 is specified in the order), and Zero-adjustment screw cover
the hardware write protection switch is set to E side F0603.ai

except EJX910A and EJX930A. The setting of the Figure 6.2 External Zero Adjustment
switches can be confirmed via communication. Screw
IM 01C25A01-01E
<6. Operation>
49
The zero-adjustment screw is located inside the cover. 6.3 Local Parameter Setting
Use a slotted screwdriver to turn the zero-adjustment
screw. Equalize the transmitter, then turn the screw
clockwise to increase the output or counterclockwise
WARNING
to decrease the output. The zero point adjustment can
be made with a resolution of 0.01% of the setting The local push button on the integral indicator must
range. The degree of zero adjustments varies with the not be used in a hazardous area. When it is
screw turning speed; turn the screw slowly to make a necessary to use the push button, operate it in a
fine adjustment, quickly to make a rough adjustment. non- hazardous location.

When using differential pressure transmitters for level


measurement and if you cannot obtain the lower
range value from the actual measurement value of IMPORTANT
0%, refer to subsection 6.2.2(2).
• Do not turn off the power to the transmitter
6.2.2 Adjusting Zero Point for Gauge/ immediately after performing parameter setting.
Powering off within 30 seconds of performing
Absolute Pressure Transmitters this procedure will return the parameter to its
previous setting.
(1) When you can obtain the Low Range
• The parameter of Ext SW must be“Enabled” to
Value from the actual measured value of perform this configuration. See the user’s
0% (0 kPa, atmospheric pressure); manual IM 01C25T (HART/BRAIN) for the
For pressure measurement using gauge pressure setting procedure.
transmitters, follow the steps below before • The Local Parameter Setting function is available
performing zero point adjustment. with HART or BRAIN communication type.

1) Close the tap valve (main valve).


2) Loosen the fill plug so that the pressure applied to 6.3.1 Local Parameter Setting (LPS)
the transmitter is only the head of the seal liquid. Overview
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and Parameter configuration by the external adjustment screw
then gradually open the tap valve. and push button (integral indicator code E) offers easy
and quick setup for parameters of Tag number, Unit, LRV,
Use a slotted screwdriver to turn the zero-adjustment URV, Damping,Output mode (linear/square root), Display
screw. Turn the screw clockwise to increase the output
out 1, and Re-range by applying actual pressure
or counterclockwise to decrease the output. The zero
(LRV/URV). There is no effect on measurement signal
point adjustment can be made with a resolution of
(analog output or communication signal) when Local
0.01% of the setting range. Since the degree of the
Parameter Setting is carried out.
zero adjustment varies with the screw turning speed,
turn the screw slowly to make a fine adjustment and
quickly to make a rough adjustment.

(2) When you cannot obtain the Low


Range Value from the actual External adjustment screw cover
measured value of 0%; F0604.ai

Adjust the transmitter output to the actual measured Figure 6.3 External Adjustment Screw
value obtained by a digital manometer or a glass gauge.
[Example] Integral indicator

The measuring range of 50 to 250 kPa; the


actual measured value of 130 kPa.

130–50
Actual measured value= 250–50 Push-button
F0605.ai
x100=40.0% (=10.4mA)
Figure 6.4 Range –Setting Switch (push button)
Turn the screw to match the output signal to the
actual measured value.

IM
01C25A01-
01E
<6. Operation>
50

screw
Process Zero adjustment

Measurement
Display push
Activate LPS mode
push 1. * Select Tag number Save/Cancel the value
Tag Number
2. * Edit Press unit Save/Cancel the value

Press Unit
3. * Edit Press LRV Save/Cancel the value
push
Press LRV
4. * Edit Press URV Save/Cancel the value

Press URV
5. * Edit Damping time Save/Cancel the value
push
Damping Time
6. * Select Output mode Save/Cancel the value

Output Mode
7. * Edit Display Out1 Save/Cancel the value
push
Display Out1
8. LRV-Apply Press Set LRV Save/Cancel the value

9. URV-Apply Press Set URV Save/Cancel the value


push
8, 9 : Re-range by applying actual pressure

10. Device Information

Process

Measurement
F0606.ai
Display

*: Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for
HART parameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.

Figure 6.5
IM
01C25A01-
01E
<7. Errors and Countermeasures>
51

7. Errors and Countermeasures


NOTE
For HART protocol revision 7, FOUNDATION Fieldbus, PROFIBUS PA and Modbus communication types, please
refer to each communication manual.

The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.

Table 7.1 Alarm Message Summary (Except EJX910A and EJX930A)


Indicator Cause Output Operation Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error keeps
CAP. ERR Capsule temperature sensor problem. Low) set with parameter. appearing even after restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR Amplifier EEPROM problem. Low) set with parameter.
Amplifier problem.
AL. 10 Input is outside measurement range Outputs high range limit value or low Check input or replace capsule when
PRESS limit of capsule. range limit value. necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside range Use heat insulation or make lagging
CAP. TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP. TMP (–50 to 95°C).
AL. 30 Output is outside upper or lower range Outputs high range limit value or low Check input and range setting, and
RANGE limit value. range limit value. change them as needed.
AL. 31 Static pressure exceeds specified Continues to operate and
SP. RNG range. output.
AL. 35 *1 Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds specified
SP. HI threshold.
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before error Check setting and change them as
P. LRV range. occurred. needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them as
SP. RNG holding static pressure in %. needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Specified values or settings to define Check setting and change
SC. CFG signal characterizer function do not them as needed.
satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP
*1: These alarms may appear only when process alarm function is activated.

IM
01C25A01-
01E
<7. Errors and Countermeasures>
52
Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)

Integral Cause 4-20mA Output Countermeasure


indicator operation during error
AL. 01 Sensor problem. Outputs the signal (High or Low) set Replace capsule if the error recurs
CAP.ERR with burnout direction switch. after the transmitter is restarted.
Capsule temperature sensor problem. [status output: undefined] Replace capsule.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Replace amplifier.
AMP.ERR Amplifier EEPROM problem.
Amplifier problem.
A/D Converter problem.
AL. 03 External temperature sensor Check external temperature sensor.
ET.ERR disconnection.
— No device ID is found. Continues to operate and output. Replace amplifier.
AL. 10 Differential pressure is outside When PV is Pres Check input or replace capsule when
PRESS measurement range limit of capsule. Output AO upper limit or AO Lower necessary.
limit.
AL. 11 Static pressure exceeds limit. When PV is SP
ST. PRSS Output AO upper limit or AO Lower
limit.
AL. 12 Capsule temperature is outside range Continues to operate and output. Use heat insulation or make lagging
CAP.TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP.TMP (–50 to 95°C).
AL. 14 External temperature is outside range. When PV is ET
EXT. TMP Output AO upper limit or AO Lower
AL. 15 External temperature sensor resistance limit.
EXT. TMP is out specification.
AL. 16 PLS Pulse output is out specification. Continues to operate and output. Check settings and change them.
AL. 30 Differential pressure exceeds specified When PV is Pres. Check input and range setting, and
PRS.RNG range. Output AO upper limit or lower limit. change them as needed.
AL. 31 Static pressure exceeds specified When PV is SP
SP. RNG range. Output AO upper limit or lower limit.
AL. 32 Flow exceeds specified range. When PV is Flow
F. RNG Output AO upper limit or lower limit.
AL. 33 External temperature exceeds specified When PV is ET
ET. RNG range. Output AO upper limit or lower limit.
AL. 35 P.HI Input pressure exceeds specified Continues to operate and output. Check input.
AL. 36 P.LO threshold.
AL. 37 SP.HI Input static pressure exceeds specified
AL. 38 SP.LO threshold.
AL. 41 F.HI Input flow exceeds specified threshold.
AL. 42 F.LO
AL. 43 ET.HI Input external temperature exceeds
AL. 44 ET.LO specified threshold.
AL. 50 P. LRV Specified value is outside of setting Holds at the output value that existed Check settings and change them as
AL. 51 P. URV range. immediately before the error occurred. needed.
AL. 52 P. SPN
AL. 53 P. ADJ Continues to operate and output. Adjust settings and change them as
needed.
AL. 54 Holds at the output value that existed Check settings and change them as
SP. RNG immediately before the error occurred. needed.
AL. 55 Continues to operate and output. Adjust settings and change them as
SP. ADJ needed.
AL. 56 Holds at the output value that existed Check settings and change them as
ET. RNG immediately before the error occurred. needed.
AL. 57 Continues to operate and output. Adjust settings and change them as
ET. ADJ needed.
AL. 58 Holds at the output value that existed Check settings and change them as
FL. ADJ immediately before the error occurred. needed.
AL. 59 Specified value is outside of setting Normal calculation.
PLS.ADJ pulse output.
— Under Temperature Fix Mode. PV is ET Temp. Output Fix at 4mA. Leave from Temperature Fix Mode.
IM
01C25A01-
01E
<7. Errors and Countermeasures>
53
Integral Cause 4-20mA Output Countermeasure
indicator operation during error
AL. 79 Displayed value exceeds limit. Continues to operate and output. Check settings and change them as
OV. DISP needed.
AL.87 Flange temperature exceeds a preset It depends on the Diag Out Option Check the heater failure.
FLG. HI upper limit. setting. Check the capsule temp. and
AL.87 Flange temperature is below a preset
FLG. LO lower limit. Off: Continue to operate and output. Amplifier temp.
Burnout:Outputs AO upper limit or AO
lower limit. Adjust Flg Temp Coef.
Fall back:Outputs Diag Out Fixed Val.
AL.88 Differential pressure/pressure Continue to operate and output. Check process condition.
INVR.DP fluctuation does not reach the reference
level required to blockage detection so
that no blockage detection is carried
out.
AL.88 Low-pressure-side fluctuation does not
INVR.SL reach the reference fluctuation level
required to blockage detection.
AL.88 High-pressure-side fluctuation does not
INVR.SH reach the reference fluctuation level
required to blockage detection.
AL.88 BlkF can not be used for blockage
INVR.F detection for some reasons.
AL.89 Appointed the diagnosis range outside.
ILBD.OV
AL.89 B Blocking (both-side blockage) is It depends on the Diag Out Option Check process condition.
B BLK detected. setting.
AL.89 High-pressure-side blockage is Off: Continue to operate and output.
H BLK detected.
Burnout: Outputs AO upper limit or AO
AL.89 Low-pressure-side blockage is
lower limit.
L BLK detected.
Fall back: Outputs Diag Out Fixed Val.
AL.89 Pressure fluctuation amplitude of high-
H LRG pressure side is large.
AL.89 Pressure fluctuation amplitude of low-
L LRG pressure side is large.
AL.89 A Blocking (single-side blockage) is
A BLK detected.
AL. 90 SIM Under Simulation Mode for flow. Simulate input output. Check Simulation Mode.
AL. 91 F. SIM Under Simulation Mode for device Output the setting value of Simulate- Check Simulation Mode.
AL. 91 P. SIM variables. Value.
AL.91 SP. SIM
AL. 91
ET. SIM
AL. 91
TF. SIM
AL. 91
PCT. SIM
AL. 91
AO. SIM

IM 01C25A01-01E
54

Revision Information
 Title : EJX and EJA-E Series
Differential Pressure and Pressure Transmitters Installation Manual
 Manual No. : IM 01C25A01-01E

Edition Date Page Revised Item


1st Aug. 2009 New publication
2nd Apr. 2010 7 to 14 2.4 Add limitation of ambient temperature for/HE.
3rd Oct. 2010 1, 5 and 15 Add EJX610A and EJX630A.
1 1. Add HART 7 manual.
2 1. Add note for wet location in (c).
3 3. Add EJX630A.
30 to 31 5.4 Modify pictures of cable gland.
41 to 43 8. Add parameters for EJX900A (Dev.rev.2).
4th Aug. 2011 1 1. Modify Table 1.1.
14 2.4.3 Alter the note (*1) for name plate.
27 5.2.2 Change the picture of configuration tool.
28 5.2.4 Add note (*3).
36 7 Add HART protocol revision 7 to NOTE.
37 7 Modify Table 7.2.
40 8 Add HART protocol revision 7 and EJX910A/EJX930A to NOTE.
Delete the Menu Tree for EJX910A/EJX930A.
5th Mar. 2012 Revise CD-R (Ed5).
6th Aug.2012 ― Add EJA-E series.
1 Add table for EJA to Table 1.1. Add note for representation of model name.
10 to 15 Revise ATEX approval.
17 Add models to PED table.
42-46 Add parameters and notes.
7th Jun. 2013 ― Add PROFIBUS PA.
7 Add note for multiple approval option.
13 to 14 Replace ATEX type n by ATEX Ex ic.
16 and 17 Add EJA110E with /HG to PED table.
20 Modify note for installation height.
8th June 2014 2 1. Add note for symbols.
8 2.4.2 Revise category for CSA Nonincendive.
17 2.7 Update safety requirement standard.
28 to 34 5. Revise drawings and symbols for terminal.
28 5.2.1 Add note for power supply.
37 to 42 6.3 Add local parameter setting function.
9th Oct. 2014 8 2.4.1 Add information for 1 to 5 V output.
10 2.4.2 Add information for 1 to 5 V output.
13 2.4.3 Add information for 1 to 5 V output.
16 to 17 2.4.5 Add EPL code. Revise applicable standard. Add information for 1 to 5
V output. Add note for electro static charge. Add electrical connection.
17 2.5 Add standard for PROFIBUS.
29 5.2 Add Figure 5.2 Terminal.
30 5.2.1 Add information for 1 to 5 V output.
33 5.3.1 Add information for 1 to 5 V output.
36 5.6 Add applicability.
40 6.3.1 Add “10.Device information”
41 6.3.3 Add note in the figure. Add method of cancel/save. Delete 6.3.4 to
6.3.11
42 7. Correct AL31 output operation.

IM 01C25A01-01E
55

Edition Date Page Revised Item


10th Apr. 2015 Removal of CD-R.
1 1. Modify descriptions. Replace CD-ROM information by the
downloading information. Modify structure of Table 1.1.
2 Delete note about CD-ROM.
1.1 Add WARNING sign.
3 Add (g) and (h).
5 2. Modify Table 2.1.
6 2.1 Replace Figure 2.2.
2.4 Delete Note for CD-ROM.
7 to 28 Add Fieldbus intrinsically safe type.
(2.4.1 b and c, 2.4.2 b, 2.4.3 c, d and g, and 2.4.4 b.)
28 2.5 for Profibus → for Fieldbus
30 2.7 Add C22.2 standard.
41, 49, 52 5, 6 and 7 Modify note for CD-ROM.
51 Delete 6.3.2.
11th July 2015 26 to 31 2.4.4 Add SU21 and SS26. Add a, b, c and d.
26 Revise Note 2.
53 6.3.1 Delete note for 10. from Figure 6.5.
12th Feb. 2017 1 Add IM for Diaphragm Seal System and DRS. Add a note on User’s Manual
for code Z.
4 Add statement for Chinese ROHS.
6 Update the L-type bracket in Figure 2.1.
8 to 12 Delete descriptions and add Control Drawing for FM approval.
16 to 23 Update ATEX applicable standards.
16 Revise descriptions for item a.
17 Delete item “b.ATEX Intrinsically Safe for HART Protocol Type for EJX90A”
20 Revise notes for ATEX flameproof type.
23 Update the tag plate for ATEX flameproof. Delete tag plate for EJX90A
intrinsically safe for HART/BRAIN.
24 Update IECEx applicable standards. Revise notes for IECEx intrinsically
safe type.
27 Delete items “e. IECEx Intrinsically Safe / type n for HART/BRAIN Protocol
Type (Except for EJX90A)” and “f. IECEx Intrinsically Safe / type n for
Fieldbus Type (Except for EJX90A).
28 Update PED information.(97/23/EC →2014/68/EU)
30 Update the L-type bracket in Figure 3.3.

IM 01C25A01-01E
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Phone : 81-422-52-5555
Branch Sales Offices
Osaka, Nagoya, Hiroshima, Kurashiki, Fukuoka, Kitakyusyu

YOKOGAWA CORPORATION OF AMERICA


Head Office
12530 West Airport Blvd, Sugar Land, Texas 77478, USA
Phone : 1-281-340-3800 Fax : 1-281-340-3838
Georgia Office
2 Dart Road, Newnan, Georgia 30265, USA
Phone : 1-800-888-6400/ 1-770-253-7000 Fax : 1-770-254-0928

YOKOGAWA AMERICA DO SUL LTDA.


Praca Acapulco, 31 - Santo Amaro, Sáo Paulo/SP, BRAZIL, CEP-04675-190
Phone : 55-11-5681-2400 Fax : 55-11-5681-4434

YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111

YOKOGAWA ELECTRIC CIS LTD.


Grokholskiy per 13 Building 2, 4th Floor 129090, Moscow, RUSSIA
Phone : 7-495-737-7868 Fax : 7-495-737-7869

YOKOGAWA CHINA CO., LTD.


3F Tower D Cartelo Crocodile Building, No.568 West Tianshan Road,
Shanghai 200335, CHINA
Phone : 86-21-62396262 Fax : 86-21-62387866

YOKOGAWA ELECTRIC KOREA CO., LTD.


(Yokogawa B/D, Yangpyeong-dong 4-Ga), 21, Seonyu-ro 45-gil, Yeongdeungpo-gu,
Seoul, 150-866, KOREA
Phone : 82-2-2628-6000 Fax : 82-2-2628-6400

YOKOGAWA ENGINEERING ASIA PTE. LTD.


5 Bedok South Road, Singapore 469270, SINGAPORE
Phone : 65-6241-9933 Fax : 65-6241-2606

YOKOGAWA INDIA LTD.


Plot No.96, Electronic City Complex, Hosur Road, Bangalore - 560 100, INDIA
Phone : 91-80-4158-6000 Fax : 91-80-2852-1442

YOKOGAWA AUSTRALIA PTY. LTD.


Tower A, 112-118 Talavera Road, Macquarie Park NSW 2113, AUSTRALIA
Phone : 61-2-8870-1100 Fax : 61-2-8870-1111

YOKOGAWA MIDDLE EAST & AFRICA B.S.C.(C)


P.O. Box 10070, Manama, Building 577, Road 2516, Busaiteen 225, Muharraq,
Kingdom of BAHRAIN
Phone : 973-17358100 Fax : 973-17336100
Apr. '15

Printed in Japan

You might also like