You are on page 1of 1

services connection of RCCB-ID

practical advice as in IEC 60947

110…220 V 220…380 V
connection in three-phase 127…240 V 240…415 V
with neutral
N 1 3 5 N 1 3 5

N 2 4 6 N 2 4 6

connection in three-phase 220…240 V


without neutral
out in

N 1 3 5 N 1 3 5 3
copper insulated cable wire 1.5 to
2.5 mm2

36 N 2 4 6 4
N 2 4 6

in out

12 12

15

380…415 V

resistor (R: 4 W) not supplied R

out in
N 1 3 5 3
36 N 1 3 5

N 2 4 6 4
N 2 4 6
12 out
in
18 R

I∆n (mA) R (Ω)


30 2200
100 620
300 220
300 2 620

additional
information
92418E.fm/2 Updated: 09/11/99 Schneider Electric