Procedure for updating software

Caution

Before updating your software, find out the product state of your SIMOREG device. You will find this on
the rating plate (field on the bottom left-hand side "Prod. State").
- Prod. State = A1, A2
(devices with the CUD1 electronics board, version C98043-A7001-L1-xx):
It is only permissible to load software versions 1.xx and 2.xx.
- Prod. State = A3
(devices with the CUD1 electronics board, version C98043-A7001-L2-xx):
It is only permissible to load software versions 3.xx.

Software Update 1/2 10.2007


s
Automation and Drives

Read out and write down all parameter Note:


1 contents. The parameter set can be transferred to a PC or
(also note software version in r060.001 and programming device by means of DriveMonitor
r065.001!) (see also Section 15 of the operation instructions).

Switch off electronics power supply


2

Connect one COM port on the PC to Cable order number: 6SX7005-0AB00


3 connector X300 on the converter. USB-RS232 (see also Section 15.3 of the operation
interface converters are supported. instructions)

Switch on electronics power supply AND Note:


4 press down the UP key on the PMU of the A software update can be started only from the
SIMOREG converter at the same time PMU panel and not via an OP1S or the
⇒ The SIMOREG converter switches to DriveMonitor system
operating state o13.0
Start on the PC the loading program Note:
5 HexLoad_Win.exe by double clicking on it.
7001Axxx.H86 and 7001Bxxx.H86:
Select the data file 7001Axxx.H86 with button Data files which contain the SIMOREG software
"Open C163/C165 - File (File"A")" (xxx is the SW release)
Select the data file 7001Bxxx.H86 with button
"Open C167 - File (File"B")"
Click on button "Start"
⇒ The software update is performed
automatically

⇒ When the software has been updated Note:


6
successfully, the SIMOREG switches to The currently programmed addressed is displayed
operating state o13.2 for approx. 1 s on the PMU while the update is in progress
⇒ The SIMOREG converter then switches to
The current status of the update routine is
operating state o12.9 in many cases
displayed on the PC
(depending on which SW version was
previously installed in the converter) for
approximately 15s.

Check the checksum:


7
Comparison of the value of parameter r062.001 with the checksum in the Internet under menu item
"Info" (see the inside page of the cover sheet of the operation instructions).

Was the electronics supply disconnected ? yes


8
while Step 6 was in progress?

Acknowledge any fault message that may


9b
appear on the SIMOREG device

n Restore default setting


o 10b
(see Section 7.4 of the operation instructions)

Start up the converter again


11b
(see Section 7.5 of the operation instructions)
Note:
The parameter set stored in Step 1 above can
be loaded from a PC or programming device
by means of DriveMonitor.

12 End

Software Update 2/2 10.2007