You are on page 1of 2

Rated Feeder Current

Insulation

Plug-socket
WIRING
Auxiliary Circuits
Insulation grade
Description

NA
630A
NA
Manual Operation
Manual Operation
630A
SF6 Gas
Manual Operation
Manual Operation
630A
Manual Operation
Manometer
1 Nos. per SF6 Vessel
NO
Voltage
NA
NA
NA
3V DC
NA
NA
NA
PVC (Single Core Cu wire, Multistanded) Flexible
1100 V
Details
Sr.
No.

Size of wire
(Control & auxiliary Circuits)
CT circuit
PT circuit
Control circuit DC If any
Control circuit AC If any
Auxiliary Buswire
Circuit identification
INTER-MODULE / INTER-PANEL WIRING
Within shipping section
Between shipping sections
TERMINATION ARRANGEMENTS
Cables
Power cable entry from
Control cable entry from
Cable boots/Terminal protector
Opening for Load Break Switch feeder
Opening for VCB feeder
Opening for Cable feeder
Control Terminals
Type of terminals for CT
Type of fixed terminals for Control Ckt.
Type of terminals for PT Ckt.
Earthing terminals
Earthing grid
Colour of earthing wire
Description

2.5 mm.²/ Red,Yellow,Blue,Black


1.5 mm.²/ Red,Yellow,Blue,Black
1.5 mm.²/Grey
1.5 mm.² Red for Phase and Black for Neutral
2.5 mm.² colour coding for AC/DC
as per above
Normal PVC ferrules at terminations
as per " Cross Dependant End Marking"
To be done at Works
Please refer the SLD diagram
Bottom
Bottom
Yes, being supplied as
loose as an accessory
NA
Gland Plate suitable for terminating up to
1Rx 3Cx 95mmsq XLPE cable
Gland Plate suitable for terminating up to
1Rx 3Cx 300mmsq XLPE cable
Disconnecting Type Polyamide (KLTDM4)
Normal Polyamide KUT2.5
NA
busbar at each end of the board