You are on page 1of 33

OISD - STANDARD - 180

JULY, 1999

LIGHTNING PROTECTION

Prepared by:
COMMITTEE ON LIGHTNING PROTECTION

OIL INDUSTRY SAFETY DIRECTORATE


2nd Floor, “Kailash”,
26, Kasturba Gandhi Marg,
NEW DELHI -110 001.

i
NOTE

OISD (Oil Industry Safety Directorate) publications


are prepared for use in the Oil and Gas Industry under
Ministry of Petroleum & natural Gas. These are the property
of Ministry of Petroleum & Natural Gas and shall not be
reproduced or copied and loaned or exhibited to others
without written consent from OISD.

Though every effort has been made to assure the


accuracy and reliability of the data contained in these
documents. OISD hereby expressly disclaims any liability or
responsibility for loss or damage resulting from their use.

These documents are intended to supplement rather


than replace the prevailing statutory requirements.

(ii)

ii
FOREWORD

The Oil Industry in India is nearly 100 years old. Due to


various collaboration agreements a variety of international codes,
standards and practices are in vogue. Standardisation in design
philosophies, operating and maintenance practices at a national
level was hardly in existence. This lack of uniformity coupled with
feedback from some serious accidents that occurred in the recent
past in India and abroad, emphasised the need for the industry to
review the existing state of art in designing, operating and
maintaining oil and gas installations.

With this in view, the Ministry of Petroleum and Natural


Gas in 1986 constituted a Safety Council assisted by the Oil
Industry Safety Directorate (OISD) staffed from within the industry
in formulating and implementing a series of self-regulatory
measures aimed at removing obsolescence, standardising and
upgrading the existing standards to ensure safer operations.
Accordingly OISD constituted a number of functional committees
comprising of experts nominated from the industry to draw up
standards and guidelines on various subjects.

The present document on “Lightning Protection” was


prepared by the Functional Committee on “Lightning Protection”.
This document is based on the accumulated knowledge and
experience of industry members and the various national and
international codes and practices.

It is hoped that provisions of this document if implemented


objectively, may go a long way to improve the safety to reduce
accidents in Oil and Gas Industry. Users are cautioned that no
document can be substitute for the judgment of responsible and
experienced engineer.

Suggestions are invited from the users after it is put into


practice to improve the document further. Suggestions for
amendments, if any, to this standard should be addressed to:

The Co-ordinator
Committee on “Lightning Protection”
Oil Industry Safety Directorate
2nd Floor, “Kailash”,
26, Kasturba Gandhi Marg,
NEW DELHI - 110 001.

This document in no way supersedes the statutory


regulations of Chief Controller of Explosives (CCE), Factory
Inspectorate or any other statutory body, which must be followed
as applicable.

(iii)

iii
COMMITTEE
ON
“LIGHTNING PROTECTION”

LIST OF MEMBERS
---------------------------------------------------------------------------------------------------------------------------
Sl.No. Name Organisation Position in
the Committee
---------------------------------------------------------------------------------------------------------------------------
S/Shri

01. V.P. Sharma Engineers India Limited Leader

02. A.K. Roy Indian Oil Corporation Ltd., Member


(Refineries Division)

03. S.C. Tyagi Oil & Natural Gas Corporation Ltd., Member

04. H. Prusty Gas Authority of India Ltd., Member

05. P.Kamalasekharan Indian Oil Corporation Ltd., Member


(Marketing Division)

06. R. Raghupathy Engineers India Limited Member

07. P.N. Deka Bongaigaon Refinery &


Petrochemicals Limited Member

08. J.K. Jha Oil Industry Safety Directorate Member


Co-ordinator.

In addition to the above, various other experts in the industry contributed in the preparation,
review, and finalisation of this document.

(iv)

iv
LIGHTNING PROTECTION

CONTENTS
---------------------------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------

1.0 INTRODUCTION 1

2.0 SCOPE 1

3.0 DEFINITIONS 1

4.0 LIGHTNING PHENOMENON 2

5.0 LIGHTNING PROTECTION CONCEPTS 4

6.0 LIGHTNING PROTECTION SYSTEM 6

7.0 CONTROL OF FUGITIVE EMISSIONS 8

8.0 PLANT BUILDING AND STRUCTURES 12

9.0 PROTECTION OF STORAGE TANKS 16

10.0 REFERENCES 20

11.0 APPENDIX 22

---------------------------------------------------------------------------------------------------------------------------

(v)

v
1.0 INTRODUCTION air terminals to earth terminations are
called Down Conductors
Lightning is a natural
phenomenon considered as “Atmospheric iv) Earth Terminations
Electricity” which develops as a result of
natural build-up of electrical charge Earthing conductors embedded in
separation in the storm clouds. Lightning the soil and designed for the Safe
strikes cause enormous loss of life and discharge of lightning currents into the soil
property all over the world. Hydrocarbon are called Earth Terminations
Industry suffers crippling damage,
disruption and loss because of this. v) Flame Protection

Protection to the plant structures, Self closing gauge hatches,


storage tanks and columns in the vapour seals, pressure vacuum breather
hydrocarbon industry against strokes of valves, flame arrestors or other
lightning has been a subject of concern reasonably effective means to minimise
and methods of providing lightning the possibility of flame entering the vapour
protection has been a subject of debate. space of a tank.

2.0 SCOPE
vi) Grounded Terminal:
This document explains the
lightning discharge phenomena, various The portion of a lightning
lightning concepts and control of fugitive protection system such as ground rod,
emissions and deals with lightning ground plate, or ground conductor that is
protection for plant building and structures installed for the purpose of providing
and Storage associated with an Oil/Gas electrical contact with the earth.
nstallation as per prevalent national and
international standards on the subject and vii) Grounded:
analyses their stipulations and provides
minimum requirements to be followed in A structure is supposed to be
the Oil Industry. This standard, however, adequately grounded if it is connected to
does not include guidelines for protection earth or to some conducting body that is
of electric equipment within or on connected to earth.
structures against lightning.
viii) Hazardous Area
3.0 DEFINITIONS
In accordance with the Petroleum
For the purpose of this standard, Rules, an area shall be deemed to be a
the following definitions shall apply. hazardous area, where:

I) Air Terminal a) Petroleum having flash point below


65o C or any flammable gas or vapour
An air terminal is that component in a concentration capable of ignition is
of a lightning protection system that is likely to be present.
intended to intercept lightning flashes.
b) Petroleum or any flammable liquid
ii) Bonding having flash point above 65o C is likely
to be refined, blended, handled or
An electrical connection between stored at or above its flash point .
an electrically conductive object and a
component of a lightning protection For details, refer OISD Standard 113 on
system that is intended to significantly Electrical Area Classification.
reduce potential differences created by
lightning current. ix) Shall

iii) Down Conductors “Shall” indicates a mandatory


requirement.
The conductors which connects

vi
x) Should particles are so distributed as to give rise
to a negative charge build-up at the base
“Should” indicates a requirement of the cloud.
which is recommendatory in nature.
The negative charge at the cloud-
xi) Side Flash: base gives rise to a positive build-up of
charge on the earth. The build-up
An electric spark, caused by continues till the potential difference
differences of potential, occurring between between the earth and the cloud base
conductive metal bodies or between such becomes so large that it causes a
metal bodies and a component of the breakdown of the resistance of air
lightning protection system or ground. medium, thereby creating a lightning
discharge.
xii) Spark Gap:
The majority of lightning strokes
As used in this code, the term are known to occur with the generation of
spark gap means any short air space a negative leader from the cloud to the
between two conductors electrically ground. The leader travels earthwards in
insulated from or remotely electrically discreet steps of approximately 30 to 60
connected to each other. meters each. When this stepped leader is
near the ground, its negative charge
xiii) Striking Distance: induces greater amounts of positive
charges on the earth, especially on
The distance over which the final objects projecting above the earth’s
breakdown of the initial stroke occurs. surface. These charges attract each other
and a cloud bound upward streamer is
xiv) Surge Arrestor: launched from the ground. The two meet
and form a completely conducting path
A protective device for limiting and very high current flows along this path
surge voltages by discharging or to equalize the potential difference. This
bypassing surge current. It also prevents is termed as the return stroke. Discharge
continued flow of follow current while phenomenon is pictorially depicted in
remaining capable of repeating these Fig.1.
functions.
Some typical values of the
xv) Vapour Openings: stepped leader and return stroke are as
follows:-
Openings through a tank shell or
roof above the surface of the stored a) Stepped Leader
hydrocarbon. Such openings may be
provided for tank breathing, tank gauging, - Average Current 0.1 to 1 KA
fire fighting, or other operating purpose.
- Speed of Propagation 2 X 105m/Sec.
xvi) Zone of Protection:
-Length of Steps 30 to 60m
Zone of Protection is the space apprx.
around a lightning conductor in which the
probability of lightning stroke is small. - Potential difference > 107 to 109
between leader & volts
4.0 LIGHTNING PHENOMENON earth.

Lightning is a natural
phenomenon which is said to be formed b) Return Stroke
as a result of a natural build up of
electrical charge separation in thunder - Peak current of first
clouds. In thunder clouds, normally, ice- return Stroke 30 KA
crystals become positively charged while
water droplets become negatively - Speed of Propagation 1/3 Speed
charged. In most of the cases, these of Light

2
-

FIGURE 1

1
4.3.1 Electrical
Wave Shape Rise time 2 to 10 micro Sec
Total discharge time to 50% 10-250 As the current is discharged
micro sec. through the resistance of the earth
electrode of the lightning protection
- Channel Temperature 30,000o K system, it produces a resistive voltage
drop which may momentarily raise the
(For more details on Lightning potential of the protective system to high
Phenomenon , reference may be made to value relative to the true earth. It may also
the book on “Lightning” by R.H. Golde) produce around the earth electrode a high
potential gradient dangerous to persons
The frequency of lightning differs and animals.
from region to region. Statistical data for
the number of thunderstorms in a given 4.3.2 Side Flashing
place is compiled and the yearly average
is termed as Ceraunic number. The The point of strike on the
higher this number, the larger is probability protective system may be raised to a high
of a lightning stroke. potential with respect to adjacent metal.
There is, therefore a risk of flash over from
It is estimated that about 2,000 the protective system to any other metal
storms exist at any one time in the world, on or in the structure.
bombarding the earth each year with over
3 billion lightning strokes. 4.3.3 Thermal

Lightning strokes could result in Although the lightning discharge


direct strikes or indirect strikes. current is high, its duration is short, its
thermal effect on the protective system is
4.1 Direct Strikes usually negligible. In general the cross
section area of lightning conductors is
Direct-stroke of lightning can chosen primarily to satisfy the requirement
cause severe damage to objects that of mechanical strength.
come in its path. The damage is largely
caused by heat, mechanical forces and 4.3.4 Mechanical
ignition of flammable materials. Typically
a direct-stroke on a tree generates so Where a high current is
much heat and mechanical force that it discharged along parallel conductor at
tears the limbs off the tree and scatters close proximity or along a single conductor
the bark over a wide area. Humans can with sharp bends, considerable
suffer heart failure, brain damage, mechanical forces are produced.
suspension of breathing or paralysis,
burns etc., 5.0 LIGHTNING PROTECTION
CONCEPTS
4.2 Indirect Strikes
Based on the understanding of the
In addition to the direct-stroke, the lightning discharge phenomenon, following
abrupt change in the electrical field, important points need to be noted.
caused by a lightning stroke, can cause
the lightning conductors to have potentials a) The down leader is self triggering and
of mega volts with respect to the true erratic in its downward movement. Its
earth, instantaneously. Any nearby metal initiation, progress and direction is
work which is earthed offers a low currently beyond the power of man to
impedance path to the stroke and the control.
discharge can flash over to this nearby
metal work, when the magnitude of the b) The final earth strike point is
potential is adequate to breakdown the determined by the nature and location
gap. of ground points which compete to
create upward intercepting leaders.
4.3 EFFECTS OF LIGHTNING
STROKE c) The first upward leader to intercept the
downward leader completes the path

2
for the main lightning discharge and called down conductor.
usually causes all other down leader
branches to collapse. Double The down conductor coveys the
discharges can occur when two down lightning energy to the earth in a safe
leaders approach earth with same time and well defined path thereby
and distance parameters. It is not preventing damage to the protected
necessary that all up leaders shall structure and avoiding side flashing.
intercept a down leader.
Earth Connection.
5.1
The connection to the earth mass
Lightning protection concepts are shall have a low impedance to prevent
based on either: the rise of potential of surrounding
earth mass and maximize the rate of
Delaying the release of upward fall of potential away from the
streamer for the area to be protected connection point. The earth mass with
the earth conductors embedded in the
(or) soil provides safe discharge of
lightning current into the soil.
Release of upward streamer from a
pre-defined point of the protected structure The remedial approach to lightning
to divert upon itself the stroke channel and protection has four options:
neutralize all the secondary effects.
- Conventional air terminal
The first approach is the preventive (Franklin Rod)
approach while the second is the remedial - Faraday Cage
or control approach. - Ionizing air terminal
- Laser Beam
5.2 Remedial Approach
The Franklin rod is a sharp
a) The remedial approach consists of pointed rod designed to intercept the
providing safety against lightning leader of lightning stroke and to transfer
strokes by employing means to the electric charge to the earth.
capture the lightning stroke leader.
Protection means in remedial The Faraday cage consists of
approach are designed: metallic material completely surrounding
the protected structure and resulting in its
- To convey the lightning energy to electrostatic shielding. For lightning
earth via a defined route. protection purpose, conductors are
spaced in a criss-crossed fashion across
- To ensure low impedance the roof structure and sides.
connection to the earth mass.
The early streamer emission
- To eliminate the secondary effects. system employs either a terminal of
specific shape (Sphere as in the case of
b) The basic components of a lightning Dynasphere) or enhanced ionizing
protection system in the remedial radioactive air terminal for the generation
approach are: of ions. Air terminal is connected to a
special down conductor attached to an
Air Terminal:- earthing system.

The air terminal captures the stepped The use of Lasers was proposed
leader of a lightning stroke by in 1974 to discharge thunder storms. The
launching an upward interception laser beam would produce multi-photon
streamer. ionization. The laser beam could thus
intercept a leader as it developed towards
Down Conductor:- the earth, and act as a conductor from
the cloud to the ground and then be
The conductor which connect air terminated to a down conductor and the
termination to earth termination is earth mass.

3
included as an option in any international
The disadvantages of the Faraday standards/practice on lightning protection.
cage are related to its high cost and the
fact that it has no impact on the 6.0 LIGHTNING PROTECTION
electromagnetic pulse related to a close SYSTEM
lightning stroke. The major drawbacks to
the laser beam are high cost, state of 6.1 Need For Protection
development and the problems of diverting
stroke energy to earth without damage to 6.1.1 The necessity of providing lightning
the laser itself. protection for structures located in
non-hazardous areas shall be
5.3 Preventive Approach assessed by calculating overall risk
factor. However, for hazardous
The preventive approach employs areas lightning protection is
method to prevent build-up of charge in essential considering the serious
the area to be protected. The system consequences of fire/damage due to
shall be able to reduce the potential lightning strokes and shall be
between the protected area and the provided irrespective of the value of
charged clouds, so that the potential risk factor.
difference is not high enough to enable the
generation of a leader to the earth within 6.1.2 Indian Standard IS:2309
the protected area. recommends following factors as a
basis of calculating the overall risk
When a thunder cloud passes factor for assessing the requirement
overhead and the field strength is greater of lightning protection.
2
than 2 KV/M , point discharge currents are
generated. Any natural occurring sharp a. Type of Construction.
point, such as trees, blades of grass on b. Contents of the building and
flat planes or pointed rocks on mountain consequential effects due to
tops will generate corona discharge. lightning stroke.
Point discharge currents act to limit the c. Degree of isolation.
electric strength. Multipoint discharge d. Type of terrain where the structure is
system consist of three elements as located.
shown in Fig. 2 e. Height of the Structure.
f. Lightning prevalence.
a) the dissipator or ionizer g. Usage of the building.
b) the ground current collector
c) the conductors connecting the Depending upon the
dissipator and the ground current characteristic features of above factors,
collect. overall risk factor shall be calculated as
per procedure given in IS-2309.
The configuration depends on the
size and height of the structure to the If the value of risk factor is less
protected, soil conditions, prevailing wind than 10--5 (One in Hundred Thousand),
condition, storm patterns, altitude and then in the absence of any other
keraunic number. The basic configuration overriding consideration, protection may
consists of a conductor with two sharp not be provided.
pointed rods connected at right angles to
each other and the right angle rods or If the risk factor is greater than
spaced along the conductor. The 10--5 (One in Hundred Thousand), then
configuration looks like barbed wire. This sound reasons shall be necessary to
conductor with multiple sets of rods support the decision of not providing the
spaced periodically along the length of lightning protection.
conductor is referred to as the dissipating
medium. Using this dissipating medium 6.2 Zone Of Protection
several array configurations can be
formed. Lightning protection system shall
be designed to protect the structures
It may be noted that as on date
multi-point discharge system is not

4
FIGURE 2

5
system. The path between air termination and earth shall be such that the lightning

current is discharged to earth without passing through non-conducting parts of the building
and also without causing fire, flashover and dangerous potential difference in and around the
structure.

Rolling sphere concept is followed to determine the zone of protection of lightning


conductor.

In this concept, the zone of protection includes the space not intruded by a rolling
sphere having radius equal to the stroking distance when tangent to earth and resting against
a lightning protection air termination, all space between the two points of contact and under
the sphere are in the zone of protection. A zone of protection is also formed when such a
sphere is resting on two or more air terminals and includes the space under the sphere
between those terminals. Fig.3 provides a graphic representation of rolling sphere concept

of zone of protection.

Striking distance of 30 Meters may be considered for the protection of structures


containing flammable materials and striking distance of 60 meters may be considered for
other structures.

Zone of protection for a single mast using 30 meters striking distance is shown in Fig.4
and that for Overhead Ground Wire( Suspended Air Terminals) is shown in Fig 5.

6.3 Lightning Protection of Structures containing flammable materials.

Protection Concept of storage tanks and vessels have been dealt in detail in attached
Appendix-I for guidance in designing lightning protection system.

7.0 CONTROL OF FUGITIVE EMISSION

For any fire to take place, three basic conditions i.e presence of oxygen, flammable
material and source of ignition must simultaneously exist. The lightning stroke i.e. the return
stroke may involve temperatures as high as 30,000o K in the discharge channel. Therefore, if
a direct strike of lightning or sparking due to a side flash takes place on a vent of a cone roof
tank while a flammable mixture is present, fire is bound to take place. it is therefore, essential
that measures to control of fugitive emission from storage tanks are given special
consideration.

The design, operating and maintenance practices for a hydrocarbon installation


should be given due attention to the need of minimising the possibility of presence of
flammable atmospheres. Control of fugitive emissions from vents, proper design and
maintenance of seals of floating roof tanks etc. are essential for avoiding damage to
petroleum installations due to lightning strokes.

Control of fugitive emissions is important from the view point of prevention of fire, in
addition to the benefits of environmental protection and product loss.

2
3
SINGLE MAST

ZONE OF PROTECTION _DEFINED BY DASHED LINES

Figure 4

4
ONE OF PROTECTION USING
OVERHEAD GROUND WIRES

ZONE OF PROTECTION DEFINED BY GROUND WIRE (S)


AND DASHED LINES

FIGURE 5

2
8.0 PLANT BUILDING AND All the vertical air terminations
STRUCTURES provided on the same structure shall be
interconnected.
The need for the protection of
plant buildings such as substation, control Where a structure has two
room office buildings, work shop, elevations; out of which lower is projecting
warehouse etc., and cooling towers shall outside and the higher elevation does not
be assessed taking into consideration the protect the lower elevation, separate
exposure risk and the following factors: network shall be provided for lower
elevation. Both networks shall be
a) Use to which structure is put. interconnected by connecting the higher
b) Nature of its construction. elevation down conductor to the lower
c) Value of its contents or network.
consequential effects.
d) The location of the structure and All the metal piping, railing etc., on
e) The height and the effective the roof shall be bonded to the protective
collection area of the structure. network.

The overall risk factor shall be 8.1.1.2 Down Conductors


established as per the guidelines of
IS:2309 to decide the need for protection. The recommended spacing of
down conductors is every 20 M of
Structures of exceptional Perimeter for structures upto 20 M in
vulnerability by reason of explosive or height and every 10 M of perimeter for
highly flammable contents need special structured above 20 M height.
consideration and every possible
protection need to be provided even 8.1.1.3 EARTH TERMINATION
against the rare occurrence of a lightning
discharge. Each down conductor shall be
provided with an earth electrode and all
8.1 General Design Requirements. earth electrodes shall be interconnected
through underground strip.
A lightning protection system Lightning protection earthing
(Conventional Air Terminal System) system may be bonded to electrical
consists of the following three basic safety earthing system, inside ground.
components:
The use of rod/pipe/strip
a) Air terminal electrodes is permissible. Their choice will
b) Down conductor depend upon site conditions, soil resistivity
c) Earth connection and economic considerations.
8.1.1 Air Termination System The material of earth electrodes
shall be galvanised iron.
The air terminal shall be capable
of drawing the lightning discharge to it in The whole of lightning protective
preference to vulnerable parts of the system including any earth ring shall have
protected structure. The air terminations a combined resistance to earth not
can be of vertical or horizontal type. exceeding 10 ohm without taking account
of any bonding.
Conductors shall be
interconnected to form a closed loop. 8.1.2 Size and Material of Conductors
Vertical air terminations shall be The material of air termination
used for very high structures with small network, down conductor and earth
base areas e.g. non-conducting chimneys termination shall be galvanised iron.
etc. Minimum 2 nos. vertical terminations
shall be provided for chimneys. Lightning currents have very short
duration, therefore thermal factors are of
Vertical air terminations shall little consequence in deciding the cross-
project at least 300 mm above the section of the conductor. The minimum
protected structure. size of the various components of lightning

2
protection system shall be as follows:
Any metal in or forming part of the
¾ Vertical Air - 25mm dia., structure on any building services having
Termination 1000mm metallic parts which by design or by
long GI chance are in contact with the general
Pipe mass of the earth should be either isolated
from or bonded to the down conductor.
¾ Horizontal air - 25mm X
termination 3mm GI The same general recommendation
Strip (or) applies to all exposed large metal items
40mm X whether connected to earth or not. ( In
5mm GI this context a large item is considered as
Strip one having any single dimension greater
than 2 m.) Minor items such as door
¾ Down conductors - Same as hinges, metal gutter brackets,
horizontal air reinforcement of small isolated beams
termination. may be disregarded.

¾ Earth terminations - 65 mm dia., If portions of a structure vary


3000mm considerably in height, any necessary air
long G.I pipe terminations or air termination networks
in Test pit. for the lower portions should be bonded to
the down conductors of the taller portions
in addition to their own down conductors.
All hardwares used for earth
connection shall be hot dipped galvanised Typical examples of air terminations for
or Zinc passivated. The amount of flat roof, large area roof of various profiles
galvanising shall be 610 gm/sq.mt as per are illustrated in Fig.6 and 7.
Industry Practice.
All members of UHF/Microwave tower
steel structure should be connected with
8.2 Protection of Sub-station, Control eachother through bolt/nut properly
Room, Pump Houses, UHF / tigthtened at more than one point and
Microwave Tower and similar whole structure should be electrically
functional buildings and Structures. continuous and earthed properly,so that
the structure can be used as down
These structures are generally conductor.
made of insulating materials such as
concrete and brick. Protection against 8.3 Protection of Compressor House,
direct stroke of lightning is made by Truck Loading, Wagon Loading
properly designed air termination network Structures.
which may consist of vertical, horizontal
conductors or combination of both. These are in general steel framed
building structures, the frame work itself
Depending upon the form of the provides an efficient natural network of
building, required number of down many paths to earth. The structural steel
conductors shall be provided as per the columns shall be connected to the plant
guidelines given in IS:2309. Down earth grid and as such down conductors
conductor system shall be routed directly are not required. The resistance of the
(where practicable) from the air total structure to the general mass of earth
termination to the earth termination shall be measured using earth meggar
network and be symmetrically placed and it shall be less than 10 ohms.
around the outside walls of the structure
starting from the corners.

The rolling sphere concept of


protection shall be adopted to determine
the area/zone of the protection taking into
account the possibility of side strikes to
the structures.

3
4
5
A network of horizontal closed or otherwise protected against
conductors (air termination system) should the entrance of flame.
be fixed to the roof of structure as per the
guidelines of IS-2309. c) Structures and all accessories e.g.
dip-gauge hatches, vent valves shall
Ventilators and other roof be maintained in good and sound
projections of non-metallic construction operating conditions.
shall be protected by means of air terminal
system and connected to the steel frame d) Flammable air-vapour mixtures shall
of structure. be prevented to the greatest possible
extent from accumulating outside
major metal forming part of the structure, such structures.
including continuous metal reinforcement e) Potential spark-gaps between
and services, should be bonded together metallic conductors shall be avoided
and connected to the lightning protective at points where flammable vapours
system. Such connections should be may escape or accumulate.
made in atleast two places and should,
wherever possible, be equally spaced f) Sheet steel of thickness less than 4.8
around the perimeter of the structure at mm shall not be used as a material
intervals not exceeding 15 m. For further of construction for the tanks and
details refer IS-2309. vessels.
Metal inside the structure should A properly designed / constructed
be bonded to the lightning protective gas tight storage tanks considered to be
system. self-protected against lightning, provided
it is properly earthed and bonded. Such a
Vents and exhaust stacks from structure may not require any additional
process plants emitting flammable means of lightning protection.
vapours or dusts should be fitted with
flame traps. 9.2 Normally in hydrocarbon industry two
types of above ground storage tanks
8.4 Protection of Stacks. are in use for storage of flammable
liquids at atmospheric pressure:
Non-conducting chimneys whose
overall width or diameter at top is upto 1) Fixed roof type tanks
1.5m shall be provided with one down
conductor, and chimneys with overall 2) Floating roof type tanks
width or diameter at top more than 1.5m
shall be provided with 2 no. down Protection against lightning for
conductors as shown in Fig.8. these two types of storage tanks are
illustrated below:
Metal stacks shall be properly
earthed at the bottom. No air Fixed roof type tanks:
terminal/down conductors are required if
the thickness of sheet steel is more than The contents of metallic tanks with
4.8 mm. steel roofs of riveted, bolted or welded
construction with or without supporting
members, used for the storage of
9.0 PROTECTION OF STORAGE
flammable liquids at atmospheric pressure
TANKS are considered to be inherently self-
protecting against lightning if the following
9.1 Following fundamental principles requirements are met:
of lightning protection of the structures and
their contents shall be adhered to:- a) All joints between metallic plates shall
be fully riveted, bolted or welded.
a) Flammable liquids shall be stored
in essentially gastight structures. b) All pipes entering or connected with the
tank shall be metallically connected
b) Openings where flammable and properly bonded with the tank at
concentrations of vapour or gas can the point of entrance.
escape to the atmosphere shall be

6
Figure 8 : Lightning protection of RCC Chimneys

1
FIGURE – 9 EARTHING OF THE TANKS
NOTE: No of earth connections shall be decided based on tank diameter considering that the
spacing between any two earth connections shall not exceed thirty meters along the tank
perimeter.

1
FIGURE – 10 TYPICAL EARTH CONNECTION

2
c) All vapour or gas openings shall be closed or with non-conductive seals do not
or provided with flame protection devices generally require shunts at the seal.
when the stored stock may produce a However, if shunts are not provided a
flammable air-vapour mixture under tight seal must be maintained to prevent
storage conditions. accumulation of vapours. Where metallic
weather shields cover the seals they shall
d) The roof shall have a minimum thickness maintain contact with the shell.
of 4.8mm.
c) Where a floating roof tank is equipped
e) The roof shall be welded, fully bolted or with both primary and secondary seals in
riveted to the tank shell. compliance with environmental
regulations, shunts shall be installed so
Tanks shall be grounded to conduct that they directly contact the tank shell
away the current of direct strokes and to above the secondary seal as in case of
avoid the buildup and potential that may primary seals explained in “a” above.
cause sparks to ground. A metal tank shall
be grounded by one of the following d) All conductive parts of internal floating
methods: covers or the floating portions of covered
floating roof tanks, ladders should be
a) A tank is connected without insulated electrically interconnected and bonded to
joints to a grounded metallic piping the tank roof/shell.
system.
10.0 REFERENCES:
b) A vertical cylindrical tank rests on earth
or concrete and is at least 6m in The following codes, standards and
diameter or rests on bituminous publications have either been referred to or
pavements and is at least 15 M in used in the preparation of this document and
diameter. the same shall be read in conjunction with
this document:
c) By bonding the tank to ground through a
1) OISD Standards/ Recommended
minimum of two ground terminals as
Practices such as:
shown in Fig.9 at maximum 30 M
intervals along the perimeter of tank.
a) OISD- 149; Design Aspects for Safety
This also applies to tanks with an
in Electrical System.
insulting membrane beneath the tank.
b) OISD- 137 Inspection of Electrical
d) Storage tanks having cathodic protection Equipment.
system require special consideration
while designing the grounding system. 2) BIS (Bureau of Indian Standards)
Publication.
Floating Roof Tanks:
a) IS-2309: Protection of Buildings & allied
In addition to the concepts followed in structures against lightning.
case of fixed roof type tanks, following 3 International Code of Practice / guidelines
measures are essential in case of floating
roof type tanks used for storage of flammable a) API Recommended Practice 2003:
liquids: Protection against ignition arising
out of Static, Lightning and Stray
a) Metallic straps (Shunts) at intervals of not Currents -
over 3 meter length on the circumference
of the roof between the floating roof and b) NFPA 780: Standard for the
the metallic shoe that slides on the inside installation of Lightning Protection
of the shell will permit the charge to drain Systems.
off without igniting vapour under the seal.
Shunt of flexible Type 302, 28 gauge (0.4 c) BS 6651 Code of Practice for Protection
mm X 51 mm) wide stainless steel straps of Structures against Lightning.
or the equivalent current carrying capacity
d) Electrical Safety Code - Institute of
and corrosion resistance are used. (Ref.
Petroleum, U.K.
Fig.10)
4. Lightning, Vol.1 & 2 by R.H. Golde.
b) Tanks without a vapour space at the seal

3
APPENDIX- I

A1. PROTECTION CONCEPTS OF STORAGE TANKS AND VESSELS

The need for the Protection against Lightning for Storage Tanks, Spheres, Bullets
containing flammable materials is self evident.

A properly bonded and earthed metallic storage tank of adequate shell/roof thickness is self
protected against lightning, provided these are tightly sealed to prevent the escape of liquid, vapour,
or gas.

It is to be noted that, pressure vessels such as spheres and bullets are gas tight by the
design of its construction. Hence, properly earthed spheres and bullets are self protected and do
not need additional measures against lightning protection.

Where the probability of flammable atmosphere around the rim of a floating roof tank and
around the vent of a fixed roof tank is relatively high as compared to other locations around the
tankages, augmentation of lightning protection system may be considered. It may however be
borne in mind that the only effective defence against ignition by a direct strike is a tight seal.

Lightning conductor as part of lightning protection system is incapable of discharging a


thunder cloud without a lightning flash. It is thus obvious that in case of a lightning strike, the source
of ignition is present due to temperatures of around 30,000o K in the discharge channel of a return
stroke or the secondary arc in case of a indirect strike

The underlying principle for augmenting lightning protection to hydrocarbon storage tanks,
is therefore based on shifting the point of strike of lightning stroke to a safe area above the vapour
space (or above the classified zones for hazardous atmosphere) so that ignition of vapours
probably present above the roof does not take place.

A1.1 Accordingly the following options are available for the augmentation of the lightning
protection system.

I) Use of lightning Air Terminals on the tank shell.

ii) Use of lightning protection masts around the storage tanks.

iii) Use of overhead shield wire.

While designing the above options following important aspects need to be kept in mind:

a) Striking distance of 30 m is to be considered for applying the rolling sphere concept of protected
zone.

b) Increasing the height of lightning masts above the striking distance (30 m) will not increase the
zone of protection. Zones of protection for varying mast height and a striking distance of 30 m
are shown in Fig.A1..

c) To prevent side flashes, the minimum distance between a mast or overhead ground wire and
the structure to be protected shall be not less than the bonding distance or sideflash distance.

Sideflash distance from a mast can be calculated by the formula:

D = h
6

Where h = height of structure.

4
Figure A1

5
Sideflash distance from a catenary may be calculated as:

D = I_
6n

Where I = Length of lightning protection cable between its grounded point and the point under
consideration.

n = Between 1 to 2.25 depending upon the number of down conductors and their spacing.

A1.2 Air Terminals installed on Tank Shell:

Protection zone provided by air terminals installed on the tank shall depend upon the tank
dia, height of air terminal and spacing of air terminals around the tank perimeter. A conventional 6
m high air terminal, spaced about 20 m around the periphery protects an area upto 15 to 18 m from
the tank shell. This implies that lightning protection using air terminals installed on the tank walls
can completely protect a storage tank upto 30 M dia whereas the center portion of the roof remains
unprotected for tank diameters more than 30m as shown in Fig.A2

The use of air terminals can be applied to floating roof tanks for reducing the probability of
rim fires due to lightning strikes since the space around the rim has relatively higher possibility of
flammable atmosphere being present due to leakage from improper sealing.

Where the tanks walls are of thickness more than 4.8 mm, separate down conductors, are
not required and tank wall itself can be used as down conductor with the proper connection of air
terminals to the tank shell. Typical details are given in Fig.A3.

Number of 6 m high air terminals (spaced about 20 m around the perimeter) required for
various tank diameters are tabulated below:

TANK DIA NUMBER OF


AIR TERMINALS

Upto 12M 3
13 - 21M 4
22 - 32M 5
33 - 38M 6
39 - 45M 7
46 - 51M 8
52 - 57M 9
58 - 63M 10
64 - 71M 11
72 - 79M 12

A1.3 Lightning Masts around Storage Tanks

For a lightning mast to prevent fires due to lightning, following basic factors need to be
borne in mind:

a) Lightning mast located more than 30m away from the tank irrespective of the height of the mast
does not provide any improvement to the self protected storage tank.

b) Lightning mast should be located close to the tank and the minimum distance is dictated by the
side flash distance and the practical considerations for mast installation.

In view of above, lightning mast is required to be located at around 5 to 6 m from the tank
shell.

Protection zone of a system of lightning masts with mast height equal to 15 m more than

6
AIR TERMINALS ON TANK WALLS

NO. OF AIR TERMINALS

FIGURE A2

7
DETAILS OF AIR TERMINALS ON TANKS

FIGURE A3

8
the tank height and spacing of about 24 m around the tank is almost same as that provided with the
use of lightning conductors installed on the tank shell, the number of lightning masts and the
lightening conductors on shell being the same. Protection zone for a 50 m dia tank using lightning
masts is illustrated in Fig.A4.

It is thus obvious that both a system of lightning masts around the tank or lightning
conductors provided on the tank wall provide similar protection to the tank for preventing fires due to
lightning. Lightning masts are much more expensive as compared to the air terminals on the shell
while the lightning masts would be easier to install as a retrofit in an operating plant in comparison
to the air terminals, since the latter would require welding work on the tank wall.

Lightning mast can be of tubular design or a lattice structure of angle irons. Earthing
system of the lightning mast shall have to be bonded to the earthing system of the associated
storage tank.

A1.4 Use of Overhead Shield Wire

A system of overhead earth wires can be designed to provide complete protection to a


storage tank within the realm of rolling sphere concept based on a striking distance of 30 m. A
single earth wire with a minimum clearance of about 8 m above the highest point of the tank can
protect a tank of about 6 to 8 m diameter. For tank diameters between 8 to 30 m two parallel earth
wires shall be required while for tank diameters between 30 to 80 m three parallel overhead earth
wires shall be needed as a minimum.

Protection zones using a system overhead earth wires are shown in Fig.A5.

Supporting structures for the overhead earth wires can be either of tubular design or a
lattice structure. Height of the structure shall be decided based on the height of the topmost point
on the tank roof and the side flash distance. The supporting structure shall also have to be located
sufficiently away from the tank so as to prevent any side flash. The earth-wire shall be bonded to
the steel supporting structure which can serve as a down conductor. Earthing system of the
supporting structure shall be bonded with the tank earthing system.

A1.5

With regard to protection for structures containing flammbale vapours, gases or liquids that can
give off flammable vapours, the following principles should be followed:

a) Liquids that can give off flammable vapours shall be stored in essentially gastight structures.

b) Openings where flammable concentrations of vapour or gas can escape to the atmosphere shall
be closed or otherwise protected against the entrance of flame.

c) Structures and all appurtenances (e.g. dip-gauge hatches, vent valves) shall be maintained in
good operating conditions.

d) Flammable air-vapour mixtures shall be prevented to the greatest possible extent from
accumulating outside such structures.

e) Potential spark-gaps between metallic conductors shall be avoided at points where flammable
vapours may escape or accumulate.

9
FIGURE A4

10
FIGURE A5

11

You might also like