You are on page 1of 21

IS 5572 : 1994

(Reaffirmed 1999)
Edition 3.1
(2000-03)

Indian Standard
CLASSIFICATION OF HAZARDOUS AREAS
(OTHER THAN MINES) HAVING
FLAMMABLE GASES AND VAPOURS FOR
ELECTRICAL INSTALLATION
( Second Revision )
(Incorporating Amendment No. 1)

UDC 621.316.17 : 614.87

© BIS 2002

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN , 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

Price Group 8
Electrical Apparatus for Explosive Atmospheres Sectional Committee, ET 22

FOREWORD

This Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by
the Electrical Apparatus for Explosive Atmospheres Sectional Committee had been approved by
the Electrotechnical Division Council.
When electrical equipment is to be installed in or about a hazardous area, it is frequently possible
by care in the layout of the installation to locate much of the equipment in less hazardous or non-
hazardous areas, and thus reduce the amount of special equipment required. This standard has
been drawn up keeping this as a primary objective.
The classification and delineation of any particular hazardous areas shall be based on available
information concerning materials and processes to be used, including such evidence as may be
supplied by the consumer, and shall take into account factors, such as height, ventilation,
standards of maintenance, type of apparatus, operation and competent personnel available for
inspection, which may affect the nature and extent of the hazard. Each room, section of area shall
be considered individually in determining its classification and also in relation to others.
The classification of areas has been done according to the extent of risk involved so that it provides
a guideline to the choice of equipment to be installed in different areas on the basis of the extent of
hazard.
This standard was originally proposed to be brought out in following two parts:
Part 1 Areas having flammable gases and vapours
Part 2 Dust laden atmospheres
However in view of separate standards now being brought out for electrical apparatus for use in
presence of combustible dusts, Part 2 of this standard which was envisaged earlier is no longer
required. Therefore this standard is not being published in parts, and is intended to cover only
chemical industries, hydrocarbon industries and other similar areas where flammable vapours are
encountered.
Flammable gases and vapours may either be heavier or lighter than air. The area classification in
the original standard was based on the assumption that the flammable vapours encountered were
heavier than air. In the first revision both the possibilities were taken care of in the classification
of areas. This revision takes into account the latest technological developments in the field of
classification of hazardous areas at the international level. Some typical area classification details
have also been included in this revision.
This standard includes generalized statements and recommendations on matters on which there
are diverse opinions. It is, therefore, important that sound engineering judgement take precedence
over a literal interpretation of text. Good judgement should be exercised without jeopardizing the
requirements laid down in this standard.
In preparation of this standard assistance has been derived from IEC Pub 79-10 (1986) ‘Electrical
apparatus for explosive gas atmospheres — Part 10: Classification of hazardous areas’, issued by
the International Electrotechnical Commission (IEC).
This edition 3.1 incorporates Amendment No. 1 (March 2000). Side bar indicates modification of
the text as the result of incorporation of the amendment.
IS 5572 : 1994

Indian Standard
CLASSIFICATION OF HAZARDOUS AREAS
(OTHER THAN MINES) HAVING
FLAMMABLE GASES AND VAPOURS FOR
ELECTRICAL INSTALLATION
( Second Revision )
1 SCOPE b) Petroleum or any flammable liquid having flash
point above 65°C where likely to be refined,
This standard provides guidance on the blended, handled or stored at or above its flash
classification of areas where flammable gas or point.
vapour risks may arise in order to permit the 2 For the purposes of this standard an area is a three-
proper selection of electrical apparatus for use dimensional region or space.
in such areas ( see Note 1 ). 3 Normal atmospheric conditions include variations
above and below reference levels of 101.3 kPa (1 013
It is intended for application in all industries mbar) and 20°C provided the variations have a
where there may be a risk due to the presence negligible effect on the explosion properties of the
of flammable gas or vapour, mixed with air flammable materials.
under normal atmospheric conditions ( see 4 Catastrophic failure in this context is applied, for
example, to the rupture of a process vessel or pipeline.
Note 2 ), but does not apply to:
5 In any plant installation irrespective of size there may
a) mining applications; be numerous sources of ignition apart from those
b) processing and manufacture of explosives; associated with electrical apparatus. Additional
precautions may be necessary to ensure safety in this
c) areas where risks may arise due to the aspect but these are outside the scope of this standard.
presence of ignitable dusts or fibres;
d) catastrophic failures, which are beyond 2 TERMINOLOGY
the concept of abnormality dealt with in 2.1 Explosive Gas Atmosphere
this standard ( see Note 4 ); and A mixture with air, under normal atmospheric
e) ignition sources other than those conditions, of flammable materials in the form
associated with electrical apparatus of gas, vapour, or mist, in which, after ignition,
( see Note 5 ). combustion spreads througout the unconsumed
f) areas where pyroforic substances are mixture.
handled. NOTES
This standard does not take into account the 1 This definition specifically excludes dusts and fibres
in suspension in air.
effects of consequential damage.
2 Although a mixture which has a concentration above
Definitions and explanations of terms are given the upper explosive limit (UEL) is not an explosive gas
together with the main principles and atmosphere, in certain cases for area classification
procedures relating to area classification. purposes it is advisable to consider it as an explosive gas
atmosphere.
The objective of area classification is the
2.2 Hazardous Area
notional division of a plant into zones within
which the likelihood of the existence of an An area in which an explosive gas atmosphere
explosive gas/air mixture is judged to be high, is present, or likely to be present, in quantities
medium, low or so low as to be regarded as such as to require special precautions for the
negligible. An area classification established in construction, installation and use of electrical
this way provides a basis for the selection of apparatus.
electrical apparatus that is protected to a 2.3 Non-hazardous Area
degree appropriate to the risk involved. The
type of protection of the apparatus selected will An area in which an explosive gas atmosphere
be such that the likelihood of it being a source is not expected to be present in quantities such
of ignition, at the same time as the surrounding as to require special precautions for the
atmosphere is explosive, is accepted as being construction, installation and use of electrical
small. apparatus.
NOTES 2.4 Zones
1 Flammable materials for the purpose of area
classification include: Hazardous areas are classified in zones based
a) Petroleum having flash point below 65°C or any upon the frequency of the appearance and the
flammable gas or vapour in a concentration duration of an explosive gas atmosphere as
capable of ignition. follows.
1
IS 5572 : 1994

2.4.1 Zone 0 2.12 Flash Point


An area in which an explosive gas atmosphere The temperature at which the liquid gives so
is present continuously or is present for long much vapour that this vapour, when mixed
periods. with air, forms an ignitable mixture and gives a
2.4.2 Zone 1 monetary flash on application of a small pilot
flame under specified conditions of test.
An area in which an explosive gas atmosphere
2.13 Boiling Point
is likely to occur in normal operation.
The temperature of a liquid boiling at an
2.4.3 Zone 2
ambient pressure of 101.3 kPa (1 013 mbar).
An area in which an explosive gas atmosphere NOTE — For liquid mixtures the initial boiling point
is not likely to occur in normal operation and if should be used.
it does occur it will exist for a short period only. ‘Initial boiling point’ is used for liquid mixtures to
indicate the lowest value of the boiling point for the
2.5 Normal Operation range of liquids present.
The situation when the plant equipment is 2.14 Ignition Temperature
operating within its design parameters.
The lowest temperature at which ignition
Minor releases of flammable material may be occurs in a mixture of explosive gas and air
part of normal operation. For example, releases when the method of testing ignition
from seals which rely on wetting by the fluid temperatures specified in relevant Indian
being pumped are considered to be minor Standard is followed.
releases.
2.15 Source of Release
Failures (such as the breakdown of pump seals,
flange gaskets or spillages caused by accidents) A source of release is a point or location from
which involve repair or shut-down are not which a gas, vapour, mist or liquid may be
considered to be part of normal operation. released into the atmosphere so that a
hazardous atmosphere could be formed.
2.6 Explosive Limits
2.16 Adequate Ventilation
2.6.1 Lower Explosive Limit ( LEL )
Adequate ventilation is that which is sufficient
The concentration of flammable gas, vapour or to prevent accumulations of significant
mist in air, below which an explosive gas quantities of gas-air mixtures in concentration
atmosphere will not be formed. over one-fourth of the lower flammable limit.
2.6.2 Upper Explosive Limit ( UEL ) Adequately ventilated area could be naturally
ventilated or artificially ventilated.
The concentration of flammable gas, vapour or
mist in air, above which an explosive gas 2.17 Protected Fired Vessel
atmosphere will not be formed. Any fired vessel that is provided with
2.7 Relative Density of a Gas or a Vapour equipment, such as flame arrestors, stack
temperatures shutdowns, forced draft burners
The density of a gas or a vapour relative to the with safety controls and spark arrestors,
density of air at the same pressure and at the designed to eliminate the air intake and
same temperature. (Air is equal to 1.0.) exhaust as sources of ignition.
2.8 Flammable Material 2.18 Pressurized Room
Material consisting of flammable gas, vapour, A room which has been made safe by
liquid and/or mist, see 5. pressurizing or purging with a plenum of safe
2.9 Flammable Gas or Vapour atmosphere by keeping minimum 25 Pa more
pressure than that of surrounding atmosphere
Gas or vapour which, when mixed with air in with all doors and windows closed.
certain proportions, will form an explosive gas
atmosphere. 3 GENERAL
2.10 Flammable Liquid Area classification is a method of analyzing and
classifying the environment where explosive
A liquid capable of producing a flammable gas atmospheres may occur to allow the proper
vapour or mist under any forseeable operating
selection of electrical apparatus to be installed
conditions.
in that environment.
2.11 Flammable Mist
The object of the classification procedure is to
Droplets of flammable liquid, dispersed in air, enable electrical apparatus to be operated
so as to form an explosive atmosphere. safely in these environments.

2
IS 5572 : 1994
Where it is necessary to use electrical — Failure of process, storage or other
apparatus in an environment in which there equipment is likely to cause an electrical
may be an explosive gas atmosphere and it is system failure simultaneously with the
not possible to: release of flammable gas or liquid.
a) eliminate the likelihood of an explosive — Flammable liquid or vapour piping
gas atmosphere occurring around the system (containing valves, meters or
source of ignition, or screwed or flanged fittings) is in an
b) eliminate the source of ignition; inadequately ventilated area.
then measures should aim at reducing the — The area below the surrounding elevation
likelihood of the occurrence of either or both of or grade is such that flammable liquids or
the above factors so that the likelihood of vapours may accumulate therein.
coincidence is so small as to be acceptable. This classification typically includes:
In most practical situations where flammable — Imperfectly fitting peripheral seals on
materials are used it is difficult to ensure that floating roof tanks.
an explosive gas atmosphere will never occur. It
— Inadequately ventilated pump rooms for
may also be difficult to ensure that electrical
apparatus will never give rise to a source of flammable gas or for volatile, flammable
liquids.
ignition. Therefore in situations where an
explosive gas atmosphere has a high likelihood — Interiors of refrigerators and freezers in
of occurring, reliance is placed on using which volatile flammable materials are
electrical apparatus which has an extremely stored in lightly stoppered or easily
low likelihood of creating a source of ignition. ruptured containers.
Conversely where the likelihood of an explosive — API separators.
gas atmosphere occurring is reduced, electrical — Oily waste water sewer/basins.
apparatus which has an increased likelihood of
becoming a source of ignition may be used. To
apply this approach the first step is to assess 4.1.3 Zone 2 Areas
the likelihood of an explosive gas atmosphere Zone 2 locations may be distinguished when
occurring in accordance with the definitions of any one of the following conditions exist:
Zone 0, Zone 1 and Zone 2. The following
clauses give guidance of this first step, namely — The system handling flammable liquid or
on the classification of areas in which there vapour is in an adequately ventilated area
may be an explosive gas atmosphere into and is so designed and operated that the
Zones 0, 1 and 2. explosive or ignitable liquids, vapours or
gases will normally be confined within
4 CLASSIFICATION OF HAZARDOUS closed containers or closed systems from
AREA which they can escape only during
4.1 To determine the type of electrical abnormal conditions such as accidental
installation appropriate to a particular failure of a gasket or packing.
situation, the hazardous areas have been — The flammable vapours can be conducted
divided into three zones, namely, Zone 0, to the location as through trenches, pipes
Zone 1 and Zone 2, according to the degree of or ducts.
probability of the presence of hazardous — Locations adjacent to Zone 1 areas.
atmosphere. Typical examples of such
classifications are given below. — In case of use of positive mechanical
ventilation, as the failure or abnormal
4.1.1 Zone 0 Areas operation of ventilating equipment can
Examples are vapour space above closed permit atmospheric vapour mixtures to
process vessels, storage tanks or closed build up to flammable concentrations.
containers, areas containing open tanks of
volatile, flammable liquid. 4.2 Areas not Classified
4.1.2 Zone 1 Areas In general, the following locations are
Zone 1 locations may be distinguished when considered safe from the point of view of
any of the following conditions exits: electrical installation:
— Flammable gas or vapour concentration is a) Areas where the piping system is without
likely to exist in the air under normal valves, fittings, flanges or similar
operating conditions. appurtenances.
— Flammable atmospheric concentration is b) Areas where flammable liquids or vapours
likely to occur frequently because of are transported only in suitable
maintenance, repairs or leakage. containers or vessels.

3
IS 5572 : 1994
c) Areas where permanent ignition sources because of their low relative density and will
are present like area where combustion not usually affect as wide an area as the
gases are present, for example flare tips, liquefied petroleum gases.
flare pits, other open flames and hot 5.1.2 Liquefied petroleum gases include
surfaces. propane, butane and mixtures thereof having
d) Enclosed premises in which a plenum or densities from 1.5 to approximately 2.0 times
purging stream of safe atmosphere is that of air. Vapour pressures exceed
continuously maintained, so that no 2.81 kg/cm2 at 37.8°C.
opening therein may be a point of ingress 5.1.2.1 These gases in their liquefied state are
of gases or vapours coming from an highly volatile and have low boiling
external source of hazard. temperature so that they readily pick up heat
e) Gas turbine installation meeting creating large volumes of vapour. They should
requirements of Annex A. be treated very conservatively in considering
f) Diesel Generator room/shed having the extent of areas affected, especially since the
adequate ventilation. heavy vapours travel along the ground for long
g) Oil/gas fired boilers installations. distances if air currents do not assist diffusion.
Consideration should be given, however, 5.1.3 Flammable liquids vary in volatility and
to potential leak sources in pumps, valves, have a flash point below 93°C and a vapour
etc, or in waste product and fuel lines pressure not exceeding 2.81 kg/cm2 at 37.8°C.
feeding flame or heat producing These are divided into three classes, as follows:
equipment to avoid installing electrical
devices which could then become primary Class A Flammable liquids having flash
ignition sources for such leaks. point below 23°C
NOTES Class B Flammable liquids having flash
1 A protected fired vessel is not considered a source of point 23°C and above but
ignition and the surrounding area is classified the same below 65°C
as for a hydrocarbon pressure vessel.
Class C Flammable liquids having flash
2 The area around the fired components and exhaust
outlets of unprotected fired vessels need not be
point 65°C and above but
classified from the standpoint of installation of electrical below 93°C
equipment.
Densities of the saturated vapours of these
3 Lack of classification around unprotected fired vessels flammable liquids at ordinary atmospheric
does not imply the safe placement of fired vessels in the
proximity to other production equipment because temperatures are generally less than 1.5 times
unprotected fired vessels are themselves sources of that of air.
ignition.
5.1.3.1 Class A liquids may produce large
4 The area around a flare tip or flare pit need not be volumes of vapour when released in
classified from the stand point of installation of
electrical equipment. appreciable quantities to the open.
5 For example, electrical equipment may be exposed to 5.1.3.2 Class B liquids are heavier and less
flammable gas during a purge cycle of a fired heater or volatile than gasoline, but have flash point at
furnace. The lack of classification around unprotected or slightly below normal ambient air
fired vessels and flare tips does not imply the safe
placement of fired vessels and flare tips in the proximity temperatures. Few commercial products are in
to other equipment because unprotected fired vessels this class, although in a refinery some stocks in
and flare tips are themselves sources of ignition. the process of refining will be of Class B. At
5 PROPERTIES OF FLAMMABLE normal storage temperature such oils release
vapour slowly and are hazardous only near the
MATERIAL
surface of the liquid. At elevated temperatures
5.1 Flammable substances, the potential Class B liquids approach the characteristics of
release of which shall be considered in area Class A liquids in vapour release.
classification for electrical installations, include 5.1.3.3 Class C includes a broad range from
non-liquefiable gases (permanent gases or fixed cleaners’ solvent to heavy fuel oil in commercial
gases), liquefied petroleum gases and vapours grades. The degree of hazard is low because the
of flammable liquids. rate of vapour release is nil at normal ambient
5.1.1 Non-liquefiable gases commonly temperatures of handling and storage. When
encountered include methane and its mixtures vapours from heated Class C products in
with small quantities of the process are released to the atmosphere, the
low-molecular-weight hydro-carbons, the chance of ignition by electrical equipment is not
mixtures being generally lighter than air. as great as in case of Class A or Class B liquids
Hydrogen, because of its properties, shall be because vapour either condense rapidly or
given special consideration. ignite spontaneously.
5.1.1.1 Non-liquefiable gases released from an 5.1.3.4 Normally, Class A and Class B liquids
opening of given size will dissipate rapidly will produce vapours considered to be in the
4
IS 5572 : 1994
flammable range for electrical design purposes. If there is a possibility of large release of
Class C liquids having a flash point below 93°C volatile products, the Zone 2 area may be
should be considered as producing flammable further extended horizontally beyond 16
vapours when handled, processed or stored m up to 32 m with a height of 0.63 m.
under such conditions that the temperature of In case of petroleum pipelines where well-
the liquid, when released to the atmosphere, maintained valves, fittings, and meters of
would exceed its flash point. a pipeline system transporting petroleum
6 EXTENT OF HAZARDOUS AREA (crude oil, products, and gases) are
installed in well-ventilated situations or
6.1 General Consideration in a pit, the extent of the Zone 2 area
6.1.1 In the absence of wall, enclosures, or above ground may be reduced to 4 m in all
other barriers, and in the absence of air directions from the possible source of
currents or similar disturbing forces, gases and hazard, although the pit itself should be
vapours disperse in all directions as governed classified as Zone 1 area.
by the vapour density and velocity, for example, NOTE — Any trench of pit below ground level and
heavier-than-air vapour disperse principally located within the area defined above should be
downward and outward and lighter-than-air classified as Zone 1 area.
vapours principally upward and outward. Thus, b) Zone 1 classification If the source of
if the source of hazard were a single point, the hazard gives rise to a hazardous
horizontal area covered by the vapour would be atmosphere under normal operating
a circle. conditions, the area described in 6.2.1 (a)
6.1.2 For vapours released at or near ground as Zone 2 should be classified as Zone 1.
level, the areas where potentially hazardous In the event of an enclosed premises not
concentrations are most likely to be found are containing a source of hazard but situated
below ground, those at ground are next most within either a Zone 1 or Zone 2 area the
likely, and, as the height above ground inside of the premises should be classified
increases, the potential hazard decreases. as Zone 1 unless separated from the
NOTE — For lighter-than-air gases the opposite is true, outside hazardous area by a fire wall.
there being little or no potential hazard at and below
ground and greater potential hazard above ground. 6.2.2 Enclosed Premises and Surrounding
6.1.3 Elevated or depressed sources of release Areas
will alter the areas of potential hazard. a) Zone 2 classification Figure 3 illustrates
6.1.4 Effect of Air Current the situation when a source of hazard
which may give rise to a hazardous
Air currents may substantially alter the outline atmosphere under abnormal conditions is
of the limits of potential hazard. A very mild located within enclosed premises. The
breeze may serve to extend the area in those whole of the inside of the building should
directions to which vapours might normally be be classified as Zone 1, as rapid dispersal
carried. However, a stronger breeze may so of hazardous atmosphere may not be
accelerate the dispersion of vapours that the expected due to lack of ventilation.
extent of potentially hazardous area would be
greatly reduced. The Zone 2 area shall extend 16 m
horizontally from the source of hazard and
6.2 Heavier-than-Air Gases and Vapours 8 m vertically from the ground level. If the
6.2.1 Open-Air Situations area covered above does not contain the
area 3 m past the perimeter of the
a) Zone 2 classification Figures 1 and 2
building, the Zone 2 area shall be
illustrate the situation when a source of
extended in such a way that this area is
hazard which may give rise to a hazardous
covered. In case of unpierced vapour-tight
atmosphere only under abnormal
walls, the area 3 m past perimeter need
conditions is located in the open air. The
not be considered within Zone 2 area.
hazardous area should in this case be
classified as Zone 2. For heavier-than-air If there is a possibility of large release of
gases and vapours the classified volatile products, Zone 2 area may be
hazardous area shall extend vertically 8 m further extended horizontally beyond
above the source of hazard and 16 m up to 32 m with height of 0.63 m.
horizontally 16 m in all direction from the NOTE — Any trench or pit below ground level and
source of hazard. Beyond 8 m from the located within the area defined should be classified as
source of the hazard in the horizontal Zone 1 area.
plane the vertical extent of the Zone 2 b) Zone 1 classification If the source of
area may be reduced to 8 m above ground hazard within the enclosed premises gives
level.
5
IS 5572 : 1994

FIG. 1 FREELY VENTILATED PROCESS AREA (SOURCE OF HAZARD LOCATED NEAR GROUND LEVEL)

FIG. 2 FREELY VENTILATED PROCESS AREA (SOURCE OF HAZARD LOCATED ABOVE GROUND LEVEL)

rise to hazardous atmosphere under normal the roof and within the shell or the tank should
conditions, the area within the building be classified as Zone 1.
should be classified as Zone 1 and the area The area surrounding the tank should be
described in 6.2.2 (a) as Zone 2 should be classified as Zone 2. It shall extend vertically
classified as Zone 1. 3 m above the tank or shall be horizontally 3 m
When the building has a ridge type roof with from it. If there is a dike on one side of the
ventilators and not a sealed roof as shown in tank, the Zone 2 area should extend up to the
Fig. 3, special consideration is necessary in dike, the vertical extension from the ground
connection with the vertical extent of the level being the same as the height of the dike.
hazardous area.
6.2.3 Storage Tanks In the case of fixed-roof tanks, the area
surrounding the tank shown in Fig. 4 as Zone 2
Figure 4 illustrates the classification of the should be classified as Zone 1. However, in case
area surrounding a floating-roof tank under of fixed roof tanks which breathe into closed
normal operating conditions. The space above system and not to atmosphere (during

6
IS 5572 : 1994
filling/emptying) area surrounding the tank Zone 1 area.
shall be classified as Zone 2 as shown in Fig. 4.
NOTE — Any trench or pit below ground level and
6.2.4 Figures 5 to 11 give some typical area
located within the area defined should be classified as classification details.

FIG. 3 PROCESS AREA WITH RESTRICTED VENTILATION

FIG. 4 TANK WITH FLOATING ROOF

7
IS 5572 : 1994

FIG. 5 PRESSURE STORAGE TANK

FIG. 6 COOLING TOWER-HANDLING PROCESS COOLING WATER

8
IS 5572 : 1994

FIG. 7A TANK CAR/TANK TRUCK LOADING AND UNLOADING VIA


CLOSED SYSTEM. BOTTOM PRODUCT TRANSFER ONLY

FIG. 7B TANK CAR/TANK TRUCK LOADING AND UNLOADING VIA


OPEN SYSTEM. BOTTOM PRODUCT TRANSFER ONLY
9
IS 5572 : 1994

FIG. 8A TANK CAR/TANK TRUCK LOADING AND UNLOADING VIA


CLOSED SYSTEM. TRANSFER THROUGH DOME ONLY

FIG. 8B TANK CAR/TANK TRUCK LOADING AND UNLOADING VIA


CLOSED SYSTEM. TRANSFER THROUGH DOME ONLY

10
IS 5572 : 1994

FIG. 9 TYPICAL DRUM DISPENSING INSTALLATION

FIG. 10 TYPICAL VENT INSTALLATION

FIG. 11 BALL OR PIG LAUNCHING OR RECEIVING INSTALLATION IN


A NON-ENCLOSED ADEQUATELY VENTILATED AREA

11
IS 5572 : 1994

6.3 Lighter-than-Air Gases and Vapours hazard. The hazardous areas are shown in
6.3.1 Definition of Lighter-than-Air Gases and Fig. 14.
Vapours 6.3.2.4 Source of hazard located outside
Where a substantial volume of gas or vapour is enclosure with one side open
released into the atmosphere from a localized In this case the area within the enclosed
source, a vapour density less than one, that is, premises above the opening is Zone 1 whereas
lighter-than-air, for the combustible indicates the rest of the enclosed premises form a Zone 2
the gas or vapour will rise in a comparatively area. The area outside the enclosure is
still atmosphere. A vapour density greater than classified as stated in 6.3.2.1. The hazardous
one, that is heavier-than-air, indicates the gas area is shown in Fig. 15.
or vapour will tend to sink, and may thereby
spread some distance horizontally and at a low
level. The latter effects will increase with
compounds of greater vapour density.
In process industries, the boundary between
compounds which may be considered
lighter-than-air is set at a vapour density of
0.75. This limit is chosen so as to provide a
factor of safety for these compounds whose
densities are close to that of air, and where
movement may not therefore, be predicted
without a detailed assessment of local
conditions.
6.3.2 Basic Extent of Hazardous Area for a
Source of Hazard Located in Open Air
6.3.2.1 The hazardous area surrounding a point
of hazard located in the air is a cylinder with
radius 4.5 m whose axis passes vertically
through the source of hazard. Its height is 8 m
above and 4.5 m below the source of hazard. If
the source of hazard is situated at a height less
than 4.5 m above ground, the height of the
hazardous area extends below the source of
hazard up to ground level. This is illustrated in
Fig. 12. The entire area is Zone 2.
6.3.2.2 Source of hazard located inside enclosed
premises with restricted ventilation — Openings
on top and bottom
In this case the entire area within the enclosed
premises is a Zone 1 area and the extremities of
the openings are considered as source of
hazard. The hazardous areas are shown in
Fig. 13.
6.3.2.3 Source of hazard located inside enclosed
premises with restricted ventilation — Openings
on sides
In this case the entire area within the enclosed
premises is a Zone 1 area and the extremities of
FIG. 12 POINT OF HAZARD IN THE AIR
the openings are considered as sources of

12
IS 5572 : 1994

FIG. 13 SOURCE OF HAZARD LOCATED INSIDE ENCLOSED PREMISES WITH RESTRICTED


VENTILATION (OPENINGS ON TOP AND BOTTOM)

13
IS 5572 : 1994

FIG. 14 SOURCE OF HAZARD LOCATED INSIDE ENCLOSED PREMISES WITH RESTRICTED


VENTILATION (OPENINGS ON SIDES)

14
IS 5572 : 1994

FIG. 15 SOURCE OF HAZARD LOCATED OUTSIDE THE ENCLOSURE WITH ONE SIDE OPEN

15
IS 5572 : 1994
ANNEX A
[ Clause 4.2(e) ]

GAS TURBINE INSTALLATIONS

A-1 INTRODUCTION b) The fuel gas pipe to each turbine hood


A-1.1 This Annex applies to gas fired turbine should have no more than one pair of
installations. flanges inside the turbine room. All other
equipment as valves, connections, filters,
A-1.2 If the turbine is equipped with an drip pot, etc, have to be located either:
acoustic hood or other enclosure containing
— outside the turbine room
parts of the fuel gas system, this enclosure
should be defined as the turbine hood. — inside an enclosure separately
ventilated
A-1.3 If the turbine, with or without a turbine
hood, is located in an enclosed area, this area — inside the turbine hood provided a
should be defined as the turbine room. special ventilation of turbine hood
— inside turbine hood, provided a special
A-2 AREA CLASSIFICATION OF THE fuel gas supply arrangement as
TURBINE ROOM described in A-4
A-2.1 In order to classify the turbine room as A-2.2 The turbine room may be classified as
non-hazardous, the following requirements Zone 1 or Zone 2 if the arrangement is not in
should both be fulfilled: compliance with the requirements stated
a) The turbine room should be adequately in A-2.1 or due to other sources of hazard
ventilated that is at least 12 air changes outside the turbine hood. The turbine or any
per hour with proper ventilation patterns. associated equipment including exhaust piping,
The ventilation system should be should not have a surface temperature above
arranged so that an over-pressure of at 200°C or above 80 percent of the ignition
least 50 Pa (0.5 mbar) is maintained in the temperature for the actual gas/air mixture in
turbine room with respect to the inside of the classified area without special precautions.
the turbine hood and any surrounding
classified areas with openings to the A-3 VENTILATION OF THE TURBINE
turbine room. A pressure switch should be ROOM
installed in order to give an alarm if the A-3.1 The turbine hood for a gas fired turbine
differential pressure drops below 50 Pa should be adequately ventilated with respect to
(0.5 mbar).

FIG. 16 GAS TURBINE ARRANGEMENT


16
IS 5572 : 1994
the removal of heat from the machinery and area inside the hood will be regarded as zone 2
dilution of flammable gas. The air should be area and accordingly all equipment inside the
taken from non-hazardous area. hood have to meet Zone 2 requirement. The
A-3.2 If the area outside the turbine hood is equipment which has to be alive after a shut
classified as non-hazardous, the ventilation down or stop of ventilation of the hood, should
system should be arranged so that an meet Zone 1 requirement. This for instance
under-pressure of at least 50 Pa (0.5 mbar) is applies to trace heater, post lubrication pumps,
maintained inside the turbine hood with etc. The post lubrication pumps should be
respect to the outside. This differential supplied from emergency power sources to
pressure may be the combined effect of the operate after a shutdown in order to prevent
under-pressure inside the turbine hood and the overheating of the bearings. Overheating may
over-pressure in the turbine room. ignite flammable vapour or gas inside the hood.
A-3.3 If the area outside the turbine hood is A-4.3 The Turbine has Exposed Surfaces
Zone 2 and the turbine hood contains any with Temperatures Above 200°C
source of ignition such as a surface with If the actual flammable gas ignition
temperature above 200°C, or above 80 percent temperature can be tested and a statement can
of the ignition temperature for the actual be made that the surface temperature of the
gas/air mixture the ventilation system of the turbine will not exceed 80 percent of the
turbine hood should be arranged so that an ignition temperature, the same situation as
over-pressure of at least 50 Pa (0.5 mbar) is described in A-4.2 above exists.
maintained inside the hood with respect to the A-4.4 The Turbine has exposed Surfaces
outside. with Temperature above 80 Percent of the
A-3.4 In both situations described above a Ignition Temperature of the Actual
pressure switch should be installed in order to Flammable Gas or the Electrical
give an alarm and shutdown after time delay if Equipment inside the Hood which will be
the differential pressure drops below 50 Pa Alive as the Turbine is Running does not
(0.5 mbar). Meet Zone 2 Requirement
A-3.5 The number of leakage sources under the The hood then should be ventilated with
turbine hood should be kept to a minimum. sufficient number of air changes per hour to
However, a manufacturer may require some make a highly efficient dilution of any
leak-prone equipment to be located inside the hazardous gas leakage inside the hood. The
turbine hood. The number of air changes required ventilation rate depends on the
required depends upon the probable sources of leakage sources inside the hood and should be
leakage, the surface temperature of the sufficient to keep the internal atmosphere
machine, etc. Examples are given in A-4. below an average of 20 percent of the lower
A-3.6 As an alternative to ventilation of the explosion limit. Ninety air changes per hour is
turbine-hood during shutdown of the turbine, regarded as a minimum. In addition to the
Halon may be injected. normal ventilation system a 100 percent spare
stand-by fan supplied from a continuous power
A-3.7 Provided electrical equipment inside the source should be provided. If the ordinary
hood which does not meet zone requirement, ventilation fails the spare fan should be
the turbine hood should be pre-purged with at automatically activated and an alarm be given
least 5 air changes before starting the turbine in the control room. As an alternative to
or energizing any electrical equipment not ventilation of the turbine-hood during
suitable for Zone 1 area. shutdown of the turbine, HALON may be
A-3.8 The fan used for pre-purging should meet injected.
Zone 1 and should be equipped with a starter A-4.5 During a shut-down, the turbine hood
suitable for Zone 1 or a starter located in an may be classified as non-hazardous due to
area remaining non-hazardous during special arrangement of the fuel gas supply
shutdown. system. A system called “Block and Bleed” is
A-4 AREA CLASSIFICATION OF THE described on Fig. 17. A shut down signal will
TURBINE HOOD close valve No. 1 and open valve No. 2. The
A-4.1 The combination of ventilation, fuel gas three way valve will open from the gas
system arrangement, temperature on exposed distribution manifold to the flare. The fuel gas
surfaces, electrical equipment inside the lines within the turbine room and the turbine
turbine hood, etc, should be considered to hood will then be depressurized. The
evaluate the safety of the turbine hood. The probability of gas escape inside the hood may
safety principles will be elucidated by some of then be regarded as minor. In case of a leak
the most common turbine/turbine hood designs. only small quantities of gas will escape. This
arrangement does not reduce the requirements
A-4.2 No Exposed Surface of the Turbine to ventilation while the turbine is running.
Inside the Hood will have a Temperature
Above 200°C During Operation A-5 DETECTION OF ESCAPED GAS
Provided the ventilation system provides at A-5.1 Gas detectors should be installed inside
least 12 air changes per hour, the hood should the turbine hood. Normally, the turbine should
be considered as adequately ventilated. The shut down if gas is detected inside the hood.
17
IS 5572 : 1994

FIG. 17 BLOCK AND BLEED SYSTEM

A-5.2 The location of the detectors should be b) The ventilation stops and inert gas (for
chosen with special care being aware of possible example Halon) is released upon detection
gas pockets, air flow patterns, etc. of gas inside the hood.
Other alternatives may be considered
A-5.3 Concerning ventilation arrangement,
depending on the actual installation.
several alternatives exist in case of a shut down
due to gas detection inside the hood. A-6 ADDITIONAL RECOMMENDATIONS
a) The ventilation of the turbine hood A-6.1 The shut down of ventilation system
continues until hot surfaces have been should correspond to the fire and gas detection
cooled to a temperature below 80 percent system and the fire extinction system installed
of the ignition temperature of the gas-air in the turbine hood and turbine room.
mixture which is present. The ventilation Accordingly, other arrangements than those
system that will be in operation after a described in this standard may give an
shut down should be supplied from an equivalent level of safety.
emergency power source with sufficient A-6.2 Ventilation and combustion air should be
capacity. taken from non-hazardous areas.

18
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.

Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards


Amendments are issued to standards as the need arises on the basis of comments. Standards are also
reviewed periodically; a standard along with amendments is reaffirmed when such review indicates that no
changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of
Indian Standards should ascertain that they are in possession of the latest amendments or edition by
referring to the latest issue of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.
This Indian Standard has been developed from Doc : No. ET 22 (3194)

Amendments Issued Since Publication


Amend No. Date of Issue
Amd. No. 1 March 2000

BUREAU OF INDIAN STANDARDS


Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002. Telegrams: Manaksanstha
Telephones: 323 01 31, 323 33 75, 323 94 02 (Common to all offices)
Regional Offices: Telephone
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg  323 76 17

NEW DELHI 110002  323 38 41
Eastern : 1/14 C. I. T. Scheme VII M, V. I. P. Road, Kankurgachi  337 84 99, 337 85 61

KOLKATA 700054  337 86 26, 337 91 20
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022  60 38 43

 60 20 25
Southern : C. I. T. Campus, IV Cross Road, CHENNAI 600113  235 02 16, 235 04 42

 235 15 19, 235 23 15
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)  832 92 95, 832 78 58

MUMBAI 400093  832 78 91, 832 78 92
Branches : A H M E D A B A D . B A N G A L O R E . B H O P A L . B H U B A N E S H W A R . C O I M B A T O R E .
FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR.
LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISHAKHAPATNAM.

You might also like