You are on page 1of 2

Annual Performance of Solar Air Conditioning

Direct Solar Absorbed Solar Absorption Cooling Load Cooling Load % of Cooling Load
Month Provided by Remarks
Radiation Radiation Chillers FLH/Month Absorption Chillers

Kwh/m2 Kwh Ton-Hr FLH Ton-Hr

Jan 133.67 617,881 226,633 194.7 4,867,444 4.7%


Feb 109.13 504,429 185,019 156.8 3,918,804 4.7%
Mar 136.66 631,693 231,699 227.3 5,683,735 4.1%
Apr 112.90 521,864 191,415 259.9 6,496,587 2.9%
May 142.80 660,083 242,112 343.7 8,591,561 2.8%
Jun 125.92 582,039 213,486 441.0 11,026,048 1.9%
Jul 99.58 460,280 168,826 482.8 12,070,704 1.4%
Aug 126.52 584,835 214,512 507.5 12,686,328 1.7%
Sep 126.48 584,650 214,444 461.4 11,535,280 1.9%
Oct 152.27 703,830 258,158 386.9 9,672,037 2.7%
Nov 151.86 701,962 257,473 290.9 7,272,169 3.5%
Dec 125.24 578,919 212,342 212.1 5,303,513 4.0%

Total 1,543.02 7,132,464.89 2,616,116.80 3,965 99,124,212 2.64%


Notes:
1- Solar data is a typical year field collected data.
2- Cooling Energy is field collected data.

Peak Cooling Load Demand = 25,000 Ton


Solar Collector Area 10,272 m2
Double Effect (DE) Absorption COP= 1.29 % of Total cooling Capacity
DE Absorption chillers' capacity= 1,250 Ton 5.0%