Job N. SC0049
PIPELINE PROJECT
DOCUMENT TITLE:
3 15/06/07 Issue for Construction Delia Santilli Marco De Giorgi Vieri Cerchia
2 14/03/07 Issue for Construction Delia Santilli Marco De Giorgi Vieri Cerchia
1 12/02/07 Issue after comments Delia Santilli Marco De Giorgi Vieri Cerchia
0 04/10/06 Issue for Approval Delia Santilli Marco De Giorgi Vieri Cerchia
REV. DATE REASON FOR ISSUE PREPARED CHECKED APPROVED KTI
Document No.: SC0049YHF00000 Rev. 3
INDEX
01 - SCOPE .........................................................................................................................6
01-01 - ABBREVIATIONS.................................................................................................7
02 - REFERENCE DOCUMENTATION...............................................................................9
03 - TEST’S METHODOLOGY..........................................................................................14
C6 - ACCESSORIES CHECK......................................................................................................................... 51
F2 - INTEGRATED TEST OF THE CORRECTNESS OF DATA BASE AND TAG ASSIGNMENT AND OF
THE ADDRESSING OF INPUT/OUTPUT SIGNALS UP TO EXTERNAL TERMINAL STRIPS ................... 68
F8 - REPORTS TEST...................................................................................................................................... 76
07 - 02 - SYSTEM DIAGRAM..........................................................................................97
01 01 - SCOPE
Scope of this document is to ensure that all the equipment and related engineering carried
out by Invensys Foxboro SCADA for the integrated Supervisory Control And Data
Acquisition (SCADA)/ESD and Telecommunication System for the East Mediterranean Gas
(EMG) Pipeline project, fully complies with the required specifications; that the whole
system and its components function properly; that all manufacturing, assembly, software
generation and configuration databases have been properly and completely designed.
FAT tests on the SCADA/ESD and Telecommunication System of the EMG Project are
planned to be performed at Program Srl workshop facilities in Pomezia.
This document is also conceived to be the base for the Invensys FSR (Foxboro SCADA
Rome) internal testing activities (PreFAT ) and make evidence of the results of them
(PreFAT-Internal Tests).
Inspection and Test Procedures as well as Test Reports (working sheets) have been
conceived to represent by themselves a track to follow and to use to support and prove
step by step tests acceptance ( Tests Certificates ).
Test Certificates shall have to report all necessary data for their unique identification and
traceability to relevant P.O. items/sub-items.
Scope of each individual test is to demonstrate the compliance of the equipment and
software with the relevant specification and engineering documentation called for.
PreFAT Reports
Prior to start of the FAT, Invensys FSR (Foxboro SCADA Rome) will conduct a pre-FAT
inspection and test of the system.
The results of this pre-FAT will be forwarded to the Company/Contractor to assess the
state of readiness for FAT.
02 02 - REFERENCE DOCUMENTATION
• 30544 000 JSS 1500 01 Rev. 0 “General supply Rules for Automation Systems”
• 30544 000 SP 1511 01 Rev. 0 “Particular Technical Specification for Supply of SCADA System”
• 30544 000 SP 1515 01 Rev. 0 “Particular Technical Specification for Supply of Emergency
Shutdown System (ESD) and Fire & Gas System (FGS)”
• 30544 000 SP 1530 01 Rev. 0 “Particular Technical Specification for Supply of Telecommunication
System”
• ISO 11064-2: Ergonomic design of control centres -- Part 2: Principles for the arrangement of
control suites
• ISO 11064-3: Ergonomic design of control enters: Part 3: Control room layout
• ISO/DIS 9241-3: Ergonomic requirements for office work with visual display terminals (VDTs): Part
3: Visual display requirements.
• RAL F2: Reichsnormen Ausschuss fur Liefersbedingungen (Paint Colour Code)
03 03 - TEST’S METHODOLOGY
A - General
These procedures are applicable to the Factory Acceptance Test (FAT) for the SCADA and
Telecommunication System supplied by Invensys Foxboro SCADA Rome (FSR) under the
contract.
Only one copy of each project document shall be present in the test room during testing.
Such copies shall be identified with the stamp «FAT MASTER».
Any deviation between check-out results and the relevant reference specification will be notified
to the engineer responsible of the testing operations who will report on a Pending Action Report,
taking all necessary corrective actions.
Inspection will not be held but will continue and go through the next test step according to the
scheduled program, unless the deviation affects the next test.
All necessary corrective actions will be implemented in the shortest possible time frame and
without any influence on the test program execution.
The results of such corrective actions will be then checked by performing again the test that was
not passed.
Invensys FSR will test the SCADA and Telecommunication system utilizing a dedicated core
testing team dedicated to the Project.
The core team makeup is comprised of a Lead engineer, full time test engineers and part time
test engineers.
The part–time specialists are to support specialized disciplines, e.g. Standard System Test etc.
The Lead Engineer is responsible for all testing as well as being the main focal point of the FAT
testing. The lead Engineer could not be a daily participant in the testing, but is the coordinator
and leader for the FAT and will be available to address any issue without delay.
There will be a FAT “Fix Team” to be shared across all subsystems’s. Fix team is assigned from
the beginning of FAT through the last post-Fat activities. The amount of rework will dictate the
number of actual fix team personnel.
KTI Contractor will assign one person (and only one) of its testing team as responsible to formally
witness each test.
At the end of each test, KTI and Invensys FSR representatives will fill-out the relevant FAT TEST
REPORT clearly indicating for test result.
The FAT procedure (and test results) will be signed off by Invensys FSR Supplier and Contractor
(KTI) representative at successful conclusion of testing.
As already described at paragraph 01, prior to start the FAT, Invensys FSR will conduct the Pre-
FAT inspections and the tests of the SCADA & ESD & Telecommunication system.
The results of these Pre-FAT inspections and tests will be forwarded to the Contractor to assess
the state of readiness for FAT.
Surveillance Parties
TPKTI KTI
FSR Invensys Foxboro SCADA Rome
PR Program srl
Surveillance Type
P Pending
S Satisfactory
N Not Conforming
TEST PROC.
DESCRIPTION NOTES
No. NO.
TEST PROC.
DESCRIPTION NOTES
No. NO.
22 Review of certificates C2
26 Accessories check C6
TEST PROC.
DESCRIPTION NOTES
No. NO.
49 “Historian” check F7
50 Reports test F8
TEST PROC.
DESCRIPTION NOTES
No. NO.
TEST PROC.
DESCRIPTION NOTES
No. NO.
20 Firewall AT-R750-S
SCOPE
The purpose is to check that the appearance and the internal and external dimensions of the
enclosures (cabinets) are in accordance with and conform to the reference documentation and
approved relevant drawings.
The main purpose of these activities of the FAT is to ensure by visually inspecting, as will be better
detailed in the following detailed test procedures (from B1 to B13), that all of the required SCADA &
ESD/F&G components are installed and are free of damage or manufacturing defects, according with
and conform to the reference documentation and approved drawings.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item shall be visually inspected, covering external appearance, the internal
and external dimensions and general arrangement.
A hardware inventory will be carried out verifying that all the components are installed in the SCADA &
ESD/F&G cabinets and by checking their installation against the approved drawings.
Checking, as better specified in the detailed procedures B1 to B13, will be mainly to include:
• Visual check cabinet structures, according to the approved drawings;
• Structural inspection;
• Verify that SCADA & ESD/F&G cabinets do not present scratches, evident dents, working defects
and
Cabinet and equipment appearance and dimensions shall be in accordance with the relevant approved
drawings.
ACCEPTANCE CRITERIA
Each SCADA & ESD/F&G enclosure (cabinet) and equipment appearance and dimensions shall be in
accordance with the relevant approved drawing.
TEST TOOLS
No specific test tools are required for the visual checks, with the exception of the meter tape measure for
the dimensional checks
SCOPE
The purpose is to check that the mechanical protection degree of the enclosures (cabinets) is in
accordance with the reference specification requirements.
A manufacturer declaration will certify conformity.
OPERATING INSTRUCTIONS
Manufacturer mechanical protection grade declaration and/or certificate shall be checked for
compliance with specification.
Each enclosure (cabinet) item shall be visually inspected for possible evident non conformance to the
requirements called for by the specified mechanical protection grade.
ACCEPTANCE CRITERIA
The certified and assessed mechanical protection grade shall be in accordance to the requirements
specified on applicable specs for the type of equipment under test.
TEST TOOLS
SCOPE
The purpose is to check that a suitable multicore cables clamping system is assembled into the
cabinets.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item in which, according to the reference documents, field and/or
interconnection termination is provided, shall be visually inspected to verify the presence of a suitable
cables clamping system.
ACCEPTANCE CRITERIA
Each and all enclosure (cabinet) including field and/or interconnection termination shall be provided with
a cables clamping system.
The cables clamping system shall be properly positioned and sized to allocate the required multicore
cables.
TEST TOOLS
PROCEDURE
N. A4 A4 - VISUAL CHECK OF THE CONDITION OF PAINTED SURFACES
SCOPE
The purpose shall be basically to check that the external and internal painting colours and surface
finishing correspond to the requirements of the reference specification.
The purpose of this check is also to verify specific painting characteristic of SCADA cabinets like
painting cycle, thickness, etc., where specific painting procedure is required by relevant documents.
OPERATING INSTRUCTIONS
Painted surfaces shall be compared with representative samples either for colour either for surface
finishing and checked for any coating defect.
For standard enclosures (cabinets) manufacturer painting certificate shall be checked for compliance of
coating characteristic with reference specification.
For non standard enclosures/cabinets (if any) coating shall be spot checked by means of scratch test
and a suitable film thickness gauge.
ACCEPTANCE CRITERIA
TEST TOOLS
RAL sample
SCOPE
The purpose is to check that accessibility and removal of individual replaceable type components meet
the expected good engineering and workmanship level.
OPERATING INSTRUCTIONS
Each enclosure (cabinet/console bay) item shall be visually inspected to verify accessibility of individual
components.
One selected sample of each type of replaceable type component shall be disassembled and re-
assembled.
Tag of selected samples shall be recorded on the relevant Test Report.
ACCEPTANCE CRITERIA
TEST TOOLS
PROCEDURE
N. B2 B2 - CHECK OF TERMINAL STRIPS FUNCTIONAL SEPARATION
SCOPE
The purpose is to check that terminal strips arrangement provides functional separation.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item shall be visually inspected to verify the arrangement of terminal strips for
functional separation.
Each enclosure (cabinet) item shall be visually compared, for terminal strips arrangement, with the
relevant approved documentation.
ACCEPTANCE CRITERIA
TEST TOOLS
NOT APPLICABLE
SCOPE
The purpose is to check that provision has been implemented to keep field Intrinsically Safe wiring
separated from non I.S. wiring.
The purpose is also to check that the I.S. wire ducts are properly identified.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item shall be visually inspected to verify the arrangement of the wire ducts for
Intrinsically Safe wiring separation and identification.
Each enclosure (cabinet) item shall be visually compared, for I.S. wire ducts arrangement, with the
relevant approved documentation.
ACCEPTANCE CRITERIA
Wire ducts for I.S. field wiring shall be blue and separated from wire ducts, of a different colour,
provided for non I.S. circuits wiring.
TEST TOOLS
SCOPE
The purpose is to check that wiring separation for various level voltage steps is implemented.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item shall be visually inspected to verify the arrangement of the wire ducts for
various voltage level wiring separation.
Each enclosure (cabinet) item shall be visually compared, for wire ducts arrangement, with the relevant
approved documentation.
ACCEPTANCE CRITERIA
Wire ducts arrangement shall however match with relevant approved documentation.
TEST TOOLS
SCOPE
The purpose is to check that the composition and the identification of the inlet/outlet terminal blocks are
in accordance with the reference documentation.
OPERATING INSTRUCTIONS
Using one copy of the reference documentation as check list, for each cabinet block, visually verify that
the inlet and outlet terminal blocks are arranged according to the relevant interconnection drawings.
Check that inlet and outlet terminal blocks and relevant wiring are labelled in accordance to the
reference documentation.
ACCEPTANCE CRITERIA
All inlet and outlet terminal blocks arrangement shall correspond to the relevant field / interconnection
cable.
Inlet/outlet terminal blocks installed shall cover all field/interconnection cables specified in the reference
documentation.
All inlet and outlet terminal blocks and relevant wiring identification labels shall be in accordance with
the reference documentation.
Percentage of spare terminals shall comply with ref. documentation requirements.
TEST TOOLS
Reference documentation.
SCOPE
The purpose is to check that physical characteristics of wires and cables used in the enclosures
(cabinets) comply with reference specifications and approved documentation.
This check is not applicable to Systems pre-formed standard cables.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) item shall be visually inspected to check the used wires and cables for
physical characteristics.
ACCEPTANCE CRITERIA
Wires and cables shall comply with IEC 332-3 or CEI 20-22 codes and shall be marked accordingly.
Physical characteristics. of wires and cables, like colour and section, shall be in accordance with those
detailed on relevant approved drawings.
All wiring shall be flame retardant as per IEC 60331 and IEC 60332.
As general rule, the section of power supply wires shall not be less then 1,0 mm2.
Power wiring for 230 Vac 50 Hz distribution within the cabinets/panels (for instance, inside the OPF
SCADA Server Cabinet) shall be not less than 2,5 mm2.
TEST TOOLS
Reference documentation.
NOT APPLICABLE
SCOPE
The purpose is to check that physical characteristics of multicore cables with connectors comply with
reference specifications and approved documentation.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
Cables shall comply with approved project documentation, codes and shall be marked accordingly.
Physical characteristics shall be in accordance with those detailed on relevant approved document.
TEST TOOLS .
Reference documentation.
SCOPE
The purpose is to check that space for future expansion is provided in each functional cabinet(s) block
as required by the relevant reference specifications.
OPERATING INSTRUCTIONS
Each functional cabinet(s) block shall be visually inspected to assess the free space available for future
expansions.
ACCEPTANCE CRITERIA
According to the specifications, a 10% installed (terminated) spare shall be provided for all Systems and
all I/Os type.
In addition a 20% spare space shall be guaranteed inside each system cabinet for all Systems and all
I/Os type.
TEST TOOLS .
SCOPE
The purpose is to check that ventilating system is assembled according to the reference specifications
and relevant approved drawings.
Procedure applicable only for cabinets with ventilating system.
OPERATING INSTRUCTIONS
Each enclosure (cabinet) shall be visually inspected to verify the ventilating system arrangement (if
any).
ACCEPTANCE CRITERIA
The ventilating system, natural or forced, shall comply with the relevant approved drawing.
TEST TOOLS .
SCOPE
The purpose is to check existence, continuity, cabling and colour coding of either Safety and screens
reference ground conductors.
The purpose is also to check the resistance of the connections of the metallic parts to the Safety ground
bar.
OPERATING INSTRUCTIONS
Visually check each enclosure (cabinet/console bay) for the existence and colour of Safety and screens
reference ground conductors.
Verify the continuity and measure the resistance between the Safety earthing terminal or contact and
each one of the accessible metal parts intended to be earthed.
ACCEPTANCE CRITERIA
All accessible metal parts shall be connected to the Safety earthing terminal or contact.
The colour of Safety earthing conductors shall be yellow/green.
Measured resistance shall be equal or less then 0.1 ohm.
TEST TOOLS .
SCOPE
Purpose of the test is to verify that the assembling, wiring and general arrangement of enclosures meet
the safety protection requirements as per relevant part of CEI EN 60439-1 code, IV Ed.
OPERATING INSTRUCTIONS
Visually inspect the inside of the enclosure (cabinet) to verify that all live and rotating parts (if any) are
protected against the possibility of direct contacts.
Perform a dielectric withstand test between input/output terminals/connector pins and both safety and
screens ground in common, according to CEI EN 60439-1 Tab.10&11, as follows:
Main circuits
1000 Vac for 5 sec. on circuits with nominal working voltage from 0 to 60 V
2000 Vac for 5 sec. on circuits with nominal working voltage from 60 to 300 V
Auxiliary circuits
250 Vac for 5 sec. on circuits with nominal working voltage from 0 to 12 V
500 Vac for 5 sec. on circuits with nominal working voltage from 12 to 60 V
2*Vn+1000 Vac (min. 1500) for 1 sec. on circuits with nominal working voltage above 60 V
As an alternative to the dielectric withstand test, the insulation resistance test can be carried out
applying a test voltage of 500 Vdc, according to CEI EN 60439-1, par.8.3.4.
ACCEPTANCE CRITERIA
All active parts inside the enclosure (cabinets) shall have a safety protection grade of at least
IP20/IPXXB (EN 60529).
There shall be no unintentional flashover or breakdown of the insulation during the dielectric withstand
test.
If the insulation resistance test is carried out, the measured resistance (in ohms) shall not be less then
1000 times the circuits nominal working voltage.
TEST TOOLS .
SCOPE
Verify correspondence between ratings reported on installed equipment plates and project design
ratings.
OPERATING INSTRUCTIONS
Visually check that equipment characteristics and rated data reported on installed plates comply with
relevant specification and applicable documentation.
ACCEPTANCE CRITERIA
Full correspondence.
TEST TOOLS .
Reference documentation.
SCOPE
The purpose is to check that standard and project documentation needed for the FAT and listed in
relevant check list is available, complete and updated.
OPERATING INSTRUCTIONS
Availability of documentation shall be checked against the relevant documentation list document.
ACCEPTANCE CRITERIA
TEST TOOLS .
Reference documentation.
SCOPE
The purpose is to check that manufacturer test certificates for integrated system components have
been issued and that they are available, complete, updated and compliant in quality with reference
specification.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
Reference documentation.
SCOPE
The purpose is to check the compliance and completeness of the Supply (the integrated system)
against all contractual relevant Material Take Off documents.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
Reference documentation.
SCOPE
The purpose is to check that the system components are free from defects or damages and in a good
preservation status.
OPERATING INSTRUCTIONS
Visually inspect each enclosure and the assembled components as well as the spares and accessory
components and check for good preservation status.
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
The purpose is to assess overall system quality by checking the final integrated system overall
assembling.
OPERATING INSTRUCTIONS
Visually inspect the overall integrated system for the execution quality, accessibility, assembling and
wiring quality, etc.
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
The purpose is to check whether spare parts and other specific accessories listed on Customer
Specification/Procurement are ready on the check-out area.
OPERATING INSTRUCTIONS
Verify the availability of the accessories against the relevant Check List.
ACCEPTANCE CRITERIA
TEST TOOLS .
PROCEDURE
N. C7 C7 - EQUIPMENT VERIFICATION TO NOMINAL PERFORMANCE
SCOPE
Scope of the test is to verify the equipment to nominal performances. This is done checking for the
availability of manufacturer test certificates or its declaration of conformity to the published
specifications.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
Reference documents.
SCOPE
OPERATING INSTRUCTIONS
Visually inspect all components that shall bear data-plates, (e.g. power supply units, monitors, etc.)
operating and warning labelling, markings etc. for the correctness and completeness of information
reported.
ACCEPTANCE CRITERIA
All components that shall bear a dataplate shall report on it the complete and correct data.
TEST TOOLS .
SCOPE
The purpose is to check that the spare capacity, in each functional cabinet(s) block, is provided as
required by the relevant reference specifications.
OPERATING INSTRUCTIONS
Each functional cabinet(s) block shall be visually inspected for the spare capacity as specified in the
relevant reference documentation.
ACCEPTANCE CRITERIA
Each functional cabinet(s) block shall provide spare capacity as required by relevant reference
documentation.
TEST TOOLS .
NOT APPLICABLE
SCOPE
The purpose is to check the performance adequacy and the proper calibration of the test equipment
and inspection instrumentation.
OPERATING INSTRUCTIONS
Verify the suitability of characteristics, calibration and calibration certificates of all equipment and
instrumentation that will be used to perform the tests.
ACCEPTANCE CRITERIA
All relevant certificates and data are available and the instrumentation for the test shall be suitable to be
used for the test.
TEST TOOLS .
SCOPE
The purpose is to verify that the check-out area is capable to provide the suitable Power Supply in
terms of voltage level and frequency, power and safety required for the integrated system test.
OPERATING INSTRUCTIONS
Check that the power supply distribution system, the voltage levels and frequency available are
compatible with those for which the system under test is designed.
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
The purpose is to verify the suitability of the supply to the environmental condition specified by the
reference documents.
This is done by the verification of the manufacturer Statement of Compliance.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
The purpose is to verify the electromagnetic compatibility provided is in accordance with the reference
specifications.
This is done by the verification of the manufacturer Statement of Compliance or CE certificate/marking.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose is to check that the Power Supply System of each item is in accordance with the reference
specifications and relevant approved documents and that it is properly functioning.
Purpose of the test is also to check whether the redundancy is operable and the protections selectivity
has been implemented in accordance to the reference documents.
Purpose of this test is also to check that all alarming relevant to the power supply system have been
implemented in accordance to the reference documents and is functioning properly.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
Power Supply system shall be in accordance with the approved reference documents.
All functional checks shall have positive result.
TEST TOOLS .
Multimeter
SCOPE
Purpose is to check that signal wiring, power supply and earthing connections from / to all peripheral
equipment are executed according to the approved documents and required recommendations.
OPERATING INSTRUCTIONS
Proper assembling and wiring of printers, workstations and engineering units shall be checked against
the approved system layout and the applicable standard documentation.
ACCEPTANCE CRITERIA
Connection of all peripheral equipment shall comply with approved drawings and applicable standard
documentation.
TEST TOOLS
Reference documentation
SCOPE
Purpose of this test is to verify that the SCADA & ESD/F&G CPUs/Processors are functioning properly.
OPERATING INSTRUCTIONS
The SCADA & ESD/F&G equipment CPUs/Processors proper functionality shall be checked by means
of the standard auto-diagnostic of each system: Servers, Workstations, RTUs, ESD.
ACCEPTANCE CRITERIA
Auto-diagnostic tests for all SCADA equipment: Servers, Workstations, RTUs and for ESD equipment
shall give positive result.
TEST TOOLS .
SCOPE
Purpose of this test is to verify the proper functioning of the peripherals like: printers, keyboards,
monitors of servers, engineering and operator stations, being part of the system.
OPERATING INSTRUCTIONS
Power on each peripheral and verify that there is no visible malfunction. Auto-test shall be carried out
on each printer.
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this test is to demonstrate the proper functionality of analogue (4-20 mA) field input signals
acquisition. The test therefore demonstrates the functionality of all devices and the correctness of wiring
between the field termination and the relevant processors.
The test of 100% of Analog Inputs of all the RTUs and of the ESD/F&G will be performed in advance
during Invensys Foxboro SCADA Pre-FAT tests and certified in the proper Pre-FAT Reports..
Also during the FAT will be performed a test of 100% of Analog Inputs for all the RTUs and for the
ESD/F&G.
This test can be jointly performed together with test of the configuration of I/O signals (see procedure n.
F.2).
OPERATING INSTRUCTIONS
• for RTU on relevant display of a PC loaded with S40 RTU Maintenance Tool.
• for HIMA PLC on relevant display of a PC loaded as programming unit.
The test shall be carried out on all channels of all modules together with procedure n. F.2.
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose of this test is to demonstrate the proper functionality of analogue (4-20 mA) field output signals
generation. The test therefore demonstrates the functionality of all devices and the correctness of wiring
between the field termination and the relevant processors.
This test can be jointly performed together with test of the configuration of I/O signals (see procedure n.
F.2).
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose of this test is to demonstrate the proper functionality of digital field input signals acquisition.
The test therefore demonstrates the functionality of all devices and the correctness of wiring between
the field termination and the relevant processors.
The test of 100% of Digital Inputs of all the RTUs and of the ESD/F&G will be performed in advance
during Invensys Foxboro SCADA Pre-FAT tests and certified in the proper Pre-FAT Reports..
Also during the FAT will be performed a test of 100% of Digital Inputs for all the RTUs and for the
ESD/F&G.
This test can be jointly performed together with test of the configuration of I/O signals (see procedure n.
F.2).
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
All indicating devices shall properly react to the simulated input changes.
TEST TOOLS .
SCOPE
Purpose of this test is to demonstrate the proper functionality of digital field output signals generation.
The test therefore demonstrates the functionality of all devices and the correctness of wiring between
the field termination and the relevant processors.
The test of 100% of Digital Outputs of all the RTUs and of the ESD/F&G will be performed in advance
during Invensys Foxboro SCADA Pre-FAT tests and certified in the proper Pre-FAT Reports..
Also during the FAT will be performed a of 100% of Digital Outputs for all the RTUs and for the
ESD/F&G.
This test can be jointly performed together with test of the configuration of I/O signals (see procedure n.
F.2).
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
All field output status and indicating devices shall properly react to the simulated logical changes.
TEST TOOLS .
SCOPE
Purpose is to check whether SCADA and HIMA ESD/F&G PLC standard software functions have been
loaded on relevant system media, that they are available and properly functioning.
The scope of this test does not include test of application software, but application software might be
loaded only to facilitate the test.
OPERATING INSTRUCTIONS
Before to start the test, for each item, the Release (Version), Reference Documentation and Licence
(where applicable) of the installed software shall be noticed and recorded.
ACCEPTANCE CRITERIA
Functional verification of standard operating system functions will however be thoroughly and
extensively tested during planned Application Software testing activities.
TEST TOOLS .
SCOPE
Purpose of this test is to verify the completeness and correctness of the input/output signals database
configuration against the customer reference documents, and the proper addressing up to the external
terminal strip.
This test can be carried out together with the check of the “User graphic pages” test (see procedure n.
F.4 “Check of static part and test of dynamic part of graphic displays”).
OPERATING INSTRUCTIONS
RTU
A printout of the database shall be used as check list.
Select the signal to be tested from the system Input database.
Find the corresponding TAG in the Customer I/O list and identify the relevant field terminals.
Display such TAG on a SCADA workstation via the “Point Details” menu and check that all parameters
comply with the customer reference documentation.
Check, for the Input Variables, the ability of the Windows Details to display a signal change simulated at
the relevant external terminals.
Check at the relevant external terminals the ability to generate a signal change from the RTU
engineering workstation.
Repeat the test for 100% of the Input/Output signals listed in the system database.
ACCEPTANCE CRITERIA
All items of the Customer I/O list shall be included in the I/O database
All items of I/O database shall be configured and all configured parameters shall comply with the
reference documentation.
All I/O variables shall be correctly addressed to the corresponding physical external interface (external
terminals).
TEST TOOLS .
SCADA system application and the data base will be fully tested via a switch bank to simulate field on/off
signals and potentiometer to simulate current sources connected to RTU/ESD and subsystems.
Lamps/LEDs will be used to indicate on/off output conditions.
This will be applicable for each RTU test and for the ESD system test as well.
The following main “Testing Equipments” will be used for the FAT:
• Linear metre
• Digital or analog tester
• Insulation gauge (Megger or equivalent) able to supply continuous tension with nominal value of 500V
minimum at no load
• Signals generator for simulation required signal types:
o 4-20 mA
o 1-5 Volt
o millivolt for thermocouple signals
o ohm for thermoresistance signals
o other types of signals
• Resistances as prescribed by technical specs.
• Operator Bench with controls and lamps
• The Programming Unit (Lap-Top) for the RTU’s and the HIMA PLC
SCOPE
The scope of this test is to verify the correctness of the Control database (Loop Drawings as
implemented in the SCADA) and its compliance with the Reference Documentation (Cause & Effect,
Logic Diagram, as applicable).
This test can be carried out together with the check of the “User graphic pages” test (see procedure n.
F.4)
OPERATING INSTRUCTIONS
HIMA PLC/RTU
Locate in the system the control loop to be tested according to the description in the reference
documents.
At the relevant graphic page or group page, select the signals that the control loop is composed of.
Simulate the signal variation, using testing apparatuses connected to system’s terminals or through SW
forcing, for the tags appertaining to the control loop and verify the loop’s behaviour.
The test shall be carried out on all control loops specified on the Customer Database.
ACCEPTANCE CRITERIA
All control loops specified on the Customer loop diagrams shall be configured and the configuration
shall perform the specified control strategy.
All configured parameters shall comply with the reference documentation.
TEST TOOLS .
SCOPE
Scope of this test is to verify the proper configuration of the User Display Graphic pages and their
operability.
Purpose of this test is also to verify that Data acquisition, Tag addressing and Control software
functions specified in loop diagrams database ( i.e. service, range, engineering units, alarms, etc.) have
been correctly implemented in Custom Graphic displays and any other dedicated function.
This test can be carried out together with the tests of the configuration of the I/O signals, the
implementation of the control strategies and the alarms management (see procedures n. F.2, F.3, F.5).
Tests will be also performed to prove graphics from field I/O through to graphic displays .
This should also include subsystems of SCADA.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
All specified graphic pages shall be configured and it shall be possible to call them up from applicable
operator workstation.
All the required/linked Display should appear when called up from the current display.
Each Software key (if present ) should appear and perform as required.
Alarm management ( colour conventions, acknowledgement, etc.) shall conform to the requirements of
the ref. documents.
TEST TOOLS .
Servers, Workstations.
SCOPE
The purpose of the test is to verify the correct implementation of alarms for the selected I/O signals and
their management.
This test can be carried out together with the tests of the configuration of the I/O signals (see procedure
n. F.2).
OPERATING INSTRUCTIONS
SCADA
Select from the Customer I/O list an alarmed signal and find on the system database the relevant
information item.
Simulate the selected signal and manually set the Input to a value corresponding to the alarm condition.
Verify that:
1 - the alarm is sent to all devices (printers, video units) specified in the reference documentation.
2 - when the alarm condition occurs, the relevant area alarm window, at the top of the screen of
the Video Unit(s) configured as alarm device, starts blinking; clicking on it, according to the
configuration, or the “Current Alarm” page is displayed where alarms are listed according to
their priority, acknowledgement status (yes/no) and time of occurrence, or the relevant RTU’s
alarm windows (if foreseen) is displayed. In this case, the involved RTU alarm window is
blinking and, clicking on it, the involved RTU “Current Alarm” page is displayed.
3 - acknowledgement soft keys perform correctly.
Repeat the test for 100% of the alarming signals listed in the Customer I/O list.
HIMA PLC
Select from the Customer I/O list an alarmed signal and find on the system database the relevant input
module and channel.
By the monitoring function of the Programming Unit manually set the input to a value corresponding to
the alarm condition.
Verify that:
1 - the alarm is sent to the SCADA video units and the printer, as applicable.
2 - when the alarm condition occurs, the "ALARM" indication, at the top of the screen of the Video
Unit, starts blinking; clicking on the soft button, the “Current Alarm” page is displayed where
alarms are listed with acknowledgement status (yes/no) and time of occurrence.
3 - acknowledgement soft keys perform correctly.
ACCEPTANCE CRITERIA
All alarming signals specified in the Customer I/O list shall be configured as such and with the priority
specified in the reference documents.
Alarm management shall be in accordance with the reference documents.
TEST TOOLS .
Servers, Workstations.
SCOPE
The purpose of the test is to verify the correct grouping and configuration of the user grouped trend
displays.
This test can be carried out together with the tests of the configuration of the I/O signals (see procedure
n. F.2).
OPERATING INSTRUCTIONS
Verify the correct call-up of each Trend group in the reference documents, if specified.
Check whether the selected Trend group display has been properly configured ( selected points,
sampling rate, etc.).
If the Trend group data is not defined in the reference documents, the test is to be carried out on a
sample configuration.
ACCEPTANCE CRITERIA
It shall be possible to call-up all Trend groups specified in the reference documents.
Each Trend group shall be called-up from the specified graphic display only.
All Trend groups shall be configured in accordance with the reference documents.
TEST TOOLS
Servers, Workstations.
SCOPE
Purpose of this test is to verify the correct configuration of the historical data archiving and presentation.
OPERATING INSTRUCTIONS
Verify that all signals specified in the reference document for historical recording are configured in the
applicable historian package.
Check whether each point has been properly configured (sampling rate, change delta, etc.).
If the historical data is not defined in the reference documents, the test is to be carried out on a sample
configuration.
ACCEPTANCE CRITERIA
All points specified in the reference document for historical recording shall be configured.
All configuration parameter of each point shall be in accordance with the reference documents.
TEST TOOLS
Servers, Workstations
SCOPE
Purpose of this test is to verify that the reports specified in the reference documents have been
correctly implemented.
Purpose of the test is also to check the ability of the system to print-out the configured reports.
OPERATING INSTRUCTIONS
For each type of report visually compare the lay-out of print-out with the requirements of the reference
documents.
Verify the content of the print- out (tags, types of variables, etc.) for correctness and completeness.
Verify the ability of the system to print each type of report.
If reports are not defined in the reference documents, the test is to be carried out on a sample report.
ACCEPTANCE CRITERIA
All reports specified in the reference documents shall be printed by the system according to the
specified terms.
The content and the lay-out of print-out of each type of report shall comply with the reference
documents.
TEST TOOLS
Servers, Workstations.
SCOPE
Purpose of this test is to verify the functionality of the standard diagnostic functions by the simulation of
external failures.
OPERATING INSTRUCTIONS
SCADA
Simulate a system failure by switching off, or disconnecting, one Workstation or one Server and check
that:
- the failure information is displayed and managed by the SCADA Workstation in accordance with
the reference documentation.
RTU
Extract one module per type (i.e.: one I/O Board) or switch off, or disconnect, one RTU and check that:
- the failure information is displayed and managed by the SCADA Workstation, as applicable, in
accordance with the reference documentation.
Simulation of the RTU chassis total power supply failure will be done to check the fail safe Digital
Output signals conditions
ESD/ F&G
Extract one main processor, one I/O module, switch off one power supply and check that:
- the failure information is displayed and managed by the SCADA workstation, as applicable, in
accordance with the reference documentation.
Simulation of the ESD total power supply failure will be done to check the fail safe Digital Output
signals conditions
ACCEPTANCE CRITERIA
The system shall respond to the simulated failures according to the standard reference documentation.
TEST TOOLS
SCOPE
The purpose of this check is to verify the correct intervention of the backup equipment when a failure to
the main device occurs. The check shall be carried out on any of the backed up equipment.
OPERATING INSTRUCTIONS
SCADA
for the SCADA Server
Alternatively switch off, and then back on, one of the two SCADA Server being the redundant
couple and check that there is no change in signals acquisition.
In the proper Diagnostic page, displayed on a SCADA Workstation, verify that the simulated
malfunction and the return to normal conditions are indicated in accordance with the standard
reference documentation.
for the Ethernet Switch
Alternatively switch off, and then back on, one of the two Ethernet Switch being the redundant
couple and check that there is no change in signals acquisition.
In the proper Diagnostic page, displayed on a SCADA Workstation, verify that the simulated
malfunction and the return to normal conditions are indicated in accordance with the standard
reference documentation.
for the System Ethernet Links
Test sequence is performed by alternatively disconnecting, and then reconnecting, the Ethernet
Links A / B of one Workstation, and checking that the station functionality is not disturbed.
In the proper Diagnostic page, displayed on a SCADA Workstation, verify that the simulated
malfunction and the return to normal conditions are indicated in accordance with the standard
reference documentation.
Repeat the test for the Ethernet Links for the SCADA Servers.
ESD/ F&G
for the main processors
Extract one of the main processors.
Verify that the system is still working properly.
Check that the malfunction is shown on the diagnostic screen of the programming unit.
Check that the relevant alarming is displayed and managed by SCADA workstation or by local RTU
laptop, as applicable, in accordance with the reference documentation.
Reinsert the processor and verify that it starts running properly without any operator intervention.
Repeat the test for the other two processors
for the Communication channel to SCADA
Extract one of the two connectors of the redundant serial link
Verify that the serial communications supported in the redundant mode is still functioning.
Check that the relevant alarming is displayed and managed by the SCADA workstation as
applicable, in accordance with the reference documentation.
Reinsert the connector and repeat the test with the second serial link.
PROCEDURE
N. F10
F10 – REDUNDANCY TESTS
cont’d
ACCEPTANCE CRITERIA
All devices provided in redundant configuration shall function properly under the condition of a single
fault.
The relevant alarming and diagnostic shall be in accordance with the reference documentation.
TEST TOOLS
SCOPE
Purpose of the test is to verify that occupation of memory and CPUs load of SCADA Servers
Processors and workstation processors, as well as the occupation of the mass memories (hard disk),
are in accordance with the reference documentation.
OPERATING INSTRUCTIONS
Check that the relevant application software is loaded into the system.
Using the standard system diagnostic, verify and record on the test report, for each processor, the
percentage of user memory occupation and the CPU load.
Using the standard commands available, verify and record, for each hard disk, the total capacity and
the free left capacity (in Mbytes).
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose of this check is to verify functionality and correct configuration of communicating systems
according to the applicable protocol’s specifications.
OPERATING INSTRUCTIONS
General test of connection functionality: visually check, by the relevant Configurator, that the
communication speed, parity and stop bit are in accordance with the reference documentation.
If redundant communication link is provided, check that by disconnecting one of the link, the
communication is still active and diagnostic is properly shown on SCADA.
Select a sample of signals to communicate (up to 100% if required) and force through SW the output
signal to each system connected. Check that the signal is correctly received and read by the receiving
system within the transmission delay defined by technical specifications.
ACCEPTANCE CRITERIA
Communication with all External Devices specified in the reference documents shall be implemented.
All signals specified in the reference documentation shall be configured and exchanged properly.
TEST TOOLS .
NOTE:
Step by Step procedure for external system interface Is detailed in Procedure N. G6
SCOPE
Purpose of the test is to verify that logic implemented in the system functionally performs the logic
sequences specified in the Customer reference documents
OPERATING INSTRUCTIONS
A copy of the system print-out of the logic diagrams (or the Customer logic reference document)and of
the relevant interlock graphic displays is used as test report.
The test is to be carried out checking, as far as possible, the single sheet of the Customer reference
document at a time or, in any case, one logic sequence at a time.
Following up, page by page, the reference document, connect the input simulators to the relevant input
terminals and check that the relevant outputs status comply with the input status according to the
specified logic diagram under testing.
Change the input status combinations to simulate, as much as possible, the expectable different field
and commands situations and check that the relevant outputs status comply with the input status
according to the specified logic diagram under testing. Check also the behaviour of the corresponding
alarm/indication on the related interlock graphic display.
If convenient, software settings of inputs and software reading of outputs can be used instead of
hardware simulation.
Mark the copy of the system print-out of the logic diagrams and the related interlock displays print-out
that are used as test report for compliance or any comment.
ACCEPTANCE CRITERIA
All logic sequences specified in the reference documentation shall be performed properly by the system
and shown accordingly on the HMI.
TEST TOOLS .
SCOPE
Purpose of this test is to verify the functionality and the correct data exchange between the SCADA
system and other external systems utilising the TCP/IP communication link.
The test simultaneously verifies the functionality and the correct configuration of data exchange.
The Gas Compressor System of the plant is controlled and monitored by Siemens PLCs and control systems
(one for each unit) located in local control rooms.
The Gas Compressor systems are connected via hardwired to the ESD and F&G system for emergency
shutdown.
The HMI for operation and monitoring of all the machinery and packages are implemented in a dedicated
operator station (situated in the plant control room) linked with the two unit control systems (situated in the
respective local control room).
The Siemens HMI for operation and monitoring are duplicated on the SCADA system only for monitoring
purposes, the signals to be configured on the HMI are provided by the vendor, all the signals are configured
as read-only type.
Signals from Siemens package are acquired by the SCADA via TCP/IP using OPC protocol.
SCADA switches on site El Arish are configured to provide connection towards proprietary Siemens subnet
and network addresses for their OPC servers, in particular:
Computer IP-Adress
Item Name Windows Subnet mask
OS-GT1 OS1 192.168.2.61 255.255.255.0
OS-GT2 OS2 192.168.2.62 255.255.255.0
The addresses for the two compression stations are configured according to KTI indications (ref. KTI mails
TPKTI/INV/E-005/006).
1. Verify that OPC Link is Established according to Above specification on both Scada PCS
System and on Siemens Sub-System
2. Verify that communication is healthy and no Time Out error is present
3. Change tags value in Siemens PLC system and check the correct reading in the Scada System
Database and on graphics display (if applicable)
4. Redundancy Test : Repeat the test 2,3 (spot check) disconnecting one channel at time
5. Verify that during channel disconnecting no spurious alarm are generated.
ACCEPTANCE CRITERIA
Each PCS is connected with flow computers of metering & regulating system (MRS), they shall calculate gas
flow rates using signals derived from field instruments.
In both El Arish and Ashqelon both CPUs of the S40 are connected to the RS485 ports of the flow computer
establishing a redundant communication link, through which the signals are exchanged using the modbus
RTU protocol.
With reference to the document SO44207109/FS “Functional Specification”, the Gould Modicon Modbus
Protocol Reference Guide does not specify how numbers greater than 16 bits (e.g. 32-bit integers and single
and double precision real numbers) should be transferred.
The Modbus protocol has 16-bit elements (called registers), and as such is only suitable for transferring 16-
bit integer data. Since no standard exists, Emerson Process Management has developed the following
formats suitable for transferring numerical data to third parties, and offers these as a standard solution.
According to what explained above, the format number 4 is used for the FLOBOSS 600 to configure the
registers exceeding the 16 bit standard modicon modbus register format, in particular for the 32 bit floating
point:
The Flow Boss System is Connected to the Scada System through a redundant Modbus RS-485 Link.
The Test will be done using a Modbus Slave Simulation Software (ModSim32) as per following steps:
1. Verify that RS485 serial communication parameter has been set as 19200 bits,8 data bit,1 stop
Bit ,No parity on both Scada PCS System (Master) and on Simulation software
2. Verify that communication is healthy and no Time Out error is present
3. Configure the Flow Boss database in the Modbus Simulation Software database
4. Using a simulation software change tags value and check the correct reading in the Scada
System Database and on graphics display (if applicable)
5. Redundancy Test : Repeat the test 2,3,4 (spot check) disconnecting one channel at time
6. Verify that during channel disconnecting no spurious alarm are generated.
ACCEPTANCE CRITERIA
SCOPE
Purpose of this test is to verify completeness and the functionality of Engineering Workstation
hardware as per reference documentation.
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose of this test is to verify completeness and the functionality of configuration software installed
on the Engineering Workstation.
OPERATING INSTRUCTIONS
The configuration software is the Scada A2 Engineering Suite. This package allows an engineer to
manage the SCADA DataBase, to start the WindowsMaker for display and graphical object creations.
Basic functions shall be checked as follows :
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this test is to verify completeness and the functionality of configuration software installed
on the Leak Detection Workstation.
OPERATING INSTRUCTIONS
The test for Data Acquisition has to be done following the hereinafter phases:
The test of this module has to be done following the hereinafter phases:
PROCEDURE
H3 – LEAK DETECTION WORKSTATION SOFTWARE TEST
N. H3
cont’d
The test of this module has to be done following the hereinafter phases:
The test of this module has to be done following the hereinafter phases:
The test of this module has to be done following the hereinafter phases:
PROCEDURE
H3 – LEAK DETECTION WORKSTATION SOFTWARE TEST
N. H3
cont’d
The test of this module has to be done following the hereinafter phases:
PROCEDURE
H3 – LEAK DETECTION WORKSTATION SOFTWARE TEST
N. H3
cont’d
PROCEDURE
H3 – LEAK DETECTION WORKSTATION SOFTWARE TEST
N. H3
cont’d
The test of this module has to be done following the hereinafter phases:
The test of this module has to be done following the hereinafter phases:
The test of this module has to be done following the hereinafter phases:
PROCEDURE
H3 – LEAK DETECTION WORKSTATION SOFTWARE TEST
N. H3
Steps 3 and 4 must be successfully verified also after changing one of the following
conditions:
• Simulation of a value change for the measured values involved in the calculation
(flow pressure, temperature)
• Change to the Delivery Gas Hourly Demand table. Note: changes to the current hour
demand or older will not affect the calculation
ACCEPTANCE CRITERIA
TEST TOOLS .
SCOPE
Purpose of this test is to verify completeness and the functionality of configuration software installed
on the ESD/F&G Engineering Workstation.
OPERATING INSTRUCTIONS
The software of the HIMA PLC’s consist of the ELOPII programming and monitoring package.
The ELOPII package is loaded in the PLC engineering workstation laptop.
Basic functions shall be checked as follows:
a. check ability to load and edit a dummy program.
b. check ability to load and monitor the program.
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this test is to verify the Security Access Level configuration of the system
OPERATING INSTRUCTIONS
Different Security Access Level are configured on the SCADA according to customer requirements (ref. to
KTI Generale Design Rules for Operator Iterfac)
For each Access Level the following features should be checked:
• User Name
• AOR Area of Reponsibility
• Security Password
• TheSystem shows the correct Access Level (Profile)
• Only the configured functionalities for the specified profile are accessible
• Only the assigned areas to the specified user are accessible
ACCEPTANCE CRITERIA
TEST TOOLS
The FAT's target is to reproduce in the supplier factory a system arrangement as close as possible to what
will be attended on customer's plant.
Therefore, all the equipment foreseen for EMG Telecommunications System installed and configured for FAT
will reproduce the final arrangement, with only the following exceptions:
• VSAT terminals
The VSAT link, connecting Ashqelon and Arish sites, will be simulated connecting directly the VSAT
Multiplexers at 128 kbps speed.
• INMARSAT terminals
The INMARSAT link, connecting Ashqelon and Arish sites, will be simulated connecting directly the
relevant layer 3 switches by a couple of Ethernet ports
The following section describes all the tests to be performed on the telecommunication network.
Three are main network hardware elements of the project that would under go testing that are:
• Layer 3 switches
• VSAT multiplexers
• PABXs
• Allied Telesyn AR-750S
The Table below lists all tests to be performed for the Telecommunication System Factory Acceptance Test.
SCOPE
Purpose of this test is to verify that the equipment complies to project scope of supply and the power
supply is within the allowed range of the equipment
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
This test is to verify the automatic redirection of data traffic to the backup links in case of VSAT failure.VSAT
multiplexer and VPN router have the task of automatically checking channels availability and switching
between them as per predefined priority that is as follows:
• First back-up channel between Ashqelon and El Arish that switches on in case of main channel
failure is the VPN link
• Second back-up channel between Ashqelon and El Arish that switches on in case of main channel
failure is the INMARSAT link
a) Verify that main channel is on as per normal operation and that Back-up channels are inactive
b) Disconnect physically the main channel connecting cable and try from the INTERNET to access the
process LAN
c) Disconnect physically the first backup channel connecting cable
d) Reconnect the first backup channel connecting cable
e) Reconnect the main channel connecting cable
ACCEPTANCE CRITERIA
1. Verify after step b) that after some seconds due to routing protocol convergence time, data
communication restores through traffic redirection to the first Back-up channel, verify that access to
the process LAN from the INTERNET is denied
2. Verify after step c) that after some seconds due to routing protocol convergence time, data
communication restores through traffic redirection to the second Back-up channel
3. Verify after step d) that traffic redirection to first Back-up data channel occurs and that second
Back-up channel gets inactive.
4. Verify after step e) that traffic redirection to main data channel occurs and that first and second
Back-up channel get inactive.
TEST TOOLS
SCOPE
This test is to :
• Verify the separation between office LAN and process LAN users realised using the VLAN feature of
Layer 3 switches.
• Verify the Internet browsing capabilities for Office LAN users only.
• Assess that SCADA operation is not affected by office LAN operation
OPERATING INSTRUCTIONS
d) Transfer a large file (i.e. more than 500 Mbps between two office LAN workstations)
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
This test is to verify the proper functionality of the maintenance to supervise, control and configure Arish and
Ashqelon layer 3 switches
OPERATING INSTRUCTIONS
b) See the report of layer 3 switch status indicating proper functionality of the same
c) Execute a configuration command
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this test is to verify that the equipment complies to project scope of supply and the power
supply is within the allowed range of the equipment
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
This test is to verify the proper functionality of the maintenance to supervise, control and configure Arish and
Ashqelon VSAT MUXes
OPERATING INSTRUCTIONS
b) See the report of MUX status indicating proper functionality of the same
c) Execute a configuration command
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this test is to verify that the equipment complies to project scope of supply and the power
supply is within the allowed range of the equipment
OPERATING INSTRUCTIONS
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
This procedure outlines the steps required to test the phone extensions provided by the Al-Arish PABX
OPERATING INSTRUCTIONS
a) Pick up the one telephone handset and ensure that dial tone can be heard. Dial the number of another
telephone connected to the exchange referring to the numbering table hereafter
ACCEPTANCE CRITERIA
1. Ensure that the called telephones on steps a) b) c) and d) are ringing and that when answered two
way speech is possible
TEST TOOLS
SCOPE
This procedure outlines the steps required to test the phone extensions provided by the Asquelon PABX
OPERATING INSTRUCTIONS
a) Pick up the one telephone handset and ensure that dial tone can be heard. Dial the number of another
telephone connected to the exchange referring to the numbering table hereafter
ACCEPTANCE CRITERIA
1. Ensure that the called telephones on steps a) b) c) and d) are ringing and that when answered two
way speech is possible
TEST TOOLS
SCOPE
This test is to verify the functionality of perform telephone calls in hot-line fashion (i.e. by just lifting the
phone reciver) from two dedicated phones, one located in El Arish the other one in Ashqelon.
OPERATING INSTRUCTIONS
a) Pick up the Arish Hot-line phone and ensure that outgoing calling tone can be heard
ACCEPTANCE CRITERIA
1. Ensure that the called telephones on steps a) b) c) and d) are ringing and that when answered two
way speech is possible
TEST TOOLS
SCOPE
This test is to verify the proper functionality of the maintenance to supervise, control and configure Arish and
Ashqelon PABX.
OPERATING INSTRUCTIONS
b) See the report of PABX status indicating proper functionality of the same
c) Execute a configuration command
ACCEPTANCE CRITERIA
TEST TOOLS
SCOPE
Purpose of this check is to verify that FAT program has been completed successfully, that Certification
of Compliance with specifications and codes is properly fulfilled, that FAT certificates and
documentation is complete.
OPERATING INSTRUCTIONS
Verify that the FAT certificates and documentation is available and review it for completeness according
to the reference documents.
Review all test results checking the list of FAT tests
ACCEPTANCE CRITERIA
TEST TOOLS
Reference documentation
Each Pending Action Report shall cover one type problem only.
The same form will be used during the PRE-FAT, the FAT and the CIST crossing the
box provided as appropriate.
FAT REPORT
Subject : ...........
N. .......
REFERENCE DOCUMENTS:
NOTES :
(P) PENDING
(S) SATISFACTORY
(N) NOT CONFORMING
Invensys Foxboro SCADA Rome S.p.a. EAST MEDITERRANEAN GAS PIPELINE PROJECT
via –Saccomuro, 21 – 00131 - ROMA
Job n. SC-0032 Company: KTI TECHNIP
N°
PENDING ACTION REPORT
Sheet of
P1 Vendor’s deviation
P2 Modifications
P3 Improvements
Remedial actions:
Invensys Foxboro SCADA Rome S.p.a. EAST MEDITERRANEAN GAS PIPELINE PROJECT
via –Saccomuro, 21 – 00131 - ROMA
Job n. SC-0032 Company: KTI TECHNIP