Blower room ventilation calculator

Maximum required blower room temperature Ts


Blower type 3D38B-100K 35 °C
max

Number of blowers in operation ? 5 The open space air temperature Ta 27 °C


 
Volumetric flow on suction side Q1 4500 m3/h Air temperature at the outlet of the blower T2 75 °C

Length of pipe in the blower room l 6 m Power of the electric motor P1 90 kW

Diameter of pipe behind the blower d 0,1 m Power input at the blower shaft P2 80,5 kW

yes
External suction ? Efficiency of the electric motor E ? 0,94
no

Results
Power dissipation of the motor Pm 0,72 kW Required amount of cooling air from fan Qv ? 1 153 m3/h
Required amount of air introduced into the engine
Power radiated by the blower Pd 1,14 kW room by the air intake grille Qa ? 1 639 m3/h

Power radiated by the pipeline Po 1,01 kW Area of the air intake grille S 0,091 m2
Power radiated by the accessories Pp 0,36 kW Side of a square of the air intake grille 0,302 m
Warming power Pv 3,23 kW

Overall warming power Pv total ? 16,14 kW


Overall fan power Qv total ? 5 764 m3/h
Side of a square of the common air intake grille ? 0,675 m

This calculation is only informative