Blower Room Ventilation Calculator: S Max A
Blower Room Ventilation Calculator: S Max A
Diameter of pipe behind the blower d 0,1 m Power input at the blower shaft P2 80,5 kW
yes
External suction ? Efficiency of the electric motor E ? 0,94
no
Results
Power dissipation of the motor Pm 0,72 kW Required amount of cooling air from fan Qv ? 1 153 m3/h
Required amount of air introduced into the engine
Power radiated by the blower Pd 1,14 kW room by the air intake grille Qa ? 1 639 m3/h
Power radiated by the pipeline Po 1,01 kW Area of the air intake grille S 0,091 m2
Power radiated by the accessories Pp 0,36 kW Side of a square of the air intake grille 0,302 m
Warming power Pv 3,23 kW