Professional Documents
Culture Documents
EDITION
This edition of the Approved Document M c. The requirements in the new Part M no
`Access to and use of buildings' replaces longer refer to `disabled people'. The aim of
the 1999 edition entitled `Access and the new Part M and AD M is to foster a more
facilities for disabled people'. The main inclusive approach to design to
changes are: accommodate the needs of all people. A
a. Part M now applies generally to material new section in the AD (Section 4) on
alterations of and extensions to existing `Facilities in buildings other than dwellings'
non-domestic buildings. It applies to has been introduced to cover audience and
material changes of use to some non- spectator facilities, refreshment facilities,
domestic uses. There is no exception for sleeping accommodation and switches,
historic buildings, but this new edition of AD outlets and controls. The guidance on
M contains guidance on such buildings. The changing facilities has been relocated to
guidance on dwellings in Sections 6 to 10 Section 5 `Sanitary accommodation in
remains unchanged from the 1999 edition of buildings other than dwellings'. This new
AD M, with the exception that some diagram edition of AD M includes guidance in
numbers and their text references have Section 0 `General Guidance' on
been changed to permit consistency with educational establishments and clarifies the
the amended Sections 1 to 5. Some treatment of purpose-built student
publication references, particularly those accommodation.
concerning lifts and sports facilities, have d. The explanation of the relationship
been replaced to reflect the most recent between Part M and the Disability
guidance available. Discrimination Act 1995 has been
b. The guidance draws on the amended in `Use of Guidance' to reflect
recommendations of British Standard BS Regulations made or revoked since the
8300:2001 `Design of buildings and their 1999 edition of AD M was published.
approaches to meet the needs of disabled e. The concept of the Access Statement has
people - Code of Practice'. There are some been introduced for the first time. It is
instances where the guidance in this recommended that an Access Statement is
Approved Document differs from the provided to identify the philosophy and
recommendations in the edition of BS 8300 approach to inclusive design adopted,
current at the date of publication of the AD. particularly when the approach taken to
It is the intention of the British Standards satisfying the Requirements differs from that
Institution to review such anomalies as may represented by the guidance in the
exist and where practicable to take them Approved Document.
into account in future editions of the
standard.
Approved Document M
3
M
Approved Document M
8
ACCESS TO AND USE OF BUILDINGS M
The Requirements
This Approved Document, which takes
effect on 1 May 2004, deals with the
requirements of Part M of Schedule 1
to the Building Regulations 2000 (as
amended by SI 2003/2692).
the width of the level approach), but in Note: Full details of tactile paving
any case spaced at a distance no are in "Guidance on the use of
Tactile Paving Surfaces."
greater than 50m;
c. the gradient along its length is
either no steeper than 1:60 along its
whole length, or less steep than 1:20 25 diameter
as well as a ramp.
1.22 Some people need to be able to
stop frequently; for instance to regain
strength or breath, or to ease pain.
Gradient of ramp
i. any intermediate landings are at 1.31 People who wear callipers or who
least 1.5m long and clear of any door have stiffness in hip or knee joints are
swings or other obstructions; particularly at risk of tripping or
catching their feet beneath nosings.
j. intermediate landings at least People with a weakness on one side or
1800mm wide and 1800mm long are with a sight impairment need the
provided as passing places when it is dimensions of the tread to be sufficient
not possible for a wheelchair user to for them to be able to place their feet
see from one end of the ramp to the square onto it. If the going is towards
other or the ramp has three flights or the upper end of the dimensional
more; range, the flight may rise to a greater
k. all landings are level, subject to a height without the need for an
maximum gradient of 1:60 along their intermediate landing, as the tread is
length and a maximum cross fall sufficiently deep to allow a person to
gradient of 1:40; stand and rest at any point within the
flight. It should be noted that excessive
l. there is a handrail on both sides; rounding of nosings reduces the
m. there is a kerb on the open side effective going.
of any ramp or landing at least 100mm 1.32 Many ambulant disabled people
high, which contrasts visually with the find it easier to negotiate a flight of
ramp or landing in addition to any steps than a ramp and, for these
guarding required under Part K; people, the presence of handrails for
n. clearly sign-posted steps are support is essential.
provided, in addition, when the rise of Note: Guidance is given in BS 8300 on:
the ramp is greater than 300mm
(equivalent to 2 x 150mm steps). – lighting stepped access; and
– slip resistance (Annex C).
Stepped access
Provisions
Note: Where there appears to be a
conflict between the guidance in Part 1.33 A stepped access will satisfy
M and Part K, Part M takes Requirement M1 or M2 if:
precedence; see the Notes to the a. a level landing is provided at the
Requirements. top and bottom of each flight;
Design considerations b. the unobstructed length of each
1.27 People with impaired sight risk landing is not less than 1200mm;
tripping or losing their balance if there
Diagram 4 Stepped access – key dimensions and use of hazard warning surface
20
6
20 rib
Rib profile
30 gap
1200 min.
bottom landing
300 min.
900 to 1100
280 to 425
25 max.
j. the projection of a step nosing overlap
Diagram 6);
k. the rise and going of each step is
consistent throughout a flight;
l. the rise of each step is between
150mm and 170mm, except adjacent to
25 max.
existing buildings where, due to overlap
dimensional constraints, the case for a
different rise is argued in the Access
Statement; 60° min.
Guarding with
cane detection
at ground level
Plan
Section
1500 1500
300 minimum
unless door
is power 1150
operated Minimum
zones of
visibility 800
500 500
L L L
DL1 and DL2 = door leaf dimensions of the doors to the lobby
DP1 and DP2 = door projection into the lobby (normally door leaf size)
L = minimum length of lobby, or length up to door leaf for side entry lobby
“a” = at least 300mm wheelchair access space (can be increased to reduce L)
1570 = length of occupied wheelchair with a companion pushing (or a large scooter)
NB: For every 100mm increase above 300mm in the dimension “a” (which gives a greater overlap of the wheelchair footprint over
the door swing), there can be a corresponding reduction of 100mm in the dimension L, up to a maximum of 600mm reduction.
Horizontal and vertical circulation in buildings other than dwellings Approved Document M
34
BUILDINGS OTHER THAN DWELLINGS M1/M2
powered hold open devices or swing- d. where fitted with a latch, the door
free closing devices should be used as opening furniture can be operated with
appropriate. These are devices whose one hand using a closed fist, e.g. a
closing mechanism is only activated in lever handle;
case of emergency. Low energy e. all door opening furniture
powered door systems may be used in contrasts visually with the surface of
locations not subject to frequent use or the door;
heavy traffic as the opening and
closing action is relatively slow. f. the door frames contrast visually
with the surrounding wall;
3.8 The presence of doors, whether
open or closed, should be apparent to g. the surface of the leading edge of
visually impaired people through the any door that is not self-closing, or is
careful choice of colour and material likely to be held open, contrasts
for the door and its surroundings. For visually with the other door surfaces
example, when a door is open, people and its surroundings;
with impaired sight should be able to h. where appropriate in door leaves
identify the door opening within the or side panels wider than 450mm,
wall, as well as the leading edge of the vision panels towards the leading edge
door. of the door have vertical dimensions
3.9 Other design considerations for which include at least the minimum
internal doors are as set out in 2.14 to zone, or zones, of visibility between
2.16 under ‘Manually operated non- 500mm and 1500mm from the floor, if
powered entrance doors’ and should necessary interrupted between 800mm
be referred to for guidance. and 1150mm above the floor, e.g. to
accommodate an intermediate
Note: Guidance is available in BS horizontal rail (see Diagram 9).
8300 on:
i. when of glass, they are clearly
– electrically powered hold-open defined with manifestation on the glass
devices at two levels, 850 to 1000mm and 1400
– swing-free systems to 1600mm, contrasting visually with
– low energy powered door the background seen through the glass
systems. in all lighting conditions (see 2.24(b) for
details of manifestation);
Provisions j. when of glass or fully glazed, they
3.10 Internal doors will satisfy are clearly differentiated from any
Requirement M1 or M2 if: adjacent glazed wall or partition by the
provision of a high-contrast strip at the
a. where needing to be opened
top, and on both sides;
manually, the opening force at the
leading edge of the door does not k. fire doors, particularly those in
exceed 20N; corridors, are held open with an
electro-magnetic device, but self-close
b. the effective clear width through a
when:
single leaf door, or one leaf of a double
leaf door, is in accordance with Table 2 – activated by smoke detectors
and Diagram 9; linked to the door individually, or
to a main fire/smoke alarm
c. there is an unobstructed space of
system;
at least 300mm on the pull side of the
door between the leading edge of the – the power supply fails;
door and any return wall, unless the – activated by a hand-operated
door has power-controlled opening or it switch;
provides access to a standard hotel
bedroom; l. fire doors, particularly to
individual rooms, are fitted with swing-
free devices that close when activated
Approved Document M Horizontal and vertical circulation in buildings other than dwellings
35
M1/M2 BUILDINGS OTHER THAN DWELLINGS
by smoke detectors or the building’s c. where they have an unobstructed
fire alarm system, or when the power width of less than 1800mm, they have
supply fails; passing places at least 1800mm long
m. any low energy powered swing and with an unobstructed width of at
door system is capable of being least 1800mm at reasonable intervals,
operated in manual mode, in powered e.g. at corridor junctions, to allow
mode, or in power-assisted mode. wheelchair users to pass each other;
d. the floor is level or predominantly
Corridors and passageways level (with a gradient no steeper than
1:60), with any section with a gradient
Design considerations
of 1:20 or steeper designed as an
3.11 Corridors and passageways internal ramp and in accordance with
should be wide enough to allow people Table 1 and Diagram 3;
with buggies, people carrying cases or
e. where a section of the floor has a
people on crutches to pass others on
gradient, in the direction of travel,
the access route. Wheelchair users
steeper than 1:60, but less steep than
should also have access to adjacent
1:20, it rises no more than 500mm
rooms and spaces, be able to pass
without a level rest area at least
other people and, where necessary,
1500mm long (with a gradient no
turn through 180°. Corridors narrower
steeper than 1:60);
than indicated in this guidance, or
localised narrowing (e.g. at archways) f. any sloping section extends the
might be reasonable in some locations, full width of the corridor or, if not, the
such as in existing buildings, or in exposed edge is clearly identified by
some extensions. visual contrast and, where necessary,
protected by guarding;
3.12 In order to help people with visual
impairment to appreciate the size of a g. any door opening towards a
space they have entered, or to find corridor, which is a major access route
their way around, there should be a or an escape route, should be recessed
visual contrast between the wall and so that when fully open, it does not
the ceiling, and between the wall and project into the corridor space, except
the floor. Such attention to surface where the doors are to minor utility
finishes should be coupled with good facilities, such as small store rooms
natural and artificial lighting design. and locked duct cupboards;
3.13 Good acoustic design should be h. any door from a unisex
employed to achieve an acoustic wheelchair-accessible toilet projects
environment that is neither too when open into a corridor that is not a
reverberant nor too absorbent so that major access route or an escape route,
announcements and conversations can provided the corridor is at least
be heard clearly. 1800mm wide at that point;
Provisions i. on a major access route or an
escape route, the wider leaf of a series
3.14 Corridors and passageways will of double doors with leaves of unequal
satisfy Requirement M1 or M2 if: width is on the same side of the
a. elements such as columns, corridor throughout the length of the
radiators and fire hoses, do not project corridor;
into the corridor, or where this is j. floor surface finishes with
unavoidable, a means of directing patterns that could be mistaken for
people around them, such as a visually steps or changes of level are avoided;
contrasting guard rail, is provided;
k. floor finishes are slip resistant;
b. they have an unobstructed width
(excluding any projections into the l. any glazed screens alongside a
space) along their length of at least corridor are clearly defined with
1200mm; manifestation on the glass at two
Horizontal and vertical circulation in buildings other than dwellings Approved Document M
36
BUILDINGS OTHER THAN DWELLINGS M1/M2
levels, 850 to 1000mm and 1400 to Vertical circulation within the
1600mm, contrasting visually with the building
background seen through the glass in
all lighting conditions (see 2.24(b) for Design considerations
details of manifestation);
3.17 A passenger lift is the most
Note: In respect of 3.14(b), for school suitable means of vertical access and
buildings, the preferred corridor width should be provided wherever possible.
dimension is 2700mm where there are However, given the space constraints
lockers within the corridor. in some buildings, it may not always be
possible to install the type and size of
Internal lobbies passenger lift that would be suitable for
Design considerations use by all, and other options may need
to be considered to provide for users
3.15 An internal lobby should allow a with mobility impairments.
wheelchair user, with or without a
companion, or a person pushing a 3.18 Signs indicating the location of a
pram or buggy, to move clear of one lifting device accessible by mobility-
door before attempting to open the impaired people should be clearly
second door, as indicated in 2.27, visible from the building entrance.
under ‘External lobbies’. Additionally, a sign identifying the floor
reached should be provided on each
Provisions landing in a location that can be easily
seen from the lifting device and is
3.16 Internal lobbies will satisfy
designed so that it contrasts visually
Requirement M1 or M2 if:
with its surroundings;
a. their length with single swing
3.19 Whatever lifting device is chosen,
doors is in accordance with Diagram
internal stairs should always be
10;
provided as an alternative means of
b. their length with double swing vertical access, and designed to suit
doors is at least (DP1 + DP2 + ambulant disabled people and those
1570mm); with impaired sight.
c. their width (excluding any 3.20 A ramp may also be provided on
projections into the space) is at least an internal circulation route to a
1200mm (or (DL1 or DL2) + 300mm) suitable lifting device, if a change of
whichever is the greater when single level is unavoidable.
leaf doors are used, and at least
1800mm when double leaf doors are Provision of lifting devices
used;
Design considerations
d. glazing within the lobby does not
3.21 For all buildings, a passenger lift
create distracting reflections;
is the most suitable form of access for
e. any junctions of floor surface people moving from one storey to
materials at the entrance to the lobby another.
area do not create a potential trip
3.22 For existing buildings, and in
hazard;
exceptional circumstances for new
f. any columns, ducts and similar developments with particular
full height elements that project into constraints (e.g. a listed building, or an
the lobby by more than 100mm are infill site in a historic town centre),
protected by a visually contrasting where a passenger lift cannot be
guard rail. accommodated, a vertical lifting
platform (platform lift), although not
equivalent to a passenger lift, may be
considered as an alternative option to
provide access for persons with
impaired mobility. The case for using
Approved Document M Horizontal and vertical circulation in buildings other than dwellings
37
M1/M2 BUILDINGS OTHER THAN DWELLINGS
such a lifting device should be argued minimise glare, reflection, confusing
in the Access Statement. shadows or pools of light and dark.
3.23 In exceptional circumstances in 3.27 All users including wheelchair
an existing building, a wheelchair users should be able to reach and use
platform stairlift may be considered, the controls that summon and direct
provided its installation does not the lifting device.
conflict with requirements for means of Note: Further guidance is available in
escape. The case for installing a BS 8300.
wheelchair platform stairlift should be
argued in the Access Statement. Provisions
Provisions 3.28 The installation of lifting devices
will satisfy Requirement M1 or M2 if:
3.24 The provision of lifting devices
will satisfy Requirement M1 or M2 if: a. there is an unobstructed
manoeuvring space of 1500mm x
a. new developments have a 1500mm, or a straight access route
passenger lift serving all storeys; 900mm wide, in front of each lifting
b. new developments, where due to device;
site constraints a passenger lift cannot b. the landing call buttons are
be accommodated to provide access to located between 900mm and 1100mm
persons with impaired mobility, have a from the floor of the landing and at
lifting platform, of a type designed for least 500mm from any return wall;
the vertical height to be travelled;
c. the landing call button symbols,
c. existing buildings have a where provided, and lifting device
passenger lift serving all storeys or, if a control button symbols are raised to
passenger lift cannot reasonably be facilitate tactile reading;
accommodated to provide access to
persons with impaired mobility, they d. all call and control buttons
have a lifting platform, of a type contrast visually with the surrounding
designed for the vertical height to be face plate, and the face plate similarly
travelled; contrasts with the surface on which it
is mounted;
d. existing buildings have a
wheelchair platform stairlift serving an e. the floor of the lifting device
intermediate level or a single storey, should not be of a dark colour and
only in exceptional circumstances. should have frictional qualities similar
to, or higher than, the floor of the
General requirements for lifting landing;
devices f. a handrail is provided on at least
one wall of the lifting device with its
Design considerations
top surface at 900mm (nominal) above
3.25 In selecting the appropriate lifting the floor and located so that it does
device care should be taken to ensure not obstruct the controls or the mirror;
it is fit for purpose. Relevant
g. a suitable emergency
legislation includes the Lift Regulations
communication system is fitted.
1997 SI 1997/831, the Lifting
Operations and Lifting Equipment Passenger lifts
Regulations 1998 SI 1998/2307, the
Provision and Use of Work Equipment Design considerations
Regulations 1998 SI 1998/2306 and the 3.29 A wheelchair user needs sufficient
Management of Health and Safety at space and time to enter and leave a
Work Regulations 1999 SI 1999/3242. passenger lift, particularly when sharing
3.26 The illumination in the passenger it with other people. Lift sizes should
lift car, on the lifting platform or on the therefore be chosen to suit the
wheelchair platform stairlift should anticipated density of use of the
Horizontal and vertical circulation in buildings other than dwellings Approved Document M
38
BUILDINGS OTHER THAN DWELLINGS M1/M2
building and the needs of disabled a. they conform to the requirements
people. The minimum size lift car of the Lift Regulations 1997, SI
shown in the provisions below 1997/831 (Note: These regulations
accommodates a wheelchair user with may be met by compliance with,
an accompanying person. A larger lift among other things, the relevant British
size (2000mm wide by 1400mm deep) Standards, EN 81 series of standards,
will accommodate any type of in particular BS EN 81-70: 2003 ‘Safety
wheelchair together with several other rules for the construction and
passengers. It will also allow a installation of lifts - Particular
wheelchair user or a person with a applications for passenger and good
walking frame to turn through 180°. passenger lifts’, or, where necessary,
3.30 Lift door systems should be by product certification issued by a
designed to allow adequate time for Notified Body.);
people, and any assistance dogs, to b. they are accessible from the
enter or leave the lift without coming remainder of the storey;
into contact with closing doors. c. the minimum dimensions of the
3.31 People using or waiting for a lift lift cars are 1100mm wide and 1400mm
need audible and visual information to deep (see Diagram 11);
tell them that a lift has arrived, which d. for lifts of a size that does not
floor it has reached and where in a allow a wheelchair user to turn around
bank of lifts it is located. within the lift car, a mirror is provided
3.32 The use of visually and in the lift car to enable a wheelchair
acoustically reflective wall surfaces can user to see the space behind the
cause discomfort for people with visual wheelchair;
and hearing impairment. e. power-operated horizontal sliding
3.33 Where planning allows, lift cars doors provide an effective clear width
(used for access between two levels of at least 800mm (nominal);
only) may be provided with opposing f. doors are fitted with timing
doors to allow a wheelchair user to devices and re-opening activators to
leave without reversing out. allow adequate time for people and any
Provisions assistance dogs to enter or leave;
3.34 Passenger lifts will satisfy g. car controls are located between
Requirement M1 or M2 if: 900mm and 1200mm (preferably
900 nominal
900
Unobstructed
wheelchair 400
turning space
1400 min.
800 min.
Approved Document M Horizontal and vertical circulation in buildings other than dwellings
39
M1/M2 BUILDINGS OTHER THAN DWELLINGS
1100mm) from the car floor and at least unsupervised environment. Where
400mm from any return wall; management control cannot be
h. landing call buttons are located exercised, particular attention should
between 900mm and 1100mm from the be paid to the product’s designed duty
floor of the landing and at least 500mm cycle.
from any return wall; 3.41 Where planning allows, lifting
i. lift landing and car doors are platforms may be provided with
distinguishable visually from the opposing doors when used for access
adjoining walls; between two levels only, to allow a
wheelchair user to leave without
j. audible and visual indication of lift reversing out. In some cases, it may be
arrival and location is provided in the more convenient to provide a second
lift car and the lift lobby; door at 90° to the first, in which case a
k. areas of glass are identifiable by wider platform would be required.
people with impaired vision; 3.42 The use of visually and
l. where the lift is to be used to acoustically reflective wall surfaces
evacuate disabled people in an should be minimised within the lifting
emergency, it conforms to the relevant platform to prevent discomfort for
recommendations of BS 5588-8. people with visual and hearing
impairment.
Lifting platforms Provisions
Design considerations 3.43 Lifting platforms will satisfy
3.35 A lifting platform should only be Requirement M1 or M2 if:
provided to transfer wheelchair users, a. they conform to the requirements
people with impaired mobility and their of the Supply of Machinery (Safety)
companions vertically between levels Regulations 1992, S.I. 1992/3073
or storeys. (Note: These regulations may be met
3.36 All users including wheelchair by compliance, among other things,
users should be able to reach and use with the relevant British Standards,
the controls that summon and direct EN81 series of standards or, where
the lifting platform. necessary, by product certification
issued by a Notified Body. In the
3.37 People using or waiting for a absence of relevant harmonised
lifting platform need audible and visual European standards, products with a
information to tell them that the travel exceeding 3m must have a
platform has arrived, and which floor it product certificate issued by a Notified
has reached. Body);
3.38 Lifting platforms travel slowly b. the vertical travel distance is:
between landings and may not be
suitable for lone users with certain i) not more than 2m, where
disabilities, e.g. those easily fatigued. there is no liftway enclosure
and no floor penetration;
3.39 Lifting platforms are operated by
continuous pressure controls. In their ii) more than 2m, where there
simplest form these may be is a liftway enclosure;
pushbuttons. However, another means c. the rated speed of the platform
of continuous pressure control may does not exceed 0.15m/s;
need to be considered to
accommodate the needs of users with d. lifting platform controls are
varying degrees of manual dexterity. located between 800mm and 1100mm
from the floor of the lifting platform and
3.40 It is important when selecting a at least 400mm from any return wall;
lifting platform that due care and
attention is paid to its intended use e. continuous pressure controls are
particularly if located in an provided;
Horizontal and vertical circulation in buildings other than dwellings Approved Document M
40
BUILDINGS OTHER THAN DWELLINGS M1/M2
f. landing call buttons are located install a conventional passenger lift or
between 900mm and 1100mm from the a lifting platform. Such stairlifts travel
floor of the landing and at least 500mm up the string of a stair. They should not
from any return wall; be installed where their operation
g. the minimum clear dimensions of restricts the safe use of the stair by
the platform are: other people.
Approved Document M Horizontal and vertical circulation in buildings other than dwellings
41
M1/M2 BUILDINGS OTHER THAN DWELLINGS
d. continuous pressure controls are a. they comply with provisions (a),
provided; (b), (e) to (g), and (i) to (k) and (n) to (p)
e. the minimum clear dimensions of of 1.33;
the platform are 800mm wide and b. a flight between landings normally
1250mm deep; contains no more than 12 risers, but
f. they are fitted with clear exceptionally no more than 16 risers in
instructions for use; small premises where the plan area is
restricted (see Diagram 12);
g. access with an effective clear
width of at least 800mm is provided; c. the rise of each step is between
150mm and 170mm, except in existing
h. controls are designed to prevent buildings where, due to dimensional
unauthorised use. constraints, the case for a different rise
is argued in the Access Statement;
Internal stairs
d. the going of each step is at least
Design considerations 250mm;
3.50 With the exception of the need for e. the area beneath a stair where the
hazard warning surfaces on landings, soffit is less than 2.1m above floor level
other design considerations for internal is protected as described in 1.39(b).
stairs are as those for ‘Stepped
Note: For school buildings, in respect
access’ (see 1.29 to 1.32). It is not
of 3.51(c) and (d), the rise should not
reasonable to require a hazard warning
exceed 170mm, with a preferred going
surface at the head of internal stairs
of 280mm. Also, for schools, refuges
since there is no recognised warning
should be provided for all stairs where
surface for use internally which can be
no other arrangement is in place (see
guaranteed not to constitute a trip
AD B, B1.xvi, and BS 5588-8 for details
hazard when used alongside flooring
of refuges).
surfaces with different frictional
resistance characteristics. However, Internal ramps
designers should be aware of the
potential risk of having a stair directly Design considerations
in line with an access route. For 3.52 With the exception of issues
mobility-impaired people, a going of at relating specifically to the external
least 300mm is preferred. environment, the design considerations
Provisions for internal ramps are as those for
‘Ramped access’ (see 1.19 to 1.25). It
3.51 Internal stairs will satisfy is worth reiterating that ramps are not
Requirement M1 or M2 if: necessarily safe and convenient for
ambulant disabled people. For
example, some people who can walk
900 to 1000
above pitch line
300 min.
900 to
1100 12 risers max.
(16 risers max. in small premises
where space is restricted)
Horizontal and vertical circulation in buildings other than dwellings Approved Document M
42
BUILDINGS OTHER THAN DWELLINGS M1/M2
but have restricted mobility find it more
difficult to negotiate a ramp than a
stair. Unless, therefore, a ramp is short,
has a shallow gradient and the rise is
no more than the minimum that can be
provided by two risers, steps should be
provided as well as a ramp.
Provisions
3.53 Internal ramps will satisfy
Requirement M1 or M2 if:
a. they comply with provisions (a) to
(c), (e) to (j) and (l) to (m) for ramped
access in 1.26;
b. where the change in level is
300mm or more, 2 or more clearly
signposted steps are provided in
addition to the ramp;
c. where the change in level is no
greater than 300mm, a ramp is
provided instead of a single step;
d. all landings are level, subject to a
maximum gradient of 1:60 along their
length;
e. the area beneath a ramp where
the soffit is less than 2.1m above floor
level is protected as described in
1.39(b).
Handrails to internal steps, stairs
and ramps
Design considerations
3.54 The design considerations for
handrails are as those for ‘Handrails to
external stepped and ramped access’
in 1.34 to 1.36.
Provisions
3.55 Handrails to internal steps, stairs
and ramps will satisfy Requirement M1
or M2 if they comply with all the
provisions contained in 1.37.
Approved Document M Horizontal and vertical circulation in buildings other than dwellings
43
M1 BUILDINGS OTHER THAN DWELLINGS
Section 4
FACILITIES IN BUILDINGS OTHER Note: The guidance here relates mainly
THAN DWELLINGS to seating. For guidance on reception
and sales counters, refer to 3.2 to 3.5.
Objectives Audience facilities generally
4.1 The aim is for all people to have 4.6 Wheelchair users and those with
access to, and the use of, all the mobility or sensory impairment may
facilities provided within buildings. need to view or listen from a particular
They should also be able to participate side, or sit in the front for lip reading or
in the proceedings at to read sign interpreters. They should
lecture/conference facilities and at be provided with spaces into which
entertainment or leisure and social they can manoeuvre easily, and which
venues, not only as spectators, but offer them a clear view of an event,
also as participants and/or staff. while ensuring they are not segregated
into special areas. Wheelchair users,
4.2 Where permanent or removable people who have difficulty in using
seating is provided as part of the seats with fixed arms and those with
design, allowance should be made for assistance dogs, should also have the
disabled people to have a choice of choice of sitting next to a
seating location at spectator events. It conventionally seated person or a
should also be possible for them to companion wheelchair user.
have a clear view of the activity taking Consideration should be given to
place while not obstructing the view of providing an area next to certain seats
others. for an assistance dog to rest. By
4.3 In refreshment facilities, bars and having some removable seating at the
counters (or sections of them) should front and back of blocks of seats
be at a level suitable for wheelchair (possibly in complete rows), greater
users. All floor areas, even when flexibility in location can be achieved
located at different levels, should be and a greater number of wheelchair
accessible. users than the minimum provision
shown in Table 3 can be
4.4 A proportion of the sleeping accommodated.
accommodation in hotels, motels and
student accommodation should be 4.7 Greater spacing between rows of
designed for independent use by seats at the rear of a block of seating,
wheelchair users. The remainder should or at the end of rows, may provide
include facilities that make them extra legroom for people of large
suitable for people who do not use a stature. With several seats removed,
wheelchair, but may have mobility, these locations may also be suitable for
sensory, dexterity or learning wheelchair users. It is desirable for
difficulties. seating to contrast visually with the
surroundings.
Audience and spectator facilities 4.8 All users of facilities should be
Design considerations able to locate suitable seating and
move safely and easily to and from the
4.5 Audience and spectator facilities seating area and ancillary
fall primarily into three categories: accommodation, such as lavatories,
a. lecture/conference facilities dining rooms and bedroom suites.
b. entertainment facilities (e.g. Lecture/conference facilities
theatres/cinemas) 4.9 People with hearing impairments
c. sports facilities (e.g. stadia). should be able to participate fully in
conferences, committee meetings and
study groups. All people should be able
Rear wall
Rostrum
Rear wall
1100* 900
Steps Steps
800
Provisions
4.24 Sleeping accommodation will
satisfy Requirement M1 if:
Work surface 850
above floor level
Microwave
oven
For all bedrooms
Refrigerator
under worktop
a. the effective clear width of the
door from the access corridor complies
1500 x 1500 with Table 2;
Wheelchair
Floor unit turning space b. swing doors, where provided for
built-in wardrobes and other storage
systems, open through 180°;
also be able to gain access to and c. handles on hinged and sliding
conveniently use sanitary doors are easy to grip and operate and
accommodation and, where provided, contrast visually with the surface of the
balconies. En-suite sanitary facilities door;
are the preferred option for wheelchair-
accessible bedrooms. Unless there are d. openable windows and window
compelling reasons for not doing so, controls are located between 800 and
there should be at least as many en- 1000mm above the floor and are easy
suite shower rooms as en-suite to operate without using both hands
bathrooms, as mobility-impaired people simultaneously;
may find it easier to use a shower than e. all bedrooms have a visual fire
a bath. An en-suite shower room or alarm signal, in addition to the
bathroom would benefit from having a requirements of Part B;
finger rinse basin adjacent to the WC,
as well as a wash basin or basin in a f. any room numbers are indicated
vanitory unit. in embossed characters;
4.20 It is also important to ensure that, For wheelchair-accessible bedrooms
in all bedrooms, built-in wardrobes and g. at least one wheelchair-accessible
shelving are accessible and convenient bedroom is provided for every 20
to use. It is an advantage if curtains bedrooms, or part thereof;
and blinds are provided with automatic,
or other remotely controlled opening h. wheelchair-accessible bedrooms
devices such as rods or pull cords. are located on accessible routes that
lead to all other available facilities
4.21 Wheelchair users should also be within the building;
able to visit companions in other
bedrooms, for example when attending i. wheelchair-accessible bedrooms
conferences or when on holiday with are designed to provide a choice of
their families. In these instances, location and have a standard of
bedrooms not designed for amenity equivalent to that of other
independent use by a person in a bedrooms;
wheelchair need to have the outer door
See Section 5
for dimensions
Wheelchair-accessible
shower room or bathroom -
See Section 5 for details
j. the door from the access corridor located at 1050mm and 1500mm above
to a wheelchair-accessible bedroom floor level, to enable viewing by people
complies with the relevant provisions of who are seated or standing;
‘Internal doors’ (see 3.10), in particular o. a balcony, where provided to a
the maximum permissible opening wheelchair-accessible bedroom, has a
force, Table 2 and the need for a clear door whose effective clear width
space of 300mm from the leading edge complies with Table 2, has a level
of the door to the side wall; threshold and has no horizontal
k. the effective clear width of any transoms between 900mm and
door to an en-suite bathroom or 1200mm above the floor;
shower room within the wheelchair- p. there are no permanent
accessible bedroom complies with obstructions in a zone 1500mm back
Table 2; from any balcony doors;
l. the size of wheelchair-accessible q. an emergency assistance alarm
bedrooms allows for a wheelchair user (together with a reset button) is located
to manoeuvre at the side of a bed, then in a wheelchair-accessible bedroom
transfer independently to it. An and activated by a pull cord, sited so
example of a wheelchair-accessible that it can be operated both from the
bedroom layout is shown in bed and from an adjacent floor area;
Diagram 17;
r. an emergency assistance call
m. sanitary facilities, en-suite to a signal outside an accessible bedroom
wheelchair-accessible bedroom, is located so that it can be easily seen
comply with the provisions of 5.15 to and heard by those able to give
5.21 for ‘Wheelchair-accessible assistance and, in any case, at a
bathrooms’ or ‘Wheelchair-accessible central control point.
shower facilities’;
n. wide angle viewers, where
provided in the entrance door to a
wheelchair-accessible bedroom, are
Disposal bin
1500 x 1500
Wheelchair
turning space Shelf
Mirror Wall A
Finger rinse
2200 min. basin
Clothes hooks Vertical grab rails
Alarm pull cord
140-160
250
Alternative position
for alarm pull cord
150 320 500 Zone for shelf for
Vertical grab rail
standing users
970
1000 min.
1500 min.
300
HD SD PT TP AR
300
720-740 680
480*
HD: Possible position for automatic hand dryer (see also Diag 21)
SD: Soap dispenser
PT: Paper towel dispenser
AR: Alarm reset button
TP: Toilet paper dispenser
Height of drop-down rails to be the same as the other horizontal grab rails
1600
min.
1600 min.
Height of independent wash basin Mirror located away from wash basin
and location of associated fittings, for suitable for seated and standing people
wheelchair users and standing people (Mirror and associated fittings used
within a WC compartment or serving a
range of compartments)
A. For people standing
B. For use from WC
Provisions
5.14 WC compartments within people) is 1200mm wide and includes a
separate-sex toilet washrooms will horizontal grab bar adjacent to the WC,
satisfy Requirement M1 or M3 if: a vertical grab bar on the rear wall and
space for a shelf and fold-down
a. the swing of any inward opening
changing table;
doors to standard WC compartments is
such that a 450mm diameter e. any compartment for use by
manoeuvring space is maintained ambulant disabled people has a WC
between the swing of the door, the WC pan that conforms to BS 5503-3 or BS
pan and the side wall of the 5504-4 in terms of key dimensions, in
compartment; order to accommodate the use of a
variable height toilet seat riser (see 5.9
b. the minimum dimensions of
and 5.11);
compartments for ambulant disabled
people, including the activity space, f. a wheelchair-accessible
and the arrangement of grab bars and compartment (where provided) has the
other fittings within the compartment, same layout and fittings as the unisex
comply with Diagram 21; toilet;
c. doors to compartments for g. any wheelchair-accessible
ambulant disabled people are washroom has at least one washbasin
preferably outward-opening and are with its rim set at 720 to 740mm above
fitted with a horizontal closing bar fixed the floor and, for men, at least one
to the inside face; urinal with its rim set at 380mm above
the floor, with two 600mm long vertical
d. an enlarged compartment for
grab bars with their centre lines at
those who need extra space (based on
1100mm above the floor, positioned
the compartment for ambulant disabled
either side of the urinal.
Horizontal
grab rail
Back rest Alarm reset
Drop-down rail
Possible location
680 800 of towel rail
480
Tip-up seat
Elevation
Drop-down rail
on side wall
250 50 200
600 300
Possible location of towel rail
Alarm (or locate in self-contained
pull cord shower room)
Grab rail
500
Clothes hooks
Tip-up
1200 seat
320 Mirror
Drop-down rails
2000
650
1500 x 1500
Wheelchair turning space
Plan
2200
500
1400
Range for adjustable
1200 and detachable
shower head
Back rest
1000
Range for
750 shower controls
Drop-down rail
on side wall
680
Drop-down rail
480
Tip-up seat
Elevation
(Alarm pull cord,
horizontal and vertical grab rails,
250 50 shower curtain rail and towel rail
Shower control and 600 300 not shown for clarity)
adjustable shower head
Alarm
pull cord
Floor drain
500 Clothes hooks
Towel rail
Tip-up
1200 seat
320
Drop-down rails
2000
650
Fall of
floor
Shower curtain
1500 x 1500
Wheelchair turning space
Plan
2200
Additional, optional
tip-up seat for users
when drying
(mainly for ambulant users)
2400
500 300
Floor drain
Tip-up
Alarm pull cord seat Mirror
Shower curtain
Vertical grab rail
Wash basin
Drop-down rails
2500
Towel rail
Fall of floor
140-160
1500 x 1500
Wheelchair turning space
Note
Layout shown for right hand transfer to shower seat and WC
Towel rail
Sanitary dispenser
Disposal bin
Shelf
Bath transfer
seat
2500
1500 x 1500
Wheelchair turning space
140-160
2700
Note
Layout shown for right hand transfer to bath and WC
600
Vertical grab rail
(500 min. length)
Alternatively rail partially cranked
at max. 13° to horizontal
Horizontal
grab rail
200
75 to 100
480*
150min.*
50 to 60 clearance
between wall
200 and handrail 250
Alarm
pull cord
Bath length
400 min.
depth
Section 8
ACCESSIBLE SWITCHES AND
Diagram 29 Heights of switches,
SOCKET OUTLETS IN THE sockets etc
DWELLING
see para 8.3
Objective
8.1 The aim is to assist those people
telephone jack points
tv sockets
switches
sockets
at suitable heights.
1200mm
Design considerations
450mm
Objectives
1000mm
9.1 For buildings containing flats, the 300mm
objective should be to make
900mm
reasonable provision for disabled
people to visit occupants who live on 300mm
1000mm
any storey.
9.2 The most suitable means of
access for disabled people from one A. COMMON STAIRS AND HANDRAILS
Provisions
Common stairs
B. EXAMPLES OF SUITABLE TREAD NOSING PROFILES
9.5 Requirement M1 will be satisfied Maximum rise 170mm
if a building containing flats, in which a Maximum going 250mm
Provision
10.3 Requirement M4 will be satisfied,
if: edge of door opening
250mm
J M R
Joysticks - wheelchair platform Maisonettes - definition 0.30 Radio signals see Communication
stairlifts 3.47 Manifestation - glass doors and aids
screens 2.22, 2.24, 3.14 Ramps - approach routes
L Material alterations 0.1-0.4, 0.9 (dwellings) 6.14-6.15
Lavatories see Sanitary Mirrors in passenger lifts see Ramps - approach routes (non-
accommodation Lifting devices domestic) 1.19-1.26
Lecture facilities 4.1, 4.5, 4.9, Mixed use development 0.12 Ramps - corridors 3.14
4.32, 4.36 Mixer taps see Sanitary Ramps - handrails 1.26,
Leisure facilities 4.1, 4.10, 4.36 accommodation 5.4 1.34-1.37
Level approaches see Approaches Motel bedrooms see Bedrooms Ramps - internal (non-domestic)
- level 3.14, 3.20, 3.52-3.53
Motion sensors 2.18, 2.21
Lifting devices 3.17-3.49 Ramps - podiums and stages
4.12
Lifting devices - accessibility to
toilets 5.10
N Reception desks see also Enquiry
Notice boards 3.5 desks 3.2-3.6, 4.32
Lifting devices - blocks of flats
9.6-9.7 Reflective wall surfaces see Wall
Lifting devices - call buttons O surfaces
3.34, 3.43, 9.7 Opening force of doors See Doors Refreshment facilities 4.13-4.16
Lifting devices - dimensions Remote controls 2.21
3.34, 3.43, 3.49, 9.7 P Restaurants 4.13-4.16
Lifting devices - illumination Parking 1.15-1.18 Revolving doors see Doors
3.26 Risers - steps and stairs
Parking ticket machines 1.16,
Lifting devices - instructions for 1.18 (dwellings) 6.17, 9.5
use 3.43 Risers - steps and stairs (non-
Passageways see Corridors
Lifting devices - lifting platforms domestic) 1.33, 3.51
Passenger lifts see Lifting devices
3.22, 3.24, 3.35-3.43 Room numbers - embossed 4.24
Planning system 0.21
Lifting devices - mirrors 3.34 Rostrums see also Podiums,
Platform lifts see Lifting devices -
Lifting devices - passenger lifts Stages 4.12
lifting platforms
3.17, 3.21-3.24, 3.29-3.34, 9.2,
Plot gradient 6.14, 6.16
9.6-9.7
Lifting devices - podiums and Plot gradient - definition 0.30
S
stages 4.12 Sales counters 3.3
Plots - dwellings 6.1-6.3
Lifting devices - speeds 3.43, Sanitary accommodation 0.8,
Podiums see also Rostrums,
3.49 0.14, 4.19, 4.24, 5.1-5.21,
Stages 4.12
10.1-10.3
Lifting devices - visual contrast Point of access - definition 0.30
3.18, 3.28, 3.34, 3.43 Sanitary accommodation -
Principal entrance (dwellings) bathrooms 4.19, 4.24, 5.19-
Lifting devices - visual information 6.2, 6.5, 7.3 5.21, 10.2
3.31, 3.34, 3.37, 3.43 Principal entrance (non-domestic) Sanitary accommodation -
Lifting devices - wall surfaces 0.29, 1.17-1.18, 3.6 changing rooms 5.15-5.18
3.32, 3.42 Principal storey - definition 0.14, Sanitary accommodation - cubicle
Lifting devices - wheelchair 0.30 doors 5.3, 5.4, 10.3
platform stairlifts 3.23-3.24, Principal storey - dwellings 7.1,
3.44-3.49 Sanitary accommodation -
7.5, 10.1-10.3 dimensions 5.7, 5.10, 10.3
Lifting platforms see Lifting Principal storey - toilet provision
devices Sanitary accommodation -
(dwellings) 10.1-10.3 dwellings 10.1-10.3
Lifts see Lifting devices Pull cords 4.20, 4.30, 5.3, 5.10 Sanitary accommodation - en-
Light switches 4.28-4.30, 5.3 Public address systems see suite hotel rooms 4.19, 4.24
Lighting 4.9, 4.34, 4.36 Communication aids Sanitary accommodation -
Lighting - artificial 4.34, 4.36 Public telephones 4.14 enlarged cubicles 5.6, 5.12,
Lighting - conference facilities Push buttons - doors 2.18, 2.21 5.14
4.9 Push buttons - lifting platforms Sanitary accommodation -
Lighting - controls 4.30, 5.4 3.39 entrance storey of dwellings
10.1-10.3
Lighting - lifting devices 3.26 Push buttons - switches and
socket outlets 4.30 Sanitary accommodation - finger
Lighting - sanitary facilities 5.4 rinse basins 5.8
Lighting - uplighters 4.34 Push pads 2.21, 4.28-4.30, 5.3
Sanitary accommodation - grab
Limb storage facilities 5.18 bars 5.4, 5.14
Lip reading and speaking 3.4, Sanitary accommodation - grab
4.6, 4.9, 4.32, 4.34 rails 5.8, 5.10, 5.11, 5.18
Lobbies 2.25-2.29, 3.15-3.16 Sanitary accommodation - hoists
Lockers 3.14 note, 5.18 5.20 note
V
Vertical circulation 3.1,
3.17-3.55
Vertical lifting platforms see
Lifting devices
Vision panels 2.13, 3.10
Visual contrast 0.29, 2.17, 3.8,
3.10, 3.12, 3.18, 3.28, 3.34,
3.43, 4.28, 5.4
Visual contrast - controls 4.28
Visual contrast - definition 0.29
Visual contrast - door furniture
2.17
Visual contrast - internal doors
3.8, 3.10
Visual contrast - lifting devices
3.18, 3.28, 3.34, 3.43
Visual contrast - push pads 4.28
Visual contrast - sanitary fittings
5.4
Visual contrast - seating 4.7
Visual fire alarm signals 4.24
Visual information - lifting devices
3.31, 3.34, 3.37, 3.43
Visual warnings - entrance doors
2.21
W
Wall surfaces see also Surfaces
3.4
Wall surfaces - lifting platforms
3.42
Wall surfaces - materials 4.32
Wall surfaces - passenger lifts
3.32
Wall surfaces - reflective 3.4,
3.32
Wardrobes see Bedrooms
Wash basins see Sanitary
accommodation
Water temperature see Sanitary
accommodation
Wayfinding 4.31
WCs see Sanitary accommodation
Weather protection see Entrance
doors - weather protection
Wheelchair-accessible bedrooms
see Bedrooms
Wheelchair platform stairlifts see
Lifting devices
Widths see Dimensions
Window controls in hotel
bedrooms see Bedrooms
Worktops - refreshment facilities
4.16
Approved Document M
79
M