Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q= 27 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 27 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 234 liters

The available standard size is : 300 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

1070
Project : Dowmat Eljandal 2 - (Domestic pump)

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 25.416 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 25.42 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 221 liters

The available standard size is : 300 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

1080 domesic
Project : Abu Ajram - Abu Makoua - Um nikhela

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 15.624 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 15.62 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 136 liters

The available standard size is : 200 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

1100 Domestic
Project : QURAYAT 2 - 1100A

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 17.64 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 17.64 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 153 liters

The available standard size is : 200 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

1100A Domestic
Project : Dawmat eljandal - Skakka 2 - Elquraiat 1 (filling pump)

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 34.065 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 34.07 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 296 liters

The available standard size is : 300 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

2060 Filling
Project : Dawmat eljandal - Skakka 2 - Elquraiat 1 (filling pump)

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 24.408 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 24.41 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 212 liters

The available standard size is : 300 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

2060 Domestic
Project : FAISALYA - HASSEDA - TABARJEL

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 20.52 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 20.52 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 178 liters

The available standard size is : 200 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

1090 Domestic
Project : skakka elsenaya (2070) - filling pump

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q = 34.056 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 34.06 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 296 liters

The available standard size is : 300 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

2070 filling
Project : skakka elsenaya (2070) - Domestic pump

Calculating the pressure tank size

Pressure tank size formula is given as follows :

Drawdown volume
cut-out pressure - cut-in pressure
size = ( cut-out pressure + 1 )

Drawdown is based on pump capacity and the number of start/stops per hour and amount of water
which can be taken from the tank before the pump starts.

250 x Q
Drawdown in liters = I

250 x Q x (cut-out pressure + 1)


Tank size in liters = ( I x ( cut-out pressure - cut-in pressure ) )

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.

Data : Pump type & model :


Motor power rating P= kw
Number of starts/stops I = 80 1/h ( from pump manufacturer )
Average pump flow Q= 18 m3/h
cut in pressure = 2.2 bar
cut out pressure = 4 bar

250 x 18 x ( 4 + 1 )
Tank size in liters = ( 80 x ( 4 - 2.2 ) ) = 156 liters

The available standard size is : 200 liters

Recommended tank size is : liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.