CABLE NOTES AND DETAILS FOR COMPANIA MINERA ANTAMINA, S.A. ANTAMINA PROJECT PERU BECHTEL INTERNATIONAL, INC. JOB No. 24097 2 Ban ot Revised Sheet 7 Q~ 1 10/26/99 Revised as Noted JW. KVP SH oO 5/21/99 Issued for Construction Jw KVP MK PK A 4/28/99 Issued for Approval JW. KVP SH REV. | DATE REASON FOR REVISION ORIG | SUPV | CHIEF | PE | CLIENT DOCUMENT No. 24097-0000-E-008 ‘000008 Ra.doe Sheet | Latest | sheet | uatest | sheet | tatest | sheet | Latest | sheet | uatest Rev. Rev. Rev. Rev Rev a 2 B 2 a 2 2 2 3 2 4 2 5 2 6 2 7 2 CABLE Kones 20D DETAILS ‘DRAWING WO. 0000-R-008 | REV 2 ‘JoB WO.» 24097 oa GENERAL NOTES 1.0 For wire and cable general notes, see Electrical Construction Specification 24097-GE-004. 2.0 INSTALLATION 3.0 40 5.0 2.1 For general notes on cable installation, refer to Specification 24097-GE-004, Electrical Construction, paragraph 7.0. 2.2 For general notes on cable termination, refer to Specification 24097-GE-004, Electrical Construction, paragraph 8.0. TESTING For general notes on cable testing, refer to Pre-operational Testing Specification 24097-PT-001. CABLE NUMBERING SYSTEM For cable and wire numbering system, refer to Drawing 0000-E-003. CABLE DERATING FOR ALTITUDE The derating factor of 0.94 shall be used to derate the cable ampacity for 4300 meter altitude. For cable selection, divide required cable ampacity by 0.94 and select cable size from applicable sea level ampacity tables. BecuTst, ‘CABLE NOTES AND DETAILS ‘DRAWING HO. 0000-B-008 | REV 2 ‘JOB WO.; 24097 wea |AMPACITIES OF INSULATED COPPER CONDUCTORS RATED 0-2000 VOLTS, CONDUCTOR TEMPERATURE 75°C AMBIENT AIR TEMPERATURE 40°C. ay (2) (3) (4) Not more than | Not more than| 3/C Cables in | 3/C Cables in 3 Conductors | 3 Conductors | Tray with | U/G Raceway in Raceway | in Raceway | Solid Raised | 6 Circuits or Cable or Cable Cover 100% LF Ambient Air | Ambient Air RHO 120 Conductor Size Temp. 30°C | Temp. 40°C | (Necate-11) | Earth temp (for ref. only) 20°C AWG/ | Nearest | NEC Table 9 kemil mm?_| 310-16, 75°C | Col(1)x0.88| Col (2) #12 4 25 20 20 #10 6 35. 30 30 #8 10 50 44 44 39 #6 16 65 57 57 51 #4 25 85 75 75. 65. #2 35 115 101 101 83 #210 70 175 154 154 124 #410) 120 230 202 202 155 250 120 255 224 224 169 350 185 310 273 273 202 500 240 380 334 334 240 Lighting and convenience outlet conductors shall be sized to limit the voltage drop (between lighting / receptacle panel to the farthest outlets) to 3%, Maximum loading allowed by NEC table 310-16 footnote is 20A on #12 AWG and 30A on #10 AWG. BECHTEL ‘CABLE NOTES AND DETAILS ‘DRAWING HO. _9000-H-008 | REV 2 ‘JOB WO.+ 24097 cz |AMPACITIES OF INSULATED COPPER CONDUCTORS IRATED 2001 - 5000 VOLTS, CONDUCTOR TEMPERATURE 90°C [AMBIENT AIR TEMPERATURE 40°C. q) (2) (3) (4) 3/C Cable | 3/C Cable in | 3- 1/C Cable | 3 - 1/C Cable Isolated Isolated in Isolated in Tray in Air | Conduit in Air | Conduit in Air | _ with Solid or in Tray Raised Cover with Solid Conductor Size Raised Cover (NEC 318-1301) (NEC 318-13a) (Table 310-69) AWG/ | Nearest | NEC Table | NEC Table [ NEC Table | Derating kemil mme 310-71 310-75 31 [310-69] x.75 SL #2 35 140 125 130 #2/0 70 215 190 205 225 #4/0 120 285 255 280 300 250 120 320 280 315 334 350 185 395 350 385 413 500 240 485 425 475 521 750 400 615 525 600 675 ‘RETR PROTECT secures ceamus noms aND DETAILS ‘DRAWENG Wo. 0000-8-000 | REV 2 o> |AMPACITIES OF INSULATED COPPER CONDUCTORS IRATED 5001 - 35000 VOLTS, CONDUCTOR TEMPERATURE 90°C |AMBIENT AIR TEMPERATURE 40°C. a) (2) (3) (4) 6) IC Cable | 3-1/C Cable | 3 - 1/6 Cable |3-1/C cables in] 3-1/C cables in Isolated | intsolated | inTray | U/G Raceway | UG Raceway inair | Conduitin Air} with Solid ] 10Circuits | 1 Circuit Raised Cover | 100%LF | 100% LF RHO 120 | RHO 120 Conductor Size (Nec 318-1301) | Earth temp | Earth temp (Table 310-69) | 20°C * 20°C AWG/ | Nearest | NECTable | NECTable | Derating Cale Cale kemil mme 310-71 310-73 _| [310-69]x.75| _E-002 E002 #2 35 165 150 #210 70 245 225 225 #410 120 325 295 300 250 120 360 330 330 172 325 350 185 435 395 409 204 393 500 240 535 480 510 243 478 750 400 670 585 652 295 596 The minimum size of cable for 23 kV service shall be 250 kemil. ** Column (4) ampacities are for 12-PVC ducts in 4 row x 3 column arrangement with 2 middle ducts not used for power cables. ‘pecert DREANTRA PROTEGE 0000-8008 | REV 2 480V - 400Y/230V 3 PHASE TRANSFORMER PRIMARY, SECONDARY CB Size | Cable | Metric CBSize | Cable | Metric KvA | FLA |(NECMax| Size | Size | FLA |(NECMex| Size | Size 250%FL) (mm?) 125%FL) (mm) 15.0 | 18.04 40 Al #8 10 | 21.65 25 Al #0 6 22.5 | 27.06 60 Al #4 25 | 32.48 [40 Al #8 10 30.0 | 36.08 80 Al #2 35 | 43.30 50 Al #6 16 45.0 | 54.13 | 128 A | #2/0 70 [64.95 | 80 Al #2 35. 75.0 | 90.21 200 A| #40 | 120 | 108.25 | 125 Al #2/0 70 112.5 | 135.32 | 320 A 500 | 240 | 162.38 | 200 A| #4/0 |" 120 150.0 | 180.42 | 378 A| 2-#4/0 | 2-120 [21651 | 250 A] 350 | 185 480V - 120V SINGLE PHASE TRANSFORMER PRIMARY. ‘SECONDARY CBSize | Cable | Metric CBSize | Cable | Metric KvA | FLA |(NECMax| Size | Size | FLA |(NECMax| Size | Size 250%FL) (mm?) 125%FL) (mime) 75 | 15.63 32 Al #8 10 | 62.50 70 Al #4 25 10.0 | 20.83 40 Al #8 10 | @3.33 | 100 Al #2 35 15.0_| 31.25 60 Al #4 25 | 125.00 | 150 A #2/0 70 25.0 | 52.08 | 128 Al #2/0 70 | 208.33 | 250 A| 350 185 375 | 78.13 | 150 A| #2/0 7o [312.50 | 350 A| 2-#4/0 [ 2-120 NOTES: (1) For proper coordination, the minimum primary breaker trip for 3 phase transformer = Secondary main breaker trip X 1.5 X 1.16 X Vs/Vp. (2) For proper coordination, the minimum primary breaker trip for 1 phase transformer = Secondary main breaker trip X 1.5 X Vs/Vp. (3) Cable sizing is based on 3 conductors in conduit in air, 40°C ambient temperature, and breaker termination of 60°C for wire size up to #1 AWG and 75°C for wire size > #1/0 AWG. (4) The secondary cable length shall not exceed 3 meters. If more than 3 meters, the cable shall be sized for minimum 1% voltage drop. ‘JOB WO.+ 24087 eS ELECTRICAL DESIGN BASIS ‘GONDUGTOR ANPAGTY ame | wre | rua | 125 | 094 | ste | cont ve Two | ae | oe | a4 | ea [ 220 | suo | 250 [ a50 T s00 equv| at | x. |doraty 25.01 350 5.0 [050 [1150 [1750 [es00 [255.0 [a100 T3900 110] we | sw | asov | ets fioratt| size | ara [200 [300 a0 [57.2 | 78 [ror 11540 Teves Lees levee Loses [2 Mayium Molor Fess Leng in meters for 9% Votiags Drop (480V) asl oa 10{ sal 1st 1 [ase [ans oss| tat 1st sal 1 021 i I a{o7sl— sat al eat 1 | 4a [7m ws salze[ ast asl 4 1 4a [50 t 2{ 1s] sel 4a{ 5/1 [asa azo ie 4e{ sol es| + | ean { 208 | s00. s{ zl 7st ast ios 1 a | aot | sr. I zs| sel iol isa[ els | sea {190 | zor [on vol —7s| 140} ast tse + {tea {roe {ise | eae | 06 { 1s] sil anol esa 258 105 [165 | 257 {386 ots a7ol saa | sso| 2 Et 00 1s|_szol sas | aso] 2 | 42a “oe | 159 | eas [357 30 #o0| soo] sxz]_3 | 63a a5 _[ 202 | 308 T 40 | aol se.0| 6501 601 3A 16 | ase | as [ { sof —a7| esol eral ose 204 187_| 340 t co] —asl_rzo{ 96a] soze | 4 | 1250 [158 —[ear [308 2 60 i200! wr7] 4 | i zoo | sie [ser joo] 7s) vae.0 | 156.01 1649] 4 | vena t zis | 258 | 28 i 1580 [19501 207.¢| 5 [saa | 105 | 21s | 260 [st ‘150 —a12) 1800 | 228.0 | 239.4 S208 25 | 270) 2001 14a} 24001 3000 | a191 1 5 | s20a. 202 [Efoctve 2 Por 1000m 340 Cu, 600V Cable, | | |2% PE In Stoel Duct (NEC Table 108 {2.208 | 1476 |oges. toss: lozse |ozse [ote7 |o164 [Max Amp mater per 334 Voltage Drop AL4E0V 1429 | 2208 | 3470 [5998 | e097 [12145 [zz0as [2oase [as275 |4oeas |4a5e2 CABLE DATA AND CONDUIT SIZING [Type etrW TE Gable -<1C wiGround [Power Condcoe Size svz_| 10 | oo wo | 250 500 [Ground Conducta: Size a2 [#10 | a ig (eg Tos [ve Power Conductor - Nearest Matic Size mm 4 4 ‘20_| 120 | 105 [aco ind Conductor Nearest Mati Size ( 4 [ete [2s [2s 35 1 te OD fin) ae uss | a7s [197 [ozs | [aves (Savare inch) oss [oz [ose 129 nut Sie for Power Gable as fas f+ xt [Condit Nearest Matic Size in mm 20 | 20 5 [Tota 00 -.9¢ Power & 71C Contol Cables oo [10 | 4 area [rota Ares = SIC Power & 7/C Control Cable ost | oas [oso elas ecel a rd Sio for Power & Control Cables as [is [1s ale [Conduit Nearest Mati Sizo in mm 4o| ao [40 Notes: 1. Conductor ampacity based on 75°C conductor temporature at 30°C ambiont por NEC table 810-16. 2. Design ambient temperature = 40°C, Conductor ampacity (40°C amb) = Conductor ampacsty (30°C amb) x 0.88. 2. The derating factors of NEC Art. 310, Note 8() shall not apply to the ampactty of cable in cable tray. 4, TC cable installed in cable tay shall bo por NEC 318-9, 5. Maximum loading allowed by NEC: 20A on #12 AWG, 30A on #10 AW. (NEC table 310-16 footnote) 6. Three phase AC motor full load current (FLA) is based on NEC table 430-150. 7. Values in this column represont roquired cable ampacity for motors at Port facies. 8. Values in tis column represent required cable ampacty for motors at 4300 m altitude. Alttude do-roating factor = 0.94. 9. The continuous rating for breakers in tartor units are based on ABB MO825, S2X, SoH and SSH breakers, (See Sheet 7) sEcHTa, CABLE NOTES AND DETAILS ‘DRAWING HO. _0000-8-008 | Rav 2 toner ep a suopeutieep sh peraucsoenpcoeb00 464 encooroLeu STESY mse er co ey on os o | 2 oa, ots | ae, a, Ses jun souEig ‘uoposyeid yeuuouL sopRqU0D soyoaig eee! LF DL OF 39H Tod woRTEUTPIOOD VA OF (ODED = Hers Amp KAvem) ANAT SIOUEIS QOW A'T UF styesedde ynoayp wyour 404 qe BuyuorsUOULG, pan opang spine8A one ‘ay sweets AT 6a Cees ora < ‘DRAWING HO, 0000-R-008 | REV 2

You might also like