Add#2: RFI 031

Item 2.51
On plan sheet M307, the 48” RW pipe installed into the Rapid Mix Base slab refers you to detail
1509231. This does not appear to be the correct detail. Please confirm that the spool coming up
through the slab should be a PE x WC x PE that is flush with the finish floor.
The 48” RW pipe installed into the Rapid Mix base slab should have a RJ spigot x WC x PE wall
pipe with PE installed flush to the floor.