fuel sensor (KELLER 4 to 20mA) configuration in DSE7320 with resistance Input
Additional required Items
100Ω resistor = 1 unit
50Ω resistor = 1 unit
Installation
50Ω resistor is connected parallel with sensor common ground to analog input C.
100Ω resistor is connected series with fuel sensor output cable and connected to analog input C.
Sensor black cable to +ve 12V
Sensor red cable to controller analog input
As below picture.
Setting the Graph in DSE7320 configuration
Connect the computer to DSE controller using USB cable
Open the DSE configuration Suit
Click “Read Configuration from a module”
Click “Inputs”
Click “Fuel level”
Click “Edit”
Set the percent points as below
64Ω = 0%
80Ω = 10%
96Ω = 75%
112Ω =130%
128Ω = 150%
Click “Save”