You are on page 1of 8

FA L L 2 0 0 6

V O LU M E 1 8 , N O. 4
PLUS:
䡲 Market Outlook '07
䡲 Evolution of the Valve Industry
䡲 Back to Basics: Relief Valves
䡲 Desuperheating for
Temperature Control
䡲 Castings or Forgings?

Fundamentals of
Electric Actuator
Control
A VIEW OF THE ELECTRICAL
FUNCTIONS OF A MOTOR ACTUATOR
FUNDAMENTALS OF
ELECTRIC ACTUATOR
CONTROL
ELECTRIC ACTUATORS HAVE BECOME A
E very motor requires controls,
and the motor of an electric
valve actuator is no different. The POPULAR WAY TO AUTOMATE ALL TYPES
function of the electric actuator’s OF INDUSTRIAL VALVES. ONE OF THEIR
controls is to start and stop the PRIMARY ADVANTAGES IS THE
motor. Those controls typically
consist of the motor switchgear, INHERENT FLEXIBILITY OF THEIR
devices that control that CONTROLS BOTH BECAUSE OF WHERE
switchgear and various interfaces
with the plant control system.
THE CONTROLS CAN BE LOCATED AND
A simple on-off switch or a BECAUSE OF THE WIDE RANGE OF
switch and a motor starter can CONTROL SYSTEM INTERFACES
control a fan motor that oper-
ates in only one direction. How- AVAILABLE.
ever, a valve actuator motor
BY RICHARD D. OAKS
must be controlled considering
criteria such as:
䡲 valve position motors, this can be accomplished by reversing two of the three motor power
䡲 torque or thrust output leads or phases. We achieve phase reversal by using two motor starters, which
䡲 motor protection work together to be what we commonly refer to as a reversing starter.
䡲 control system commands Figure 1 shows how a reversing starter reverses the direction of a motor.
䡲 local control When Coil A is energized, Contacts A close, and the motor runs in the
䡲 operation in both direc- clockwise direction. When Coil B is energized, Contacts B close, and the
tions (since we want to motor runs in the counter-clockwise direction. Note that motor power leads
open and close the valve). L1 and L3 are reversed when Contacts B are energized as opposed to when

Controlling the Motor


Contacts A
To control the motor, contacts
large enough to handle the cur- L1
L2 Motor
rent required for starting and
L3
running the motor must be pro-
vided. Those contacts are
Contacts B
engaged and disengaged by a
magnetic coil. The contacts and
coil make up a magnetic starter.
That starter’s contacts make
and break the power to the
Coil A
motor as the starter coil is ener-
gized and de-energized.
Since an actuator must oper- Coil B
ate in both directions, we need a
means to reverse the direction of Figure 1—Reversing starter: Coil A pulls in Contacts A, resulting in clockwise motor rotation.
the motor. For three-phase Coil B pulls in Contacts B, resulting in counter-clockwise motor rotation.

Valve M A G A Z I N E © 2009 Valve Manufacturers Association. Reprinted with permission.


Contacts A are energized. Con- has reached the open or closed end actuator motor to de-energize at
versely, when the coils are de-ener- of travel so the motor can be de- each end of travel.
gized, the contacts open and the energized. A supplementary sensing method
motor will stop. Various methods of position is continuous position feedback
Most reversing starters are fur- sensing are used. The most com- throughout the entire valve stroke.
nished and configured with mechan- mon is a mechanically operated This indicates to an operator or
ical and electrical interlocks. This is switch referred to as a limit switch. process control system the current
a redundant system whose purpose The switch is physically tripped by valve position at any point of valve
is to ensure both starters will not a mechanism operated by and travel. The operator is then able to
energize at the same time. mechanically linked to the output view valve position as 0 to 100%
The motor power available in of the actuator. The most effective open on a meter at a control con-
industrial facilities varies. Typically, method for tripping the switch is to sole. The position feedback signal is
three-phase motor power available use a counter gear device, but usually 4 to 20 milliamps from a
in North America is 460 volts / 3 cams can also be used to mechani- transmitter, but it also can be a
phase / 60 hz. The power available cally trip switches. resistance reference from a poten-
in many overseas facilities has a fre- Another method of position sens- tiometer.
quency of 50 hz. Voltage ranges ing is a proximity switch, which
from 208 to 600 volts. operates similar to the mechanically Torque Sensing
In a similar manner, reversing the operated switch, but without the Torque sensing is needed to limit the
two power leads with reversing physical tripping mechanism. output torque of the actuator. The
starters operates single-phase In addition, an encoder can be torque-sensing switch is commonly
motors. Generally, single-phase actu- used to sense position. The encoder called a torque switch, and several
ator motors also are furnished with senses mechanical motion or travel methods of sensing are used. The
starting capacitors. In some cases, and translates that information into most widely used method is to meas-
single-phase motors can be operated electronic data. The two types of ure the actuator output torque by
without reversing starters. For exam- encoders are absolute and incre- determining the axial movement of
ple, a switch can be used to reverse mental, and both are used in elec- the actuator’s sliding worm gear,
the power leads. In this case, all tric actuators. Incremental which compresses springs. The axial
motor control contacts are subject to encoders have output signals that movement is converted to a rotary
the current drawn by the motor, so repeat over the full range of travel, movement, which trips a switch.
we must assure the contacts both in so each position is not uniquely That same rotary movement can
the actuator and in the process con- defined. When the incremental also drive an encoder.
trol system are capable of accommo- encoder is turned on, the position is A second method of sensing is to
dating the motor current. unknown since the output signals measure the motor current. By cor-
In addition to magnetic reversing are not unique to a specific posi- relating that current to output
starters, solid-state starters are tion. Absolute encoders, on the torque, a switch can be tripped at a
sometimes furnished with actuators. other hand, have a unique value for specific value of current and, there-
Solid-state starters do not have each position. When an absolute fore, the torque at that value.
moving parts, and they switch the encoder is turned on, the position is A third method involves measur-
power to the motor electronically. known. For both types of encoder, ing motor speed by rapidly sensing
Generally, these devices are used in there are various methods to deter- position changes. The motor speed
rigorous modulating applications mine the position for the encoder, is high without load and falls as the
when the actuator is expected to but with electric actuators, the load or torque output rises. By
start up to 1,200 times per hour. methods are magnetic and optical. compensating for voltage and tem-
With all encoders, the information perature variations, a correlation
Position Sensing is gathered and stored electroni- can be established between motor
Position sensing is primarily cally, so the end-of-travel positions speed and torque output. Torque
needed to determine when the valve can be programmed, enabling the limits can then be determined rela-

© 2009 Valve Manufacturers Association. Reprinted with permission. Fall 2006


E L E C T R I C A C T U A T O R C O N T R O L

tive to that speed. current reaches a specific level, a


Another method uses a load cell switch trips and the motor is de-
and switch in conjunction with the energized. Typically, the switch then
sliding worm gear. resets automatically.
In all cases, a switch is tripped or
an electronic device signals when a Control Power
certain level of output torque is The actuator motor often draws rela-
reached, and the actuator motor is tively high current, up to several hun-
de-energized. dred amps at a high voltage such as
the 460 volts previously mentioned.
Motor Protection The control circuit, however, is
Many motors in industry, such as always low voltage—DC or single-
those used to operate pumps and phase AC with low current—usually
fans, are designed to operate con- less than one amp. As a result, a con-
tinuously. Motors in electric motor trol transformer or power supply is
actuators, however, are not provided with the motor controls.
designed to operate continuously— The power supply converts the motor
they are designed to generate high power to control power. For example,
output torque instantaneously for Figure 2—Local controls: open-stop-close
460 volts / 3-phase motor power
the purpose of unseating a valve. pushbuttons; open-fault-close indicating might be converted to 24 volts DC or
Continuous running could result in lights; local-off-remote selector switch 120 volts AC. In some facilities, the
the motor overheating, insulation plant control system provides 24
breaking down and possible motor when a certain temperature is volts DC for the actuator control cir-
failure. As a result, the motor must reached, the switch trips and de- cuit.
be protected from the excessive energizes the motor. When the
accumulation of heat. motor windings cool, the switch Local Controls
One method of protection is to remakes, and the motor circuit is Another element that affects motor
install one or more thermal switches restored. control is use of local controls.
in the motor windings. These Another method of protection is These devices can directly operate
switches operate like thermostats— to sense motor current. When the the valve. Typical local controls are

Open
Direction
Starter
Three Phase Contacts
Power Motor
Closed
Direction
Control Supply Starter
Power Contacts

Open Open
Open
Direction Direction Open Direction
Position
Control Torque Starter Coil
Sensor
Signal Sensor
Motor
Protection
Closed Closed
Closed
Direction Direction Closed Direction
Position
Control Torque Starter Coil
Sensor
Signal Sensor

Figure 3—In this motor control logic block diagram, the power circuit is shown with blue lines and the control circuit with green lines.

Valve M A G A Z I N E © 2009 Valve Manufacturers Association. Reprinted with permission.


pushbuttons—for local open-stop-
close control and selector
switches—generally for local open-
stop-close control or selection of
local-off-remote modes of opera-
tion.
In addition to controls, indicating
lights are used to designate various
actuator status criteria such as
when:
䡲 open valve position is reached
䡲 closed valve position is
reached
䡲 the monitor relay is tripped
䡲 over-torque condition occurs
or
䡲 the selector switch is in the
remote position.
Figure 2 shows a typical local
control station with three pushbut-
tons (open-stop-close), a selector
switch (local-off-remote) and three
indicating lights (open-fault-close).

Motor Control Circuit


We now have several important Figure 4—An electric actuator with integral motor controls
devices that must be tied together to
control the actuator motor. Each
direction of travel has a control cir- has not been reached and the pre- cuit boards. The availability of
cuit in which the controlling devices set torque limit has not been LEDs and dip switches on the cir-
work together logically to control exceeded. The starter coil will pull cuit boards and interfaces with PCs
the respective motor starter. in the starter contacts, and the gives actuator users the ability to
Figure 3 shows a block diagram motor will run until the starter easily change control circuit param-
of an actuator motor control circuit. drops out, which will occur when the eters, such as selecting position or
The motor power components are position is reached, the torque torque seating for the clockwise
connected with blue lines. Those exceeds the pre-set limit, the control direction or counter clockwise direc-
components are the input of the signal is removed, or the motor pro- tion of actuator rotation.
control power supply, the open tection trips. The closed direction
starter contacts, the closed starter control signal, limit switch, torque Where Are
contacts and the motor. The control switch and starter coil are similarly Controls Located?
components are connected with configured. The output of the con- The location of the electric actuator
green lines. An open direction con- trol power supply and motor protec- controls varies. While the position
trol signal, open position limit tion devices are usually common to sensing, torque sensing and motor
switch or sensor, and open direction both circuits. thermal switch protection devices are
torque switch or sensor are tied In the past, these devices were all always at the actuator, the rest of the
together in series with the open hard-wired into an electrical control controls (reversing starters, power
direction starter coil. When we get circuit. Most actuators furnished supply, control logic and local con-
a signal to open the valve, the open today perform the same function trols) can be located either at the
direction starter coil will be ener- electronically by connecting the actuator or remotely.
gized as long as the open position devices with electronic-printed cir- When the motor controls are

© 2009 Valve Manufacturers Association. Reprinted with permission. Fall 2006


E L E C T R I C A C T U A T O R C O N T R O L

allowing the actuator motor to run


until a limit is reached, the torque
switch trips or the control contact
is opened. When the control circuit
is interrupted, the starter drops
out and the motor stops.
A local-off-remote selector
switch is frequently used to allow
plant personnel to select between
controlling with integral
pushbuttons or remote open-and-
close contacts. This switch is
usually furnished with the local
controls.
A 4-20 milliamp analog signal
also can be used to position an
automated valve at or between the
fully open or fully closed positions.
Generally, 4 milliamps is a close
signal while 20 milliamps is an
open signal, and any signal
between 4 and 20 commands
the valve to go to a position
proportional to the signal—for
example, 12 milliamps is a 50%
open signal.
The device that accepts the
analog signal is known as a
Figure 5—An electric actuator with remote motor controls
positioner. It compares the
command signal (usually 4-20 mA)
located at the actuator, they are practice when the automated valve and the present valve position
described as integral controls. is inaccessible or located in an commonly known as position
Figure 4 shows an actuator with environmentally unfriendly spot feedback (usually 4-20 mA or 0 to
such controls. Over the past 20 such as places with high-ambient 5000 ohms). The positioner
years, the trend has increasingly temperatures or that are frequently determines the difference between
been toward furnishing integral submerged. the two values and energizes the
controls with electric actuators. open-or-close motor control
This configuration is preferred Control Signals circuits accordingly. For example,
because of its high degree of relia- Control of electric actuators is if 4 milliamps represents the
bility, since the entire control pack- very flexible. Command control closed position and the command
age is designed, assembled and signals can originate from a device signal is 8 milliamps while the
tested by one responsible sup- as simple as a local open-stop- feedback signal is 12 milliamps,
plier—the actuator manufacturer. close switch or pushbuttons. the positioner will determine what
When the motor controls are Contact closure or discrete open- is required for the valve to travel
located in a remote location, they and-close control signals can also from the 12 milliamp position
are called remote controls. Figure originate from remote control toward the 8 milliamp position,
5 shows an actuator with remote stations or process control therefore driving the actuator in
controls and cabling between the systems. With contact closure, a the closed direction.
actuator and controls. Furnishing normally open contact closes, The positioner is furnished with
the controls remotely is common completing the control circuit and the motor controls. Analog signals

Valve M A G A Z I N E © 2009 Valve Manufacturers Association. Reprinted with permission.


are frequently used to control
automated valves in process ACTUATOR CONTROLS CHECKLIST
control applications requiring
positioning or modulating service. 䡺 Are the motor controls to be integral with the actuator?
As with the contact closure
example, a local-off-remote switch 䡺 If the controls are going to be remotely mounted, is the actuator
is generally furnished with the
supplier expected to furnish them?
positioner. In this case, we select
between the integral pushbuttons
in the local position and the 䡺 What is the available motor power?
positioner in the remote position.
Digital communication or field- 䡺 How are the actuators going to be controlled (discrete signals [24
bus technology is also used to com- VDC or 120 VAC], analog signal [4-20 mA], fieldbus [PROFIBUS
municate control signals from a DP, DeviceNet, Modbus, Foundation Fieldbus], etc.)?
control system to individual valves.
With a conventional control system, 䡺 Are there any other special control considerations (solid-state
as many as 16 dedicated control
wires can be running from the con- starters, special local controls, control power furnished by control
trol station to each actuator. The system, etc.)?
cost of the wire, conduit and instal-
lation labor for a conventional con-
trol system is high. With a fieldbus
system, the control station is wired (PLC). This PC or PLC may be
to each actuator with a common bus tied into a larger distributed
or fiber optic cable. The cost of control system, supervisory control
cabling material and installation is and data acquisition system, or
significantly lower when compared plant-wide network.
to a conventional system. In addi-
tion, other control instruments such Summary
as transmitters, or controlled As this article shows, control of
devices such as pump or fan motor electric actuators is very flexible.
starters, can be added to the same Many types of control configura-
control bus. Plus, more information tions and technologies can be used
can be transmitted from the actua- to control an actuator electrically.
tor to the control system, including It is important for the purchaser or
the number of valve operating specifier to clearly indicate to the
cycles, motor thermal switch trip, actuator supplier how the actuator
limit switch trip or torque switch is to be controlled as well as what
trip in mid travel and diagnostic controls they expect the supplier to
data. This information can be a furnish. VM
valuable tool to the plant owner,
operating personnel and mainte-
RICHARD D. OAKs is
nance staff. marketing manager
The means of communication is for AUMA Actuators,
by one of many protocols such as Inc. (www.auma-
Profibus, DeviceNet, Modbus or usa.com), Canonsburg,
Foundation Fieldbus. When we use PA. He is a member of
Valve Magazine’s Edi-
digital communications, the torial Review Board.
control station is a computer or Reach him at 724.743.2862 or via email at
programmable logic controller richo@auma-usa.com.

© 2009 Valve Manufacturers Association. Reprinted with permission. Fall 2006


1o°°
   ,  /

"1 
/" -

$VDZRUOGOHDGHULQSURYLGLQJUHOLDEOHDXWRPDWHGYDOYH
$V D ZRUOG OHDGHU LQ SURYLGLQJ UHOLDEOH DXWRPDWHG YDOYH
FRQWUROV $80$ KDV DOVR EHFRPH D OHDGHU LQ RIIHULQJ
D ZLGH UDQJH RI QRQSURSULHWDU\ GLJLWDO FRPPXQLFDWLRQ
SURWRFROV WKDW HQDEOH RXU DFWXDWRUV WR LQWHUIDFH ZLWK
'HYLFH1HW )RXQGDWLRQ )LHOGEXV 352),%86 '3 DQG
0RGEXV 578
,Q DGGLWLRQ $80$ RIIHUV UHGXQGDQF\ WKH SRVVLELOLW\ WR
FRQQHFW YLD ILEHU RSWLFV DQG WKH FDSDELOLW\ WR PRXQW WKH
DFWXDWRU FRQWUROV UHPRWHO\ IURP WKH DFWXDWRU
,QYHVWLJDWH QRZ KRZ RXU DFWXDWRU WHFKQRORJ\ ZLWK WKH
ZLGH RIIHULQJ RI GLJLWDO FRPPXQLFDWLRQ SURWRFROV FDQ KHOS
VLPSOLI\ YDOYH FRQWURO LQ \RXU RSHUDWLRQ

$80$ $FWXDWRUV ,QF


 6RXWKSRLQWH %OYG
&DQRQVEXUJ 3$  86$
3KRQH  
)D[  
(0DLO PDLOER[#DXPDXVDFRP
ZZZDXPDXVDFRP

You might also like