You are on page 1of 1

Twido Overview

Feature Description
Programming port All bases: EIA RS485
TWDLC•E40DRF compact bases: Built-in RJ45 Ethernet communications port
Expansion I/O 10 and 16 I/O compact bases: no expansion modules
modules 24 I/O compact and 20 I/O modular bases: up to 4 expansion I/O modules
40 I/O modular and 40 I/O compact bases: up to 7 expansion I/O modules
AS-Interface V2 10 and 16 I/O compact bases: no AS-Interface bus interface module
bus interface 24 I/O and 40 I/O compact, 20 I/O and 40 I/O modular bases: up to 2 AS-Interface bus interface
modules modules
CANopen fieldbus 10 and 16 I/O compact bases: no CANopen fieldbus interface module
interface modules 24 I/O and 40 I/O compact, 20 I/O and 40 I/O modular bases: 1 CANopen fieldbus interface
module
Remote link Maximum 7 slaves by remote I/O or peer bases.
communication Maximum length of entire network: 200 m (650 feet).
Modbus Non-isolated EIA RS485 type, maximum length limited to 200 m.
communication ASCII or RTU mode.
Ethernet TWDLCAE40DRF, TWDLCDE40DRF compact bases and 499TWD01100 Ethernet interface
communication module: 100Base-TX auto-negotiated type Ethernet communications over TCP/IP protocol, via
built-in RJ45 port.
ASCII Half-duplex protocol to a device.
communication
Dedicated function Fast counters TWDLCA•40DRF and TWDLCD•40DRF Compact bases: 4
blocks All other compact bases: 3
All modular bases: 2
Very fast counters TWDLCA•40DRF and TWDLCD•40DRF compact bases: 2
All other compact bases: 1
All modular bases: 2
PWM/PLS All modular and 40 I/O compact bases: 2
Analog 24 I/O and 40 I/O compact bases: 2
potentiometers All other bases: 1
Built-in analog Compact bases: none
channel Modular bases: 1 input
Programmable Input filter time can be changed during configuration
input filter No filtering or filtering at 3 ms or 12 ms
I/O points are configured in groups

24 35011387 06/2011