You are on page 1of 1

07.04.

2017

Operating Theatres

This has reference to your request to provide information on particulate cleanliness classification appropriate
to operating theatres.

Details of Operating theatres: ISO 14644-1 Laminar Flow Diffuser


Designation Size L x W / (mm)
1. Hybrid Theatre ISO 5 2800 x 2800
2. Cardiac Theatre ISO 5 2800 x 2800
3. Neurosurgery Theatre ISO 5 2800 x 2800
4. Orthopaedic Theatre ISO 5 2800 x 2800
5. General Surgery ISO 5 2800 x 2800
6. General / Plastic Surgery ISO 5 2800 x 2800
7. Urology / General Surgery ISO 5 2800 x 2800
8. Gynaecology ISO 5 2800 x 2800
9. General Purpose Theatre ISO 7 2400 x 2400
10. General Purpose Theatre ISO 7 2400 x 2400
11. Minor Operations ISO 8 1400 x 2400
12. Septic Theatre ISO 7 2400 x 2400
13. Eye Theatre ISO 7 1400 x 2400
14. General / Eye Surgery ISO 5 2800 x 2800
15. ENT Theatre ISO 7 1400 x 2400
16. General Purpose Theatre ISO 7 2400 x 2400
17. Accident & Emergency Theatre ISO 7 2400 x 2400
18. Accident & Emergency Theatre ISO 7 2400 x 2400
19. Obstetrics Theatre ( caesarean) ISO 7 1400 x 2400
20. Obstetrics Theatre (caesarean) ISO 7 1400 x 2400

Reference: HTM 03-01, DIN 1946-4, VDI 2167-1, UNI 11425:2011