Operation Manual
026-1704 Rev 8
Emerson Commercial and Residential Solutions
1065 Big Shanty Road NW, Suite 100
Kennesaw, GA 30144
770-425-2724 • 1-800-829-2724
www.emerson.com
Email: ColdChain.TechnicalServices@Emerson.com
Table of Contents • 5
5.1. STATUS LED............................................................................................................................................................... 19
5.2. TX AND RX LEDS ....................................................................................................................................................... 19
5.3. CODE A AND CODE B LEDS ...................................................................................................................................... 19
5.4. RELAY OUTPUT LEDS ................................................................................................................................................ 20
6 THE MULTIFLEX HAND-HELD TERMINAL INTERFACE ............................................................................. 21
6.1. MULTIFLEX I/O BOARD HAND-HELD TERMINAL SCREENS ....................................................................................... 21
6.1.1. Navigation ........................................................................................................................................................... 21
6.1.2. Opening Screen ................................................................................................................................................... 22
6.1.3. Board Address ..................................................................................................................................................... 23
6.1.4. Settings ............................................................................................................................................................... 23
6.1.5. Input/Output Select Menu.................................................................................................................................... 23
6.1.6. Input Screens ....................................................................................................................................................... 24
6.1.6.1. Input Status/Config Menu................................................................................................................................................. 24
6.1.6.2. Status-Volts....................................................................................................................................................................... 24
6.1.6.3. Status-Eng Units ............................................................................................................................................................... 24
6.1.6.4. Input Config ...................................................................................................................................................................... 24
6.1.7. Relay Output Screens .......................................................................................................................................... 25
6.1.8. Analog Output Screens........................................................................................................................................ 26
6.1.8.1. Analog Status/Override..................................................................................................................................................... 26
6.1.9. Analog Fail-Safes................................................................................................................................................ 27
6.1.10. Digital Status (PWM) ....................................................................................................................................... 27
6.1.11. Digital Period Status........................................................................................................................................ 27
6.1.12. Config Fail % Screen ....................................................................................................................................... 28
7 WIRING CONNECTION TO SITE SUPERVISOR................................................................................................ 29
8 RELAY OUTPUT TEST MODE................................................................................................................................ 30
RS-485
Analog
Outputs (4)
Table 1-2 shows the available models of
Port
Network
MultiFlex combination input/output boards.
Status LEDs
Hand-Held
Relay Output
Terminal Jack
Indicator Lights (16) P/N Model Name Description
S4 and S3 General Status LED Input
Network Address
Switches
Connectors (16)
810-3063 MultiFlex 88AO 8 analog/digital
inputs, 8 relay
outputs, 4 analog
outputs. No battery.
Figure 1-3 - MultiFlex 1616 Combination Input/Output Board
810-3064 MultiFlex 88 8 analog/digital
There are several models of the MultiFlex board inputs, 8 relay
that combine the functionalities of input boards, outputs. No battery.
relay output boards, digital output boards, and 810-3065 MultiFlex 168AO 16 analog/digital
inputs, 8 relay
analog output boards. The MultiFlex outputs, 4 analog
combination input/output boards are designed to outputs. No battery.
be replacements for the 8IO Combination Input/ 810-3066 MultiFlex 168 16 analog/digital
Output Board, but the MultiFlex board provides inputs, 8 relay
outputs. No battery.
several new hardware options and software
810-3067 MultiFlex 168DO 16 analog/digital
features. inputs, 8 relay
outputs, and 4
The MultiFlex combination I/O boards consist pulse-width
of two circuit boards: a bottom layer with up to modulating digital
16 combination digital/analog inputs, and a output. No battery.
plug-in top layer which contains a combination 810-3073 MultiFlex 16 analog/digital
1616LAO inputs, 16
of relay outputs, digital outputs, and analog low-voltage
outputs. (24VAC rated) relay
outputs, and 4 analog
All boards feature both +5VDC and +12VDC outputs. No battery.
output voltage points for use in powering 810-3077 MultiFlex 16 analog/digital
transducers or other input devices that require 1616LDO inputs, 16
power. low-voltage
(24VAC rated) relay
On the RS485 Network, the MultiFlex outputs, and 4
combination input/output boards present pulse-width
modulating digital
themselves to the Einstein or REFLECS site outputs. No battery.
controller as 16AI Analog Input Boards, 8RO 810-3072 MultiFlex 1616L 16 analog/digital
Relay Output Boards, 8DO Digital Output inputs, 16
low-voltage
Boards, and/or 4AO Analog Output Boards,
(24VAC rated) relay
depending on what type of inputs or outputs are outputs. No battery.
equipped. Dip switches are used to assign
Table 1-2 - MultiFlex Combination Input/Output Board Models
network ID numbers to each board type.
Other Boards in the MultiFlex Family Overview of the MultiFlex Product Line • 3
The MultiFlex CUB has its own installation and
operation manual, P/N 026-1705.
1.3.4. The MultiFlex PAK
The PAK is a distributed pack (rack) controller
that controls compressors and condenser fans.
The PAK can control up to 8 compressor groups
containing up to 16 compressors. The
compressor control strategy is either Fixed Steps
with up to 20 fixed combinations of compressor
groups, or an alternate Cyclic strategy that
distributes compressor activations, with setpoint/
deadband using ON and OFF delays.
The PAK can also control up to 4 condenser fan
groups containing up to 8 total condenser fans.
The PAK condenser control strategy is
sequential TD control with setpoint/deadband
using ON and OFF delays.
The MultiFlex PAK has its own installation and
operation manual, P/N 026-1712.
2.3.1. Choosing Transformer Sizes Table 2-2 gives the VA ratings of the MultiFlex
board products. Refer to your site controller’s
In most site installations, a single transformer manual for VA ratings of the other I/O boards
will power multiple devices. Choose a that may be powered by one of these
transformer with a VA rating large enough to transformers.
power all devices that will be attached to it.
24 VAC
NO POWER LED
Old Style
MultiFlex Board
(Top Left Corner)
Figure 2-6 - Wiring Non-Center Tapped MultiFlex Boards to Do not connect the center tap of the transformer
Transformers With a Center Tap to the 0V terminal.
In addition, the MultiFlex combination boards Rule 2: Do not power an old-style MultiFlex
can be powered by one of the 50VA or 75VA non-center-tapped board with a transformer
non-center-tapped transformers listed in Table 2- that is also powering a center-tapped device.
1 on page 6. Figure 2-7 shows how to wire the
transformers to the MultiFlex boards.
TERMINATION
3.1. Wire Types
Emerson specs Belden #8641 shielded twisted
Figure 3-1 - I/O Network Configurations
pair cables for use as I/O network wiring (or
Belden #82641 and Belden #88641 for plenum 3.2.1. Maximum # of Boards on a
installations). Daisy Chain
If the recommended cable is not available in To determine how many MultiFlex controllers
your area, be sure the wiring meets or exceeds may be daisy-chained together, look for a plus
the following specs: sign "+" at the end of the model type on the
board’s plastic insulating cover.
Shielded? Yes
Conductor Type Twisted Pair
Gauge 18 - 24 AWG
Capacitance between 31 pF/ft or less
signal wires
Capacitance between 59 pF/ft or less
signal and shield
Nominal Impedance 12050
Table 3-1 - RS485 I/O Network Wiring Specifications
3.2. Network Configuration The "+", which appears on all MultiFlex boards
(Daisy Chains) manufactured after May 2004, means the board
is equipped with a low-power network
The RS485 Input/Output (I/O) network is wired transmitter. Up to 256 of these boards may be
in a daisy-chain configuration. In a daisy chain, connected to a single controller. If the board has
boards are wired together in series with no no "+" beside the model type, the maximum
branches or "star configurations," and the number that can be connected to an E2 is 32.
network is terminated at either end of the
If you have a mixture of plus and non-plus
daisy-chain.
boards, multiply the number of non-plus boards
by 8, and add that to the number of plus boards.
This will result in the maximum number of
boards you can interconnect.
Both the MultiFlex16 and the previous- Table 3-2 shows all of the combination
generation 16AI are recognized as “16AIs” by MultiFlex I/O boards and the board numbers
the site controller, and therefore each one of both they represent.
types of boards should have a unique board
number. MultiFlex Model 16AI 8RO 4AO 8DO
Type
The network ID on the MultiFlex 16 is set using 88 and 168 1 1
the first five dip switches on dip switch bank S3. 88AO and 168AO 1 1 1
Refer to Figure 3-3 for dip switch setting 168DO 1 1 1
instructions. 1616L 1 2
1616LAO 1 2 1
1616LDO 1 2 1
Table 3-2 - Model Types and Board Address Requirements
ON
ON
ON
ON
1
2
3
3
4
4
5
5
6
6
7
7
8
16AI: POSITION 1-5 NETWORK ADDRESS (1-16) boards, these boards must be configured as two
8RO boards with consecutive numbers.
POSITION 6-7 BAUD RATE (9600 or 19200)
BAUD RATE
ADDRESS 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON
1 2
BOARD 9
3 4 5 6 7 8
ON
1
BOARD 10
2 3 4 5 6 7 8
ON
1 2
BOARD 11
3 4 5 6 7 8
ON
1
BOARD 12
2 3 4 5 6 7 8
ON
1
BOARD 25
2 3 4 5 6 7 8
ON
1
BOARD 26
2 3 4 5 6 7 8
ON
1
BOARD 27
2 3 4 5 6 7 8
ON
1
BOARD 28
2 3 4 5 6 7 8
TERMINATION JUMPERS
ON
ON
ON
ON
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
S4 S3 S2 S1
Loss of
Fail-safe Light Light Loss of
Communi
Switch is ON is OFF Power
cation
Loss of
Fail-safe Light Light Loss of
Communi
Switch is ON is OFF Power
cation
4.2.2. Relay Output Ratings and Fuse Each relay is fused with a 2A fast-blow 5mm x
Protection 20mm fuse, Bussman GMA-2 or equivalent.
Each relay output on the MultiFlex Combination
I/O boards is rated for up to 240 VAC with a
maximum current of 2 amps.
DIGITAL
firmware; see Section 6.1.9., Analog Fail-
Safes). All that is required to connect a device to
an analog point is to connect the “+” terminal to
the positive wire on the device and the “-”
terminal to the negative (or ground) wire of the
device.
HAND
HELD
TERMINAL
JACK
MultiFlex I/O Board Hand-Held Terminal Screens The MultiFlex Hand-Held Terminal Interface • 21
Shortcut Keys (F1 and F2) use the number keys to enter a value, or if the
At any time, you may press the F1 key on the field requires a selection from a list of options,
Hand-Held Terminal to return to the opening use the “point key” (.) and the “dash key” (-) to
screen, or F2 to move to the Input/Output Select cycle through the options. To record your
menu. change, simply press the UP ARROW or
Configuration Mode DOWN ARROW key to move the cursor to
On any menu or configuration screen, to make a another field.
selection or enter a value you must press the To exit Configuration Mode, use the UP
RIGHT ARROW key to begin Configuration ARROW or DOWN ARROW keys to move the
Mode. cursor off the screen. When it is no longer
In Configuration Mode, you will see a cursor visible, you are no longer in Configuration Mode
shaped like an arrow pointing right. Use the UP and may navigate normally.
ARROW and DOWN ARROW keys to move
the cursor to the field you want to change. Then,
F1 F2
INPUT/
OPENING BOARD OUTPUT
SETTINGS
SCREEN ADDRESS SELECT
MENU
1 2 3 3
INPUT RELAY ANALOG DIGITAL
STATUS/ STATUS/ STATUS STATUS
CONFIG OVRD 1-4 MENU MENU
1 2 1 2 3
1 2 3
SELECT RELAY ANALOG DIGITAL
STATUS STATUS ANALOG - PERIOD CONFIG
ENG. STATUS/ STATUS/OVR STATUS -
(VOLTS) (ENG. UNITS) FAIL-SAFES (SECONDS) FAIL %
UNITS OVRD 5-8 (VOLTS) PWM %
ONLY AVAILABLE
ON BOARDS WITH ONLY AVAILABLE ONLY AVAILABLE
RELAY OUTPUTS ON BOARDS WITH ON BOARDS WITH
OTHER SCREENS (4 INPUTS per SCREEN) (168, 168AO, ANALOG OUTPUTS DIGITAL OUTPUTS
88, 88AO, (168AO, 88AO) (168DO)
168DO)
READ-ONLY SCREENS
= (NO EDITABLE FIELDS)
Figure 6-2 - MultiFlex I/O Board Hand-Held Terminal Interface Navigation Map
MultiFlex I/O Board Hand-Held Terminal Screens The MultiFlex Hand-Held Terminal Interface • 23
6.1.6. Input Screens 6.1.6.3. Status-Eng Units
I01: 74.500 DF
6.1.6.1. Input Status/Config Menu I02: 111.200 PSI
SELECT: 1 I03: 75.200 DF
1= STATUS-VOLTS I04: 65.04 RH
2= STATUS-ENG UN
3= INPUT CONFIG The Status-Eng Units screen shows the same
information as the Status-Volts screen, except it
The Input Status/Config Menu offers three
displays it in the engineering units designated
choices:
for that input (see Section 6.1.6.4. for more on
1. STATUS-VOLTS - Selecting this option will how to set the engineering units). The
show the status of all the inputs in volts. engineering unit chosen for the input is
2. STATUS-ENG UN - Selecting this option displayed in the right-hand column.
will show the status of all the inputs in
engineering units. Engineering units must be The Hand-Held Terminal shows four inputs at a
specified for each input using the Input time. To view more inputs, press the DOWN
Config screens (option 3), or else the board
assumes the input is a temperature sensor and
ARROW key to scroll down.
will display the input value in degrees 6.1.6.4. Input Config
Fahrenheit.
I01: TEMP-DF
3. INPUT CONFIG - Selecting this option will I02: 500 LB-PSI
allow you to specify the engineering units for I03: TEMP-DF
each sensor connected to an input. Doing this
will allow you to see the sensor value in terms
I04: HUMIDITY-RH
of its intended engineering units.
The Input Config screen is where you specify
6.1.6.2. Status-Volts the type of sensor that is attached to each input
I01: 5.000 V and the engineering unit with you wish to
I02: 5.000 V display the input values in the Hand-Held
I03: 5.000 V Terminal.
I04: 5.000 V
Setting the engineering units using these screens
The Status-Volts screen shows the current input will only affect how their values are displayed in
voltage of all inputs on the MultiFlex board. the STATUS-ENG UNITS screen (Section
Units with no inputs attached to them (and with 6.1.6.3.). Currently, neither Einstein nor
their input dip switches set to the UP position) REFLECS is capable of reading the MultiFlex’s
will read 5 volts. engineering units settings, so the sensor type and
The Hand-Held Terminal shows four inputs at a engineering units will still have to be specified
time. To view more inputs, press the DOWN in the controller in order for the inputs to be read
ARROW key to scroll down. correctly.
Fields I01 through I16 correspond to points 1
through 16 on the MultiFlex board. To change
the engineering unit for an input, press the
RIGHT ARROW key to enter Configuration
Mode, and press DOWN ARROW until the
cursor points to the field you wish to change.
MultiFlex I/O Board Hand-Held Terminal Screens The MultiFlex Hand-Held Terminal Interface • 25
To begin an override, press the RIGHT ARROW Overriding an Analog Output
key to enter Configuration Mode, and use the
DOWN ARROW key to move the cursor to the WARNING! Point overrides performed by HHT are
not visible to or recognized by the MultiFlex’s parent
output you wish to override. controller. In some cases, this may cause unnecessary
R01: OFF OVRON proof failure alarms and other erroneous conditions. If
R02: OFF a site controller is available, it is recommended all
R03: ON overrides be performed from the site controller instead
R04: OFF of the HHT.
Press the DASH key to choose an override You may temporarily override any analog output
command. “OVR ON” will override the output to any voltage between 0 and 10 volts using the
ON, and “OVR OFF” will override the output Hand-Held Terminal interface.
OFF. To begin the override, press the DOWN
ARROW key. To begin an override, press the RIGHT ARROW
key to enter Configuration Mode, and use the
Cancelling an Override DOWN ARROW key to move the cursor to the
To cancel an override, move the cursor to the output you wish to override.
field that says OVR ON or OVR OFF and press
A01:10.0 OVR5.5
the “CANCEL” button on the Hand-Held A02:10.0
Terminal. A03:10.0
You may also cancel all active overrides in the A04:10.0
MultiFlex board by unplugging the Hand-Held Use the number keys to enter the voltage value
Terminal. This will reset all relay output and you wish to override the output to. The number
analog output overrides. you enter may have up to one decimal place.
If you need timed overrides or permanent When you have entered the override value, press
overrides that do not require the Hand-Held the DOWN ARROW key to begin the override.
Terminal to remain plugged in, you must
perform the override from the REFLECS or Cancelling an Override
Einstein front panel. To cancel an override, move the cursor to the
override value and press the “CANCEL” button
6.1.8. Analog Output Screens on the Hand-Held Terminal.
6.1.8.1. Analog Status/Override You may also cancel all active overrides in the
A01:10.0 MultiFlex board by unplugging the Hand-Held
A02:10.0 Terminal. This will reset all relay output and
A03:10.0 analog output overrides.
A04:10.0
If you need timed overrides or permanent
This screen shows the current voltage output of overrides that do not require the Hand-Held
each of the four analog outputs on the Terminal to remain plugged in, you must
MultiFlex board. The fields numbered A01 perform the override from the REFLECS or
through A04 correspond to analog points #1 Einstein front panel.
through #4 on the board.
To change the fail-safe value, press the RIGHT When pulsing during an override, the 168DO
ARROW key to enter Configuration Mode, and will use the pulse period at which the output was
press the DOWN ARROW key until the cursor pulsing before the override began. If the output
points to the value you wish to change. Using the was being controlled by an application in a
number keys, enter a percentage value from 0 to Emerson site controller, the period used will be
100. To save your fail-safe setting, press the the same period programmed in the controller.
DOWN ARROW key. Cancelling an Override
An override initiated from an HHT can be
6.1.10. Digital Status (PWM) cancelled from the same screen in which you
D01:100 % initiated the override (the Digital Status (PWM)
D02:100 %
screen). Move the cursor until the arrow points
D03:100 %
D04:100 % to the point with the override you wish to cancel,
and press the CANCEL button on the HHT
This screen shows the current pulse percentage
of each of the four digital outputs on the 168DO. 6.1.11. Digital Period Status
The percentage represents the total amount of D01: 10 Period
D02: 10 in
the pulse period the output is ON (+8VDC). D03: 10 Seconds
To view the pulse period, back out of this screen D04: 10
by pressing the UP ARROW key, and from the
The Digital Period Status screen shows the
Digital Outputs menu, select option 2
current period (in seconds) at which the four
(see Section ).
outputs on the 168DO are pulsing. This value is
read from the Emerson site controller that
commands the output and may not be changed
from the HHT.
MultiFlex I/O Board Hand-Held Terminal Screens The MultiFlex Hand-Held Terminal Interface • 27
6.1.12. Config Fail % Screen
D01: 100% Off
D02: 100% line
D03: 100% (Fail)
D04: 100% PCT
This screen sets the default percentage at which
the digital outputs on the 168DO will pulse if
communication is lost with the site controller.
When the board recognizes it is off-line, it will
immediately switch to its fail-safe percentage,
and will remain at this rate until the board
returns to on-line status. The 168DO will use the
same pulse period it used before the board went
off-line.
If a digital output is not being commanded by
any applications in the site controller, it will
pulse at the value programmed in its Config
Fail % field regardless of whether or not the
board is on-line or off-line.
MultiFlex I/O Board Hand-Held Terminal Screens Wiring Connection to Site Supervisor • 29
8 Relay Output Test In Relay Output Test Mode, fail-safe dip
switches 1-8 (located on the output board layer
Mode of MultiFlex I/O boards, and next to switch bank
S1 on the 8ROSMT) can be used to change the
Newly released versions of the MultiFlex I/O state of the relays.
board family and the 8ROSMT have a new A fail-safe switch in the ON position will cause
feature that allows relays to be manually the corresponding relay to be energized (i.e.,
energized and de-energized without use of an OPEN on the N.C. terminals, and CLOSED on
override from a Hand-Held Terminal when the the N.O. terminals). A fail-safe switch in the
board is offline. When a MultiFlex is in Relay OFF position will cause the relay to be
Output Test Mode, the output fail-safe dip de-energized (i.e., CLOSED on the N.C.
switches may be used to cycle the states of the terminals and OPEN on the N.O. terminals).
relay outputs. The feature is designed to help
manufacturers of panels test output wiring The LED that shows the output state will also be
quickly and easily without need for a site ON when the switch is ON and OFF when the
controller or HHT. switch is OFF.
Relay Output Test Mode is available in the To exit Relay Output Test Mode, set the address
following product versions: switches S3 and S4 to any position other than
“all OFF.” The fail-safe switches will Board
Type Version resume normal operation.
MultiFlex I/O Board Hand-Held Terminal Screens Relay Output Test Mode • 31
For Technical Support call 770-425-2724 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such
products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product
remains solely with the purchaser and end-user.
026-1704 Emerson is a trademark of Emerson Electric Co. ©2019 Emerson Retail Solutions, Inc. All rights reserved.