MTTR

COMPONENTE
Falla/Año) (hr)
System grid 0.643 1.32
Disconnectors 220 kV 0.0061 50.1
Transmission Lines
220 kV 0.0075 8
23 kV 0.0075 8
Cable
23 kV 0.00336 16
4.16 kV 0.00617 20.4
Switchgear Bus
220 kV 0.00063 20.6
23 kV 0.00063 20.6
4.16 kV 0.00063 20.6
400 V 0.00034 41.5
Circuit Breakers
220 kV 0.0036 62.4
23 kV 0.0036 62.4
4.16 kV 0.0036 62.4
400 V 0.0027 47.2
Relé de Protección 0.0002 5
Transformers Liquid filled
75 MVA (220/23 kV) 0.013 367
15 MVA (23/4.16 kV) 0.013 367
7.5 MVA (23/4.16 kV) 0.013 367
2.5 MVA (4.16/0.4 kV) 0.0030 382
Ducto de barra 0.000125 12.9
Motor
MV 0.0404 71.4
LV 0.0109 50.2
Carga
MV 0.0404 71.4
LV 0.0109 50.2
VDF 1.254 5

Tomado del Standard IEEE 493-1997 “Recommended Practice for the Design of Reliable Industrial
and Commercial Power Systems. Gold Book “.