You are on page 1of 23

=~~=

(Reaffirmed 1984)
ANSIIIEEE 8td 06-1977
(Revision or IEEE 66-1968)
(Reaffirmed 1982)

• IEEE Guide for Insulation


Maintenance of Large
Alternating-Current Rotating
Machinery (1 0 000 kVA and
Larger)
.' < ' ~ .' ~ ...

"" - Circuits and Devices

• Energy and Power


Sponsored by the
Rotating Machinery Committee of the
IEEE Power Engineering Society

•• Published by the Institute of ElectriCIIland Electronics Engineers, Inc., 345 East 47th Street, New York, NY IDOll USA.

March 15, 1977 SH06478


• ANSI/IEEE Std 56-1977
(Revision of IEEE Std 56-1958)
(IEEE Reaffirmed 1982)
(ANSI Reaffirmed 1984)

An American National Standard


IEEE Guide for Insulation Maintenance of
Large Alternating-Current Rotating Machinery
(10000 kVA and Larger)

• Sponsor
Rotating Machinery Committee of the
IEEE Power Engineering Society

Approved June 3, 1976


Reaffirmed March 11, 1982
IEEE Standards Board

Approved November 2R, 1977


Reaffirmed January 27, 1984
American National Standards Institute

© Copyright 1977 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA
No part t!(lhi.<; publlnlf;fm waylw r(7)roduced in anyjorm,
in (HI e/.t'Clnm;l' rl'trim)(li sysumr. or Qlhenl'ise,
without Jwior Il'ri.tlrn perm,issi(m oj the publisher.
When the IEEE Standards Board approved this standard on June 3, 1976, it had the following •
membership:

William R. Kruesi, Chairman Irvin N. Howell, Jr., Vice Chairman


Ivan G. Easton, Secretary , \

William E. Andrus Irving Kolodny William J. Neiswender


Jean Jacques Archambault Benjamin J. Leon Gustave Shapiro
Dale R. Cochran Anthony C. Lordi Ralph M. Showers
Warren H. Cook John P. Markey Robert A. Soderman
Louis Costrell Thomas J. Martin Leonard W. Thomas, Sr.
Jay Forster Donald T. Michael Charles L. Wagner
Joseph L. Koepfinger Voss A. Moore William T. Wintringhamt
William S. Morgan

tDeceased


-I
Foreword
ie IThis foreword is not a part of IEEE Std 56-1977, IEEE Guide for Insulation Maintenance of Large Alternating-Current Ro-
tating Machinery (10 000 kVA and Larger).1

The present revision was prepared by a Working Group of the Insulation Subcommittee of the
IEEE Rotating Machinery Committee. Working Group personnel were:
R. F. Sharrow, Chairman

J.M. Brown N. V. Gjaja


A. W. W. Cameron R.J. Hillen
E. B. Curdts W.J. Sheets

A. W. Zwiener

The original document was prepared by a similar working group whose personnel were:
G. L. Moses, Chairman
P. L. Alger W. T. Gordon E. H. Povey
J.S. Askey G. L. Hill C.L. Sidway
L. J. Beberich W. R. Hough J. B. Swering
O. D. Butler J. W. Jones H. R. Tomlinson
E. B. Curdts M.S. Kerwen E.H. Tovee

• J. F. Dexter
P.A. Emmons
J. L. Kuehlthau
H. C. Marcraft
A. L. Van Emden
R. W. Wieseman


An American National Standard

• IEEE Guide for Insulation Maintenance of


Large Alternating-Current Rotating Machinery
(10 000 kVA and Larger)

1. Purpose The extent to which a maintenance pro-


gram is pursued will depend largely on the op-
The purpose of this guide is to present infor- erator's own experience and philosophy, but
mation necessary to permit an effective eval- should also take into account the importance
uation of the insulation systems of large alter- of service reliability of the equipment. Where
nating-current rotating electrical machines. high service reliability is required, a regular
Such an evaluation can serve $S a guide to the maintenance program involving periodic dis-
degree of maintenance or replacement which assembly and knowledgeable visual exam-
might be deemed necessary, and also offer ination of the equipment, together with the
some indication of the future service re- application of electrical tests of proven signifi-
liability of the equipment under consid- cance, is strongly recommended.
eration. It should be recognized that some over-
potential tests may be damaging to insulation
in marginal condition. Where there is un-
2. Scope certainty, consultation with the manu-
facturer is recommended. This is implicit in
This guide is intended to apply in general to setting up any maintenance testing program.
large alternating-current rotating electrical
machines rated at 10000 kVA or more, and
operating at voltages of 6000 V and above.
4. Service Conditions
Reducing Insulation Life
3. Significance of Maintenance
As has been stated, electrical machines and
Rotating electrical machines are complex their insulation systems are subjected to me-
structures which are subjected to mechanical, chanical, electrical, and thermal stresses
electrical, and thermal stresses of varying which give rise to many deteriorating influ-
magnitude. Of the various components, the ences, the most significant of which are the
insulation systems are the most susceptible to following.
aging or damage due to these stresses. The ser-
4.1 Thermal Aging. Gradual aging caused by
vice life of an electrical machine will, there-
temperatures due to normal operating loads.
fore, largely depend on the serviceability of
the insulation systems. 4.2 Overtemperature. Unusually high tem-
Where reliability is of concern, adequate in- perature from causes such as overload, high
spection and testing programs are advocated ambient temperature" restricted ventilation,
to assure that the equipment is maintained in and loss of cooling liquid.
satisfactory condition to minimize the possi-
4.3 OvervoItage. Unusually high voltage such
bility of in -service failure.
as from switching or ligh,tning surges.
The experience and data obtained from
regular maintenance inspection and testing 4.4 Contamination. This deteriorates elec-
programs can, in addition to providing an trical insulation by actually conducting cur-
evaluation of the present condition of the rent over insulated surfaces, or by attacking
equipment, give some indication of long-term the material reducing its electrical insulating
trends and probable need for future repair or quality or its physical strength, or by thermal-
replacement. ly insulating the material forcing it to operate

7
IEEE
Std 06-1977 IEEE GUIDE FOn INSULATION MAINTENANCE OF

at higher than normal temperatures. Included


here are:
Wetness or extreme humidity
Oil or grease
Conducting dusts and particles
Nonconducting dusts and particles
5.1.4 Core Assembly. The principal insula-
tioncbmponents in this assembly are the in-
sulation between laminations in the core and
insulation on through bolts (when used).
5.1.5 Other Parts. Insulation is sometimes
used on bearings and other mechanical parts

Chemicals of ind ustry such as hydrogen seals, oil seals, and piping.
Temperature sensors may be applied, and
4.5 Physical Damage. This contributes to these usually incorporate insulation. Refer to
electrical insulation failure by opening leak- the manufacturer's instruction book.
age paths through the insulation. Included
here are: 5.2 Stator-Winding Insulation
Physical shock 5.2.1 Strand Insulation. The individual
Vibration strands of stator-coil conductors are usually
Overspeed insulated with organic films, fibers bonded
Unusual electromagnetic forces with resins, or mica in various forms bonded
Erosion by foreign matter with resins. Fibers may be such materials as
Damage by foreign objects paper, cotton, asbestos, glass, polyester, or
Thermal cycling . combinations thereof.
5.2.2 Turn Insulation (Conductor). In a coil
4.6 Partial Discharge (Corona) Effects. Par- with more than one turn, groups of strands
tial discharges which may occur at higher op- forming a single-turn (conductor) may be held
erating voltages may be accompanied by sev- together and insulated. Individual strand in-
eral undesirable effects such as chemical ac- sulation, as described in Section 5.2.1, may
tion, heating, and ionic bombardment. also serve as turn insulation.
5.2.3 Ground Insulation. Ground insula-
tion is generally defined as that insulation in-
tended to insulate the current-carrying com-
5. Insulation Systems in ponents (such as the coils, the collector rings,
General Use and connections thereto) from one another
and from the noncurrent-carrying com-
5.1 Insulated Parts. Insulation is present in ponents which are usually considered to be
various machine components, but the com- grounded (such as the core iron, the shaft, and
.plexity of the structure is such that only a gen- other structural members).
eral description can be given here. However, Ground insulation takes on many different
detailed information on the structure of insu- forms depending on the type of machine and
lation systems and modes of insulation failure the manufacturer's practices. I

are important to evaluation. Ground insulation is generally a dry-type,


5.1.1 Stator Winding. The stator winding multilayered system comprising various insu-
with its associated leads is the main curren t- lating materials bonded and filled. Mica or
carrying winding of the machine. The coils of micaceous products are generally preferred in
the stator winding have strands and ground high voltage machines for at least a part of the
insulation and may have turn insulation. ground-insulation system.
Wedges, blocks, and other insulated me- 5.2.4 Insulation Grading System. The sur-
chanical supports are a part of the stator face of slot portions of stator coils, including
winding assembly. several inches of the coil beyond the core,
5.1.2 Rotor Winding. The rotors of ac ma- is normally semiconducting. The semi-
chines are either salient pole or cylindrical conducting characteristic is accomplished by
type. In all cases, they have turn and ground the application of conducting varnish or by
insulation, insulated mechanical supports, the use of semiconducting tapes.
and lead insulation and may have collector 5.2.5 Support Insulation. Supports may be
rings with insulation. nonmetallic or metallic in design. Non-
5.1.3 Brush Rigging. Machines with collec- metallic supports are made of insulating ma-
tor rings will have insulated brush rigging. terial such as wood, molded parts, or com-

8
mgE
LAHC:E AL'J'EHNATINUClIIOWNT IH)TATIN<l MACIIINEHY St.d f)fi-I !I77

• pressed laminates of cotton, asbestos, glass, or


synthetic fibers. Where necessary, metallic
supports are insulated.

5.3 Rotor Winding Insulation


5.3.1 Turn Insulation (Conductor). Turn
encapFmlated in insulating mnterinlA. Insu-
lated leads complete the connections from the
elements to a terminal board.

6. Visual-Inspection Methods
insulation on wire-wound coils usually in-
corporates a thin insulating layer on the To achieve maximum benefit from a visual-
strand itself; for example, various materials inspection program, it should be directed ini-
such as asbestos, cotton, fiberglass, papers, tilJIly to those areas which have been shown
micas, and synthetic materials. by previous experience to be most prone to the
Turn insulation on strap-wound coils of forms of damage or degradation caused by the
both salient-pole and cylindrical-type rotors influences listed in Section 4 of this guide.
usually incorporates various forms of tape or The most significant items to which in-
. strip material with resin bonding, spection should be directed are the f~llowing
5.3.2 Ground Insulation. Various types of sections.
ground insulation are used on the rotating
field coils of synchronous machines (salient 6.1 Stator Windings
pole or cylindrical type) and on the wound ro- 6.1.1 Inspect for deterioration or degrada-
tor induction machines. A variety of organic tion of insulation resulting from thermal ag-
and inorganic materials are used. ing due to cumulative time-temperature ef-
5.3.3 Collector Insulation. The insulation fects. Coils may reveal general puffiness,
used on collector rings and leads must be ad- swelling into ventilation ducts, or a lack of
equate both for support and creepage to the firmness of the insulation, suggesting a loss of
grounded shaft. The insulation usually con- bond with consequent separation of the insu-


sists of laminated fibers or mica suitably lation layers from one another or from the
bonded or impregnated . winding conductors or turns.
6.1.2 Inspect for girth cracking or tape sep-
5.4 Brush-Rigging Insulation. The insulatd aration of the ground wall. This is most likely
components on brush rigging are generally to occur on machines having one-turn stator
molded compounds, laminates, or tubes made coils greater than about 3 m in length and
from paper, cotton, glass, or synthetic fibers having asphaltic-type bonds. Particular at-
suitably bonded and impregnated. tention should be paid to the areas immedi-
ately adjacent to the ends of the slots. Where
5.5 Core and Frame-Assembly Insulation considerable insulation cracking is observed,
5.5.1 Stator-Core Interlaminar Insulation. it is recommended that the wedges at the ends
Stator cores are built up from thin steellami- of the slots be removed, if possible, for in-
nations insulated from one another to reduce spection, as dangerous cracks may also have
core losses. A variety of thin insulating films occurred just within the slots.
are used, such as varnish, water-glass, chem- 6.1.3 Inspect for contamination of coil and
ical deposits, or chemical treatments. connection surfaces by substances which ad-
5.5.2 Core-Tightening Through-Bolt Insu- versely affect insulation surface electric
lation. The core-tightening through bolts are strength, the most common being carbon dust,
insulated from ground throughout their oil, or moisture contamination.
length with insulating materials suitably 6.1.4 Inspect for abrasion or contami-
bonded. Bolt-end hardware, such as nuts and nation of coil and connection surfaces from
washers, must also be insulated from ground. other sources, such as chemicals, abrasive,
Key bars or bolts, used at the outer diameter or conducting substances. Such effects are ag-
of the core for tightening, usually require no gravated in the case of machines used in ad-
insulation. verse-atmospheric industrial applications,
such as chemical plants, rubber mills, and pa-
5.6 Stator-Winding, Embedded, Temperature- per manufacturing facilities.
Detector Insulation. Stator-winding, em- 6.1.5 Inspect for cracking or abrasion of in-
bedded, temperature-detector elements are sulation res~lting from prolonged or abnormal

9
If~EE
Stcl rl£)· 1!)77 lI~r~E {jtJJDE FOR INSUI.ATION MAINTENANCE OF

mechanical stresses. In stator windings, 100Re-


ness of the hracing structure is a certain guide
to such phenomena and can itself cause fur-
ther mechanical damage if allowed to go un-
corrected.
6.1.6 Inspect for eroding effects of foreign
bility of oamnging turn or ground in~m)at,ion
and breaking Of loosening of connections be-
tween coils.
6.2.3 "In cylindrical rotors, inspect for evi-
dence of heating or current between retaining
rings, wedges, and the. rotor body. Heating

substanceR embedded or lodged against coil in- may be caused by high circulating currents
sulation surfaces. Particularly damaging are due to generator motoring, phase-current im-
magnetic pieces (even snlall particles) which balance, or sustained single-phase faults.
vibrate under the influence of the mRgnetic If evidence of overh~ating or hurning is dis-
field in the machine. covered, ultrasonic or other nondestructive
6.1.7 Inspect for insulation deterioration tests should be made to determine whether
due to partial discharges (corona) in the body thermal cracks (which might propagate into
of the machine or end windings in the higher catastrophic failures) are present. Hardness
voltage ratings. These are evidenced by tight- tests are often desirable to detect possible
ly adhering deposits of white, gray, red, changes in metal characteristics or properties
brown, or black color. These deposits are par- after exposure to excessive temperatures.
ticularly noticeable in areas where the insula- The rotor body should be checked for loose
tion is subject to high electrical stresses.Expe- or cracked slot wedges and loose balance
rience is required to distingu'ish these effects weights.
from powdering which can occur as a result of The condition and tightness of end-winding
relative vibratory movement between hard blocking, signs of deterioration, or movement
surfaces as can be caused by loose end-wind- of the retaining ring insulating liner due to
ing supports. the above effects, and any other looseness
should be noted. Powdered insulation in air

.'
6.1.8 Inspect for loose slot wedges or slot
fillers, which, if allowed to go uncorrected, ducts may be evidence of coil movement. Red
may themselves cause mechanical damage or oxide at metallic joints is evidence of move-
reduce the effective,ness of stator coil retention ment of metal parts.
against normal operating or fault-condition Inspect to determine that insulation migra-
forces. tion has not closed off cooling passages.
6.1.9 Inspect for looseness in the paralIel- To investigate extraordinary conditions ex-
ring or phase-connection supporting struc- posed by inspection or operation, removal of
ture. Slight looseness of some elements could, retaining rings may he required.
if allowed to go uncorrected, lead to more The tightness of field-lead connections and
serious problems due to progressive wear. condition of collector and collector-lead insu-
6.1.10 Inspect bushings for leaks or cracks .. lation should be noted.
These and other terminal components should
be clean to avoid extraneous leakage paths 6.3 Brush Rigging. Insulation supporting the
which might affect overpotential tests, espe- brush rigging should be inspected for evidence
cially dc, which may be performed. of carbonized leakage paths or contamination
which may lead to flashover.
6.2 Rotor Windings. In addition to insulation
degradation from causes similar to those listed
in Section 6.1, close attention should be paid 6.4 Core Assembly. In the core assembly, the
to the following in rotor windings. following items are considered to be the most
6.2.1 Inspect for distortion of coils and coil- significant.
to-coil connections due to the effects of abnor- 6.4.1 Stator-Core Laminations. Inspect for
mal mechanical, electrical, or thermal forces. failure of interlaminar insulation. This fail'-
Such distortion might cause failure of insula- ure first appears as localized darkening of the
tion between turns or to ground. insulation, paint, and varnish in an area of
6.2.2 In salient-pole rotors, inspect' for the stator bore and can lead to complete ma-
shrinkage or looseness of field coil washers. chine failure.
This permits coil movement during periods of Interlaminar insulation failure usually re-
acceleration and deceleration with the proba- sults from mechanical damage, such as from

10
IEEI·;
LAH(m AL'I'I·:HNNI'INO·CUHHENT HOTATINO MAClIlNgHY SId G(j·l!l77

• abuse during assembly and disassembly or


from foreign objects in the air gap or from
electrical arcs during a winding failure.
Whenever severallnminations have become
short circuited, excessive local heating might
arise, resulting in enlargement of the faulted
jng-insulation failure. Refer to IEEE Std 115-
1965, Test Procedure for SynchronouH Ma-
chines, for electrical test procedure.

area. 7. Cleaning
Where such damage is widespread and con-
cern might be felt regarding the adequacy of 7.1 General. Care and good judgment must be
subsequent repairs, a loop (or ring) test is rec- used in any program for cleaning of electrical
ommended. This test is detailed in Section machinery and windings. Excessive cleaning
8.1.10. and unwise use of solvents can do more dam-
Inspect for looseness of core laminations. age than good, and result in expensive re-
Loose core laminations at the air-gap side of winding or repairs.
the core (teeth), especially at core ends, will The need for cleaning may be indicated
vibrate, abrade interlamination insulation from:
(and ground insulation), short circuit lamina- (1) Previous history of machine
tions, and cause heating. Also, vibrating lami- (2) Equipment application
nations may fatigue, crack, break off, and con- (3) Visual inspection
taminate the machine with iron particles. .( 4) Low insulation resistance
Iron oxide powder deposits are an indication (5) Overheating
of loose core iron or loose wedges. Once the need for cleaning is established,
6.4.2 Ventilation Ducts. Inspect for loose or the cleaning method can be tailored to the
broken ventilation duct separators (or fin- type of contamination and the severity of the
gers). Th~se can cause core looseness. Also, contamination buildup.
these can break off, resulting in mechanical After cleaning (and drying if necessary) the
damage to the coil insulation and the inter- insulation surface condition should be che,ek-
laminar insulation. ed for surface cracks, porosity, or the effects of
harsh cleaning methods. The desired surface
6.4.3 End Fingers. Inspect for overheating
insulating finish should be reestablished by
of the end fingers, which is evidenced by dis- the application of suitable varnishes, paints,
coloration of the paint or components in the
or resins. Depending on accessibility or size,
areas affected. Abnormal overheating can
surface treatments may be applied by dipping,
lead to thermal degradation of the insulation
spraying, flooding, or brushing.
between laminations with consequent short
circuiting of laminations, overheating, and 7.2 Cleaning Techniques. The method of
damage to the adjacent coil insulation. cleaning can be adapted to the type of con-
6.4.4 End Flux Shields. Inspect for over- tamination and the buildup of contaminants.
heating of the end flux shields (when present) The methods listed in the following section
which is evidenced by discoloration of the are in increasing order of severity and possible
paint or components in the areas affected. . damage to windings.
When these shields are insulated, abnormal 7.2.1 Vacuum Cleaning. Dry contaminants
heating can lead to thermal degradation of such as carbon dust, coal dust, and fly ash can
the insulation. be removed with a vacuum cleaner. Con-
6.4.5 Insulated Stator-Through-Bolts. taminants can be dislodged for vacuum pick-
When these are used, inspect the insulation up by:
components (washers, tubes, etc) at the ends (1) Rubbing with dry cloths
of the through-bolts for evidence of distress. (2) Brushing with a bristle brush
Verify that the nuts are tightened and locked. (3) Scraping with soft wood or fiber scrapers
6.4.6 Bearing, Hydrogen-Seal, and Other (Wire brushes or metal scrapers should not be
Insulation. Whenever bearings and other me- used because of possible damage to the insula-
chanical parts are disassembled, inspect their tion and the dangerous possibility of in-
insulation for signs of deterioration. Pitting in troducing magnetic or other metallic particles
the bearing material may be evidence of bear- into the winding or core assembly.)

11
mI4~14~
Std o(l·1!)77 IEEE GUIDE Fon INsULA-noN MAINTENANCI~ (>I<'

(4) Nozzle shapes should be varied as re- Where a stronger or faster-drying solvent is
quired to enable directing the vacuum clean-
ing into hidden, difficult to clenn arOllS.
7.2.2 Air-Lance Cleaning. After vacuum
cleaning, additional cleaning can be done em-
ploying shaped nozzles to direct high-velocity
~equired, a chlorinated safety solvent can be
uRcd on llRphnltic nndRYllthetic-f(~Hil1 tYJ)eR of
insulation. For recomrnendations on specific
solvents to be used with each given insulation
the manufacturer of the machine should be

clean dry air to dislodge trapped con- consulted. Here, again, solvent-dampened
taminants. It is recommended that air pres- cloths are often sufficient for wiping off con-
sure be limited to avoid damaging the insula- taminants. Refer to Section 7.2.3.3 for risk of
tion. damage.
7.2.3 Solvent Cleaning. Care must be ex- Mixtures of petroleum solvents and chlori- '
ercised in the choice and application of clean- nated solvents can be used with better clean-
ing solvents from the standpoint of worker ingcapability than the petroleum solvents,
safety, and risk of damage to the insulation. alone. Such mixtures must not be considered
The manufacturer should be consulted to se- nonflammable, even though in some propor-
lect a solvent and method of application tions they might be. Differences in evapora-
which is noninjurious to the winding. tion rates can chang~ characteristics of the
blend.
7.2.3.1 Person nel Safety. The persons Carbon-tetrachloride and benzene are high-
who will carry out the cleaning should be in- ly toxic solvents and Clre not to be used for
structed on the safe use of the solvents. cleaning. Gasoline, naphtha, and similar liq-
Among those instructions should be the fol- uids are not to be used for cleaning because of
lowing: fire and explosion hazards.
(1) Use personal protective equipment such 7.2.3.3 Risk of Damage. Liquid solvents
as respirators, goggles, and gloves. Avoid skin are effective in removing oily contaminants,
contact with solvents, particularly the chlori- but there are risks involved, particularly from
nated solvents. spray applications of solvents. The solvents
(2) Use small quantities of solvent at a time may carry contaminants into cracks, crevices,
to minimize exposure to vapors. or inaccessible areas and cause the insulation
(3) Determine that adequate ventilation ex- resistance to decrease to unsafe levels.
ists. Chlorinated solvents must not be used on
(4) Rotate cleaning personnel to minimize stainless steel components unless agreed upon
exposure. with the manufacturer because of the possi-
(5) Have fire extinguishers, for solvent fires, bility of stress corrosion caused by the chlo-
available to use. rides. Examples of stainless steel components
(6) Do not smoke around solvents. are: (1) nonmagnetic retaining rings and
(7) Use safety containers of the kind pre- wedges on turbine-generator rotors, and (2)
scribed by appropriate regulations. stator cooling oil or water systems on turbine-
(8) Make certain the machine is cleared generators. Chlorinated solvents must not be
electrically and the windings are grounded. used on aluminum or copper components be-
Ground spray equipment also, if used. cause of chloride attack.
(9) Keep ignition sources out of the cleaning Solvent cleaning of cylindrical rotors should
area. Such sources are sparks, flames, weld- be avoided. Cleaning of cylindrical rotors
ing, open lamp, heaters, and switches. should be limited to vacuuming, blowing with,
7.2.3.2 Types of Solvents. Petroleum sol- dry compressed air, wiping with dry or solvent.
vents of the safety type can be used for re- dampened cloth, or combinations of these
moving oily and greasy contaminants from as- three methods. The need for more extensive'
phaltic or synthetic-resin types of insulation. cleaning may involve retaining ring removal
These solvents should be used sparingly. to provide access to areas where contaminants
Quite often a lint-free cloth, dampened in sol- are trapped. Carbon brushes should not be al-
vent, is adequate for rubbing off the con- lowed to absorb solvents, particularly the
tamination. Saturation of asphaltic-type in- chlorinated types.
sulations should be avoided to prevent soft- Neither petroleum solvents nor chlorinated
ening of the insulating materials. solvents should be used on silicone insulated

12
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY Std 56-1977

windings because of the degrading effect on Silicone-insulated windings can be gener-


this type of insulation. ally cleaned using the water hose method with
a nonionic, nonsudsing detergent.
7.2.4 Abrasive Blasting. Another method
for removing contaminants utilizes an air
blast of ground corn cobs or ground nut shells. 8. Maintenance Tests
This method is often successful for removing
oily contaminants. The air-abrasive blast The tests listed below have been used gener-
must not be held too long on anyone area or ally either to establish the long-time trends in
the insulation will be damaged by abrasion. parts of the insulation structure, or to detect
Care must be exercised to avoid blowing the specific types of flaws which may develop in
abrasive material into inaccessible areas portions of the insulation.
where it cannot be completely removed and The common tests normally used for main-
may block ventilating passages or cause me- tenance evaluation are directed at deter-
chanical imbalance during operation. mining the condition of the ground insula-
7.2.5 Steam Cleaning. The steam-jenny tion. These are direct-current, insulation-re-
method of cleaning utilizes a high-velocity jet sistance tests, and overvoltage proof tests. It is
of steam and water containing a mild non- customary to make one or more of such tests
conductive detergent. The detergent spray is at each inspection.
followed by multiple steam and water sprays Other tests are sometimes employed to de-
without detergent to provide adequate rin- tect specific types of insulation deterioration.
sing. The machine must then be dried or Their use should be based on the need for the
baked to remove alf moisture from the wind- information they provide.
ings and to obtain an acceptable insulation re- With many maintenance tests, the trends
sistance value. If an overvoltage test is applied measured over a period of years are normally
after steam cleaning, there is a risk of insula-

'.
more important than absolute measured val-
tion failure if all moisture has not been re- ues determined at a specific inspection period.
moved or the insulation is defective. A sudden change in the values for a given ma-
Regardless of the procedure used for drying chine should be investigated andthe cause de-
insulation systems, initial dryout temper- termined. In windings, large insulation areas
atures should not exceed 75 to 85 C (reached
0

are involved, and discrete areas of weakness


at a maximum rate of 5° CIh). In exceptional mayor may not significantly affect the overall
cases, where insulation resistance does not re- measured values for the entire winding.
spond to this limit after 24 h, the maximum Inspections and tests of windings are usual-
temperature may be carefully increased to ly made at convenient intervals in the range of
100-105° C. At temperatures of 100 C or high-
0

1 to 5 years. Ordinarily, intervals of 2 to 3


er, the possibility of insulation rupture (as years (depending upon machine availability)
water changes to steam) should be a prime between times of inspection and test are con-
consideration in the time-temperature sched- sidered good practice.
ule selected. Ventilation is required to remove
the water vapor during the heating cycle. 8.1 Stator Winding
The steam cleaning method is effective on 8.1.1 Insulation Resistance. IEEE Std 43-
heavily contaminated windings and windings 1974, Recommended Practice Testing Insula-
subjected to flooding or salt contamination. tion Resistance of Rotating Machinery out- t

The steam cleaning method usually can be lines recommended practice for measuring in-
used on silicone-insulated windings. sulation resistance.
7.2.6 Cleaning By Water Immersion or Wa- 8.1.2 Dielectric A bsorption Test. IEEE Std
ter Hose. The machines involved in this guide 43-1974 and IEEE Std 95-1962, Recommend-
are generally too large for immersion, but ed Practice for Insulation Testing of Large

.•
heavily contaminated or flooded machines AC Rotating Machinery with High Direct
can be washed with a hose. Baking and drying Voltage, outline recommended practices for
precautions noted under steam cleaning obtaining dielectric absorption data.
:
would also apply for water immersion or water 8.1.3 Overvoltage Test. Overvoltage tests
hose cleaning. are used to obtain assurance concerning the

13
IEEE
Std 56-1977 IEEE GUIDE FOR INSULATION MAINTENANCE OF

minimum strength of the insulation. Such that a desired level of insulation strength is
tests are made on all or parts of the ground in- present. Test equipment, employed in the ap-
sulation. Many users of large rotating ma- plication of turn insulation tests, is usually of
chines apply overvoltage tests periodically, the type where a capacitor is alternately
generally at the beginning of the overhaul of charged and then discharged into the coil un-
related equipment. This allows for the de- der test (or into an inducing coil which has
tection and possible repair of insulation weak- been placed in the stator bore, over the coil
nesses during the scheduled outage. under test).
An overvoltage test should be applied to Since the insulation between turns of stator
each phase separately with the remaining coils varies greatly in types of insulating mate-
phases not under test being grounded. In this rials, types of construction, and spacing, test
way, the insulation between phases (or lines) values are usually determined after con-
is also tested. This is only practical, howev~r, sultation with the coil or machine manu-
where both ends of each phase are brought out facturer. Any test value selected to verify the
to separate terminals, as is usually the case in adequacy of interturn insulation should be
generators. Some motors may have three or based on the design, physical spacing and
four leads brought out which precludes test electrical strength of the insulating system.
between phases. Refer to IEEE Project 522, Guide for Testing
Overvoltage tests may be performed either Turn-to-Turn Insulation on Form Wound
with alternating or direct voltage. The level of Coils for Rotating Machines, for turn-to-turn
overvoltage which should be applied will de- testing (see Section 9).
pend to a large extent on the type and age of 8.1.5 Partial-Discharge Tests
the machine involved, the degree of exposure 8.1.5.1 Slot-Discharge Test. The slot dis-
to overvoltages, and the level of serviceability charge test is made for the single purpose of
required from the machine in question. It checking the adequacy of the electrical con-
should, however, be sufficiently searching to tact between conducting-coil surfaces and the
discern any weakness or incipient weakness in iron of stator slots. Loss of this electrical con-
the insulation structure which might lead to tact results in a relatively high energy dis-
service failure. It should be recognized that if charge between the conducting-coil surface
the windings are clean and dry, overvoltage and the core. The energy is that resulting
tests may not detect defects which are in the from a substantial portion of the coil-side ca-
end turns or in leads remote from the stator pacitance. Since greatly accelerated deteriora-
core. tion of the major ground insulation is pro-
The values of test voltages usually are duced by slot discharge, early detection and
selected in the range of 125 to 150% of the correction of this condition is important.
rated line-to-line voltage and are normally Slot-discharge analyzers utilize detection
held for 1 min: circuits resonant in the frequency range
(1) Refer to IEEE Std 4-1968, Techniques where energy from surface discharging is high
for Dielectric Tests (ANSI C68.1-1968), for (approximately 2500 Hz), while blocking 60
power frequency testing (see Section 9). Hz voltage by means of a high-pass filter.
(2) Refer to IEEE Std 433-1974, Recom- Tests are made with the winding energized
mended Practice for Insulation Testing of at approximately the operating stress to
Large AC Rotating Machinery with High ground. Detection is accomplished by con-
Voltage at Very Low Frequency, for 0.1 Hz necting the slot-discharge analyzer to the ma-
testing and recommended voltage level ratio chine terminals, one phase at a time. When a
(see Section 9). discharge exists, high-frequency reflections
(3) Refer to IEEE 95-1977 for direct voltage are readily observable on. a cathode-ray os-
testing and recommended voltage level ratio cilloscope connected to the slot-discharge an-
(see Section 9). alyzer output. Location of specific coils suffer-
ing slot discharge is accomplished by a probe
8.1.4 Turn-To-Turn Insulation Test. In test. The probe test utilizes the slot-discharge
cases where the integrity of the insulation be- analyzer in conjunction with a probe which
tween adjacent turns in a coil is subject of successively contacts the conducting surfaces
concern, tests should be made to establish of individual stator coils.

14
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY Std 56-1977

• If the rotor is removed to provide access to


the stator-bore surface, an alternate test may
be made to provide a partial check of the ad-
equacy of coil surface grounding in the slot
portion of the stator. With slot wedges re-
moved, contact-resistance measurements be-
(1) Equipment capable of energizing the
stator winding at its normal operating line-to-
neutral voltage at rated frequency.
(2) An antenna or corona probe.
For end-winding corona measurement, the
antenna is usually about 1 in long, sur-
tween exposed top-coil surfaces and the iron of rounded by an insulation housing, and
the slot may be taken with a low-voltage mounted on the end of a long insulating
ohmmeter, used with a suitable probe. If handle.
slot wedges are not removed, it is often possi- For internal-cavity-discharge (corona) mea-
ble to obtain these resistance measurements, surements, these utilize a multiturn coil
through core vents, from the coil side to the wound on a ferrite rod approximately 2 in long
iron of the core. Resistance measurements by 0.25 in diameter and mounted on the end of
should be made at several locations along the an insulating handle. Measurements are
slot length of every stator coil. Since bottom- made by placing the ferrite rod over the teeth
coil sides are relatively less accessible, eval- enclosing the coil being tested.
uations are usually based on values measured (3) An amplifier and indicator (for con-
on top-coil sides. Values of coil surface contact nection to the antenna) or a peak-pulse meter
resistance, when in accordance with manu- (for connection to the ferrite corona probe).
facturer's recommendations, verify adequate The amplifier is one of the usual type for au-
coil surface grounding and the absence of slot dio frequencies and must reject 60 Hz and ra-
discharge. dio frequency signals. The indicator may be
earphones, an output meter, or a cathode-ray
8.1.5.2 Corona-Probe Test. The corona- oscilloscope.
probe test is intended to be an indicator and The peak-pulse meter is a broadband in-
locator of unusual ionization about the insu- strument calibrated in units of picocoulombs
lation structure. This test is sensitive to end- of apparent charge. Measurements may be ob-
winding surface corona, as well as internal- tained from the meter itself or by connecting
cavity ionization in the insulation structure. the meter output to an oscilloscope or chart
Compared to slot discharge, the discharge en- recorder.
ergies involved in surface corona or internal- The use of the corona-probe test and the
cavity ionization may be of a much lower or- evaluation of test data obtained is in relative-
der of magnitude. The energy in the discharge ly early stages of development and study. The
varies as the square of the voltage across the ability of the test to distinguish varying in-
gap and directly as the effective capacitance tensities of external corona activity and inter-
at the point of breakdown. nal cavity corona has been established. How-
Partial Discharge (Corona) has several un- ever, the evaluation of data, to permit dis-
desirable effects, such as chemical action, pro- crimination between harmful and acceptable
duction of heat, and ionic bombardment. The levels, has not yet reached the stage where in-
deteriorating effects of corona are dependent dustry standards are established.
on its intensity and repetition rate as well as
the design of the insulation system involved. 8.1.6 Winding Resistance. A reduction in
Inorganic insulation components such as winding resistance may indicate shorting of
mica and glass are not affected seriously by co- conductors. An increase in winding resistance
rona. Charring or decomposition of organic may indicate poor connection.
materials will occur in the vicinity of contin- Resistance of the stator winding is usually
ued corona activity. However, surface effects measured with a low-resistance (Kelvin)
may be limited by insulating finish treat- bridge or by the drop-in-potential method. Re-
ments incorporating pigmentation to resist at- fer to IEEE Std 118-1949, Master Test Code
tack from the weak acid deposits formed by for Resistance Measurement (see Section 9).
surface corona in the presence of oxygen and The measurement is normally made for each

• moisture .
Corona-probe-test equipment consists of
three basic units:

15
phase separately. The stator winding should
be at room temperature when the cold resist-
ance measurement is made, and the temper-
IEEE
Std 56-1977 IEEE GUIDE FOR INSULATION MAINTENANCE OF

ature of the winding carefully determined.


Refer to IEEE Std 119-1974, Recommended 6~,". ,.·
R.
Practice for General Principles of Temper-
ature Measurement as Applied to Electrical
Apparatus (see Section 9).
The resistance-temperature characteristic
of copper in the range of temperatures usually VOLTAGE
encountered is a straight line which, if extra- '-------------0 SOURCE

polated, intersects the zero resistance axis at . Rx = RTD element


0
- 234.5 C. Based on this characteristic, the R A. R B. R c = Lead resistances
temperature corresponding to any resistance A. B. C = RTD terminals
of a copper winding may be determined from R 1. R 2. R 3 = Known resistances
the formula: .
Fig 1
R2 RTD and Wheatstone Bridge Circuit
t2 = R1 (234.5 + t1 ) - 234.5

where R I and R 2 are winding resistance in 8.1.8 Insulation-Resistance Test of Em-


ohms measured at temperatures of t I and bedded Temperature Detectors. Stator wind-
t 2 C. respectively.
0
ing embedded temperature detectors (resist-
ance or thermocouple types) are connected by
8.1.7 Resistance Temperature Detectors. cable to a terminal board on the frame of the
RTDs (Resistance temperature detectors) are unit. Often one lead of each of the detectors is
resistance coils so constructed that the tem- connected to a common ground strip at the
perature may be measured by change in resist- terminal board. If a detector located in the
ance. slot portion should become grounded, cir-
Measurements are usually made in order to culating currents could occur between that ~-~
verify that RTDs are properly· connected and ground and the terminal board ground. To ~)"
that they are free of undesired ground con- guard against this possibility, insulation re-
tacts or open circuits. Measurements consist sistance measurement should be made on the
of comparisons of readings from each RTD detectors at convenient intervals. Tests are
with all others, and should be made at room usually made on all detectors simultaneously
temperature. Refer to IEEE Std 118-1949 and at 500 V dc after the terminal board common
IEEE Std 119-1974 (see Section 9). has been isolated from ground. (Recording
For the measurements, a resistance bridge is equipment, connected externally to the termi-
normally used. A special RTD meter for nal board, should be isolated from the test po-
directly reading temperatures of detectors can tential.)
also be used. Referring to Fig. 1, all three leads 8.1.9 Insulation Resistance Test of Insu-
of a given RTD must be of equal length and lated Stator-Through-Bolts. Insulation resist-
wire size so that the three lead resistances all ance to ground of Stator-Through-Bolts
have the same value. By subtracting the re- should be measured at a voltage level recom-
sistance measured between terminals Band C mended by the manufacturer.
from the resistance measured between termi- 8.1.10 Test of Interlaminar Insulation of
nals A and C (or A and B), the resistance of Stator Core. A test, often referred to as a loop
the temperature sensing element alone can be test or a ring test, has been found to be an ef-
accurately determined. The temperature ele- fective and relatively easy method of testing
ment is usually made of copper wire and is ap- interlaminar resistance of stator core. Prior to
propriately sized so that its resistance at 25° C conducting this test it is recommended that
is 10 n . From the measured change in resist- the manufacturer be consulted.
ance, the temperature of the element may be In cases where significant damage is visual-
calculated. After proper meter corrections are ly evident, the interlaminar insulation must
applied, temperature readings of each RTD be reestablished before the application of the
and the thermometer readings should agree to test. Otherwise, additional overheating and
within plus or minus 3° C. burning damage may occur during the test.

16
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY Std 56-1977

• 8.1.10.1 Safety Considerations. Consid-


erable hazard may exist in connection with
this test. All test personnel involved should be
familar with the safety precautions which
should be observed. The following is a list of
some of the major safety items related to this
tor Coil Insulation, details the recommended
practice for the power factor tip-up test.
Dissipation-factor or power-factor tests pro-
vide useful information for evaluating the in-
sulation structure of high-voltage machine
windings. The value and significance of the
test: test is greatly dependent on the size of the test
(1) Shielded cable should never be used for sample. Dissipation-factor or power-factor
the magnetizing coil as applied voltage will values measured on a complete assembly are
also be induced into the cable shield. averages of those values which would have
(2) Do not go near the magnetizing coil or been obtained on individual components of
the stator core when the test setup is ener- that assembly. Thus, weaknesses or deteriora-
gized. tion in one component may be masked by the
(3) All electrical connections should be average dissipation factor or power factor
checked before a trial application of power is measured on an entire assembly.
made.
(4) Appropriate fire protection should be
made available during the test.
8.2 Rotor Winding
(5) Liquid cooling system, if present, should
8.2.1 Insulation Resistance. IEEE Std 43-
be drained and remain empty.
1974 outlines a recommended practice for
(6) Machine terminals should be opened
measuring insulation resistance.
and safely covered and flagged.
8.2.2 Dielectric Absorption Test. IEEE Std
(7) Stator RTDs and their recorder should
43-1974 outlines a recommended practice for
remain in service during tests.
measuring dielectric absorption.
(8) Adequate phone and other communi-
For this test the potential is usually 500 V
cation systems should be established among
dc.
various points for proper test control.
8.2.3 Winding Resistance. A reduction in
(9) If thermocouples are used for temper-
winding resistance may indicate shorting of
ature measurements, a considerable personnel
conductors. An increase in winding resistance
hazard may exist since up to full search coil
may indicate poor connection.
voltage can be induced in the thermocouple
When using the voltage-drop method,
lead. Also, care should be exercised to avoid
changes in winding temperature and resist-
short circuiting laminations with the thermo-
ance should be limited by using a value of di-
couple lead.
rect current not exceeding one-third the rated
(10) On large machines, for example,
value.
steam-turbine generators, cables should be se-
The rotor winding should be at room tem-
cured against motion during energizing.
perature before the cold resistance measure-
(11) Care must be taken that no metallic
ment is made, and the temperature of the
objects are in contact with the air-gap side of
winding carefully determined.
the core laminations. Also extraneous metal-
For synchronous machines, it is necessary
lic structural objects, metal ladders, crane ca-
that field resistance and the corresponding
bles, etc, which might form a conducting cir-
temperatures be accurately measured since
cuit around the core, should not be left in the
the temperature rise of the field winding dur-
machine during test.
ing operation is commonly determined from
8.1.10.2 Test Procedure. A summary of the change in resistance.
helpful notes and precautions concerning the In measuring the rotor resistance by the
performance of this test are given in Appendix voltage-drop method, it is essential that volt-
A. age contacts for the voltmeter be placed
directly on the collector rings or exposed leads

'.
8.1.11 Insulation Dissipation-Factor or of the rotor winding.
Power-Factor Tests. IEEE Std 286-1975, Rec- 8.2.4 Winding Impedance. The presence of
ommended Practice for Measurement of Pow- short-circuited turns in the windings of cylin-
er-Factor Tip-Up of Rotating Machinery Sta- drical rotors of turbine-generators or individ-

17
IEEE
Std 56-1977 IEEE GUIDE FOR INSULATION MAIN1'ENANCE OF

ual field coils of salient-pole generators or mo- The effects of short-circuited turns on rotor
tors may be detected by impedance measure- vibration may be due to electromagnetic or
ments. These measurements are usually ob- thermal influences. Electromagnetic effects
tained by applying 110 V at power frequency would inherently be more pronounced on ro-
across the collector rings and measuring the tors with four or more poles. Removal of ex-
input current and voltage at standstill. At citation will often indicate whether the effects
constant input conditions, voltages are mea- are electromagnetic, thermal, or both. If
sured across the field coils of individual poles. . short-circuited turns cause thermal un-
With the field coils connected in series, sim- balance, the vibration will vary with temper-
ilar coils should have a comparable voltage ature and hence will lag any increase in ex-
drop. A running impedance test may be per- citation by the length of time required for
formed by measuring voltage and current at heating to occur. If variations from the cold to
the collector rings while the rotor speed is in- the hot condition are not too great, weight ad-
creased. This method determines the speed at justments can sometimes be made to keep the
which an intermittent short circuit occurs. (If vibration amplitude entirely within a satisfac-
a rotor has brushless excitation, the manu- tory range for all temperatures. Otherwise, ei-
facturer's instructions should be reviewed ther thermal balancing or reinsulation of the
carefully before making impedance tests.) short-circuited turns is necessary.
Under test conditions, the effect of a short- If the primary effect of short-circuited rotor
circuited turn in a field coil can be compared turns is an increase in excitation require-
to the effect of a shorted secondary on the im- ments, reinsulating would be dependent on
pedance of a transformer. Field coils with the ability to supply sufficient field excitation,
shorted turns will have a significantly lower under normal reactive load conditions, with-
impedance ·(and lower voltage drop) than the out exceeding exciter or rotor recommended
remaining coils, with no short circuits, in the operating temperature limits.
series circuit. When a coil with short-circuited Experience on generators has shown that
turns has been discovered, the test may be ex- short-circuited rotor turns are not usually
panded to measure the voltage drops across progressive in nature and are more apt to re-
individual coil turns. The ease of applying duce the temperature in their respective coils
this exploratory test is dependent on the con- than increase them. However, due to in-
struction of the coil and the available access to creased excitation current requirements, the
individual turns.
average rotor temperature is increased even
The overall ohmic value of winding imped- though a voltage-drop type of temperature in-
ance obtained from the impedance test is use- dicator may show the reverse.
ful if an initial reading, with no short-cir-
cuited turns, is available for comparison. Changes in rotor excitation requirements
When ohmic values are used for comparison may be detected by comparison of a recent no-
purposes, test results should have been ob- load saturation curve with the original curve.
tained at approximately the same voltage for If the rotor has a temperature recorder, the
the two tests being compared. chart should be examined for indications of a
sudden drop in rotor resistance at the time vi-
Rotor windings of synchronous motors of-
bration appeared.
ten suffer progressive damage from the high
currents induced in the shorted turns during 8.2.5 Winding Flux Distribution. In addi-
each start up. However, generator rotors have tion to the impedance measurements referred
been known to operate satisfactorily for many to in Section 8.2.4 of this guide, several other
years with a few short circuits between succes- tests are available by means of which short
sive turns in one or more coils. Therefore, re- Circuits between turns of cylindrical-pole ro-
insulation of generator rotor short-circuited tors can often be detected and located.
turns is often unnecessary. Location of the slots containing short-cir-
In operation, the first signs of short-cir- cuited turns or coils may be possible in solid
cuited rotor turns may be increased rotor vi- rotors without retaining ring removal, by
br ation or increases in excitation require- measuring the leakage flux across the top of
ments. the slot wedge with an alternating voltage ap-

18
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY Std 56-1977

• plied to the collector rings. and comparing the


readings for the various slots. With non-
magnetic wedges. a single short-circuited turn
out of 20 to 30 turns will reduce by nearly 50%
the alternating voltage induced in an explor-
IEEE Std 433-1974, Recommended Practice
for Insulation Testing of Large AC Rotat-
ing Machinery with High Voltage at Very
Low Frequency.
IEEE Std 454-1973, Recommended Practice
for the Detection and Measurement of Par-
ing coil held above the slot wedge. Slots with
magnetic wedges should be compared with tial Discharges (Corona) During Dielectric
one another. as their leakage flux is quite low. Tests.
An oscilloscope is often useful to measure the IEEE Project 522, Guide for Testing Turn-to-
exploring-coil voltage. which will be quite low. Turn Insulation on Form Wound Coils for
if a 110 V ac supply is used across the collector Rotating Machinery.
rings. Other means are also used. such as an
ac potentiometer or a vectormeter. In some 1
9.2 ASTM Standard
cases. a detector coil may be built into the sta- ASTM Std D3382-75, Standard Methods of
tor, in the main stator body. embedded in a Test for Measurement of Energy and Inte-
stator slot-wedge or inserted into the gap. grated Charge Transfer Due to Partial Dis-
charges (Corona) Using Bridge Techniques.

9. References
10. Bibliography
9.1 IEEE Standards
IEEE Std 4-1968. Techniques for Dielectric [1] VAN HESS, B. Generator-Insulation Tests.
Tests (ANSI C68.1-1968). Bulletin, Edison Electric Institute, vol 6,
IEEE Std 43-1974, Recommended Practice May 1938, pp 204-206.
for Testing Insulation Resistance of Rotat- [2] SUBJECT COMMITTEE ON GENERA-
ing Machinery. TOR INSULATION AND TESTING. Field
IEEE Std 51-1955, Guiding Principles for Di- Testing of Generator Insulation. AlEE
electric Tests. Transactions, vol 60, Dec 1941, pp 1003-
IEEE Std 62-1958, Guide for Making Dielec- 1011.
tric Measurements in the Field. [3] DAVIES, E. R., and LEFTWICH, M. F.
IEEE Std 67-1972, Guide for Operation and Progress Report of D-C Testing of Genera-
Maintenance of Turbine-Generators (ANSI tors in the Field. AlEE Transactions, vol 61,
C50.30-1972). Jan 1942, pp 14-18.
IEEE Std 95-1976, Recommended Practice [4] FIELD, R. F. The Basis for the Nondestruc-
for Insulation Testing of Large AC Rotat- tive Testing of Insulation. AlEE Trans-
ing Machinery with High Direct Voltage. actioTl.';, vol 60, Sep 1941, pp 890-895.
IEEE Std 100-1972, Dictionary of Electrical & [5] MONTSINGER, V. M. Breakdown Curve
Electronics Terms (ANSI C42.100-1972). for Solid Insulation. AlEE Transactions, vol
IEEE Std 115-1965, Test Procedure for Syn- 54, Dec 1935, pp 1300-1301.
chronous Machines. [6] PEEK, F. W., Jr. Dielectric Phenomena in
IEEE Std 118-1949, Master Test Code for Re- High-Voltage Engineering. New York:
sistance Measurement. McGraw-Hill Book Company, 1929.
IEEE Std 119-1974, Recommended Practice [7] HAYDEN, J. L. R., and EDDY, W. N.
for General Principles of Temperature Mea- Dielectric Strength Ratio Between Alter-
surement as Applied to Electrical Ap- nating and Direct Voltages. General Electric
paratus. Review, vol 26, 1923, pp 645-652.
IEEE Std 286-1975, Recommended Practice [8] GILT, C. M., and BARNS, B. L. Insulation
for Measurement of Power-Factor Tip-Up Tests of Electrical Machinery Before and
After Being Placed in Service. AlEE Trans-
of Rotating Machiney Stator Coil Insula-
actioTl.fi, vol 48, Apr 1929, pp 656-665.
tion.
IEEE Std 432-1976, Guide for Insulation
Maintenance for Rotating Electrical Ma- 1 American Society for Testing and Materials, 1916
chinery (5 HP to less than 10000 HP). Race Street. Philadelphia, Pa., 19103.

19
IEEE
Std 56-1977 IEEE GUIDE FOR INSULATION MAINTENANCE OF

. [9] HURD, D. T. Mechanism of Dielectric [22] MARCROFT, H. C. Use of Dieelctric-Ab-


Breakdown. General Electric Review, vol 51, sorption TeRts in Drying Out Large
Dec 1948, PI> 26-:3:3. Generators. AIE1~ Transactions, vol 64, Feb
[10] ATKINSON, F. W., and TAYLOR, R. B. A i9"!), pp !)6-60.
Portable Instrument for Measuring Insula- [23] RYLANDER, J. L. A High-Frequency Volt-
tion HCRiRtnncc nt High Voltnge. AIEl~ age Test' for Insulation of Hotating Elec-
'i'ransaction8, vol U4, Apr HHo, PI> 1()4·1()(). trical AppnrntuA. ;\ I /I:/~ Tran,'Iad;on,'I, vol "!),
[11] ATKINSON, F. W., and HI~WSON, J. Di- Feh IH26, PI> 4GH-40G.
rcct-Current Over-Potentinl Testers for [24] FOUST, C. M., and nOHATS, N. Insulation
High-Voltage Immlation Fault Detection, Testing of Electric WindingR. AlEE TranH-
AlEE Technical Paper No 51-128, pre- actions, vol 62, Apr 194:3, PI> 203-206.
sented at the AlEE Winter General Meeting, [25] SEXTON, H. M., and ALKE, R. J. Detec-
New York, NY, Jan 22-26, 1951. tion of Turn-to-Turn Faults in Large High-
[12] WISEMAN, R. W. Maintenance Over- Voltage Turbine Generators. AlEE Trans-
Potential Tests for Armature Windings in actions, vol 70, part I, 1951, pp 270-274.
Service. General Electric Review, vol 53, Aug [26] RAWLS, J. A. Power Factor Testing of Elec-
1950, pp 24-28. tric Equipment to Determine Insulation
[13] HUNT, J. F.,and VIVIAN, J. H. Operation Values. AlEE Technical Paper No 51-37,
of Synchronous Machines for Continuity of presented at the AlEE Winter General
Service on Southern California Edison Com- Meeting, New York, NY, Jan 22-26, 1951.
pany System. Minutes, Electrical Equip-
[27] DOBLE, F. C. The A-C Dielectric Loss and
ment Committee, Edison Electric Institute
Power-Factor Method for Field Investigation
(New York), May 3; 1949.
of Electrical Insulation. AlEE Trans-
[14] HUNT, J. F., and VIVIAN, J. H. Routine
Insulation Testing of Synchronous
actions, vol 66, 1941, pp 934, 939.
Machines. AlEE Transactions, vol 70, part I, [28] POVEY, E. H., and OLIVER, E. F. Non-
1951, pp 756-762. destructive Testing of Generator Insulation.
[15] JOHNSON, J. S. A Maintenance Inspection AlEE Technical Paper No 51-130, presented
at the AlEE Winter General Meeting, New
t/'
Program for Large Rotating Machines.
AlEE Transactions, vol 70, part I, 1951, pp York, NY, Jan 22-26, 1951.
749-755. [29] JOHNSON, J. S. Slot Discharge Detection
[16] MOSES, G. L. Alternating and Direct Between Coil Surfaces and Core of High-
Voltage Endurance Studies on Mica Insula- Voltage Stator Windings. AlEE Trans-
tion for Electric Machinery. AlEE Trans- actions, vol 70, part II, 1951, pp 1993-1997.
actions, vol 70, part I, 1951, pp 763-769. [30] rJOHNSON, J. S., and WARREN, M. Detec-
[17] LAFFOON, C. M., HILL, C. F., MOSES, G. tion of Slot Discharges in High-Voltage
L., and BERBERICH, L. J. A New High- Stator Windings During Operation. AlEE
Voltage Insulation for Turbine-Generator Transactions, vol 70, part II, 1951, pp 1998-
Stator Windings. AlEE Transactions, vol 70, 2000.
part I, 1951, pp 721-730. [31] TOMLINSON, H. R. Interlaminar Insula-
[18] ASKEY, J. S., and JOHNSON, J. S. Insula- tion Test for Synchronous Machine Stators.
tion Resistance and Dielectric-Absorption AlEE Transactions, vol 71, part III, Aug
Characteristics of Large A-C Stator Wind- 1952, pp 676-677.
ings. AlEE Transactions, vol 64, Jun 1945,
[32] Capacitance of Synchronous-Machine Arm-
pp 347-351.
ature Windings Determined for High-
[19] JOHNSON, J. S., and WElL, C. Factors
Potential Test. General Electric Review, J ul
Affecting Insulation Resistance of Large
1947, pp 26-30.
D-C Machines. AlEE Transactions, vol 65,
Nov 1946, pp 705-710. [33] CAMERON, A. W. W. Diagnoses of A-C
[20] WIESEMAN, R. W. Insulation Resistance Generator Insulation Condition by
of Armature Windings. AlEE Transactions, Nondestructive Tests. AlEE Transactions,
vol 53, Jun 1934, pp 1010-1021. vol 71, part III, Jan 1952, pp 263-274.
[21] RYLANDER, J. L. Effect of Temperature [34] MARCROFT, H. C. Field Studies of
on Insulation Resistance. Electric Journal, Generator Windings. AlEE Transactions, .)/~
Aug 1935, Sep 1937. vol 71, part III, Oct 1952, pp 822-829.

20
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY Std 56-1977


[35] ALKE, R. J. D-C Overpotential Testing Ex- [42] CURDTS, E. B. Insulation Testing by
perience on High-Voltage Generators. AlEE D-C Methods. Technical Publication
Transactions, vol 71, part III, Aug 1952, pp 22Tl, James G. Biddle Company.
567-570. [43] HARROLD, R. T., FORT, E. M., and
[36] HILL, G. L. Testing Electrical Insulation of GOODWIN, T. A. The Interpretation of
Rotating Machinery with High-Voltage Corona and Dielectric Measurements on the
Direct Current. AlEE Transactions, vol 72, Mica-Asphalt Insulation of a 30-Year-Old
part III, Apr 1953, pp 159-174. Waterwheel Generator at Grand Coulee
[37] DUKE, C. A., SMITH, L. E., ROBERTS, Dam. IEEE Transactions on Power Appara-
C. A., and CAMERON, A. W. W. Investiga- tus and Systems, vol 92, Nov/Dec 1973, pp
tion of Maintenance Tests for Generator In- 1935-1944.
sulation. AlEE Transactions, vol 80, part
[44] FINDLAY, D. A., BREARLEY, R. G., and
III, Aug 1961, pp 471-480. LOUTTIT, C. C. Evaluation of the Internal
[38] SIDWAY, C. L., and LOXLEY, B. R. Insulation of Generator Coils Based on Pow-
Techniques and Examples of High-Voltage er-Factor Measurements. AlEE Trans-
D-C Testing of Rotating Machine Windings. actions, vol 78, part IlIA, Jun 1959, pp
AlEE Transactions, vol 72, part III, Dec 268-279.
1953, pp 1121-1129.
[39] MOSES, G. L., and HARTER, E. F. [45] DAKIN, T. W. Corona Pulse Detection Cir-
Winding-Fault Detection and Location by cuits and Their Calibration, AlEE Techni-
Surge-Comparison Testing, AlEE Trans- cal Paper No 62-260, presented at the AlEE
actions, vol 64, Jul 1945, pp 499-503. Winter General Meeting, New York, NY,
Jan 28-Feb 2, 1962.
[40] JOHNSON, J. S. Preventive Maintenance

(. Inspection and Testing of Motors and [46) DAKIN, T. W., WORKS, C. N., and JOHN-
Generators. Westinghouse Maintenance SON, J. S. An Electromagnetic Probe for
News (Westinghouse Electric Corporation, Detecting and Locating Discharges in Large
East Pittsburgh, PA), vol 23, no 4, 1959, vol Rotating-Machine Stators. IEEE Trans-
24, nos 1 and 2, vol 25, no 1, 1960. actions on Power Apparatus and Systems,
[41] HERMANN, P~ K., MARHT, R., and vol 88, Mar 1969, pp 251-257.
DOON, H. H. Detecting and Locating Inter- [47] OLIVER, J. A., WOODSON, H. H., and
turn Short Circuits on Turbine Generator JOHNSON, J. S. A Turn Insulation Test for
Rotors. IEEE Transactions on Power Ap- Stator Coils. IEEE Transactions on Power
paratus and Systems, vol 82, Oct 1963, pp Apparatus and Systems, vol 87, Mar 1968,
686-698. pp 669-678.

II
"

21
IEEE
Std 56-1977 IEEE GUIDE FOR INSULATION MAINTENANCE OF

Appendix
Test of Laminar Insulatjon in Stator Cores
IThis appendix is not a part of IEEE Std 56-1977, Guide for Insulation Maintenance of Large Alternating-Current Rotating Ma-
chinery (10000 kVA and Larger).1

Incl uded in this appendix are some helpful A3. Calculations


considerations to aide in the testing of lami-
nar insulation in stator cores. The following calculations are performed in
designing the test. Volts-per-turn value for the
magnetizing coil as well as the search coil is
A 1. Design of Magnetizing Coil given by:

In order to test the stator core adequately, it


is necessary to magnetize the core at approxi- VPT = 4.44f ¢ 10- 8 (Eq 1)
mately its normal operating peak. (D -D )
The turns of the magnetizing coil should en- ¢=B 1
2 2 L eff (Eq 2)
circle the stator through the main bore (after
rotor is removed) and around the outer frame. where
A preferable return ·route, if available, is near VPT volts (rms) per turn
the outside diameter of the core, within the f = frequency in hertz
frame. On large-diameter machines (such as ¢ peak core flux in lines
waterwheel generators), the magnetizing coil B peak core-flux density in lines per
should be distributed around the periphery of square inch (from manufacturer)
the stator to ensure uniform flux distribution outside diameter of core in inches
around the entire core. A clearance of 3 in to diameter to bottom of stator slots in
12 in should be maintained between the mag- inches
netizing-coil conductor and solid metal (that effective length of core in inches
is, metal floor, frame, etc).
The effective length' of core should be ob-
tained from the manufacturer. If that is not
A2. Search Coil possible, the value can be calculated as fol-
lows:
A single turn of A WG 12 to 18 wire, insu-
lated adequately for the volts per turn ap- Leff =(L-Nvbv)Fs (Eq 3)
plied, should be placed around the core, pref- where
erably diametrically opposite from the magne- L gross length in inches
tizing coil. The actual core flux density can be number of ventilation ducts
measured by placing the search coil so that it width of ventilation duct in inches
encircles only the core and does not include core stacking factor (from manufac-
the frame members. On most machines this is turer
not possible, but the error in measured flux
density is acceptable. From the known supply of voltage and the
A voltmeter connected to the search coil will volts-per-turn value from Eq (1), the number
read approximately the volts per-turn value of turns for the magnetizing coil can be deter-
calculated in Section A3. mined by direct division. The result should be

22
IEEE
LARGE ALTERNATING-CURRENT ROTATING MACHINERY 8td 56-1977

• rounded to the next higher integer. This num-


ber of turns should be used in the first trial
test.
In order to determine the size of the cable
necessary for the magnetizing coil, data on
ampere-turns per inch of mean back iron per-
Using the results from Eq (4), the approxi-
mate minimum conductor area can be calcu-
lated.

A4. Temperature Measurements


iphery corresponding to the core-flux densities
will be required. These data should be obtain- The magnetizing coil should be located re-
ed from the manufacturer. mote from the areas suspected as damaged in
The magnetizing-coil current requirement order to facilitate temperature measurement.
is given by: Thin shavings of paraffin, thermometers af-
fixed with a suitable putty, thermocouples,

It
= ATI
Nt
(Dl +D2)
2 1l' (Eq 4)
portable pyrometers, or infrared cameras can
be used to detect hot spots. These should be
detectable in 15 to 30 s if the low interlaminar
where resistance is located at the bore surface. If the
It magnetizing coil current in am- low interlaminar resistance is radially out-
peres ward from the tooth surface or in core areas
ATI ampere-turns per inch (from manu- below the bottom of stator slots, 10 to 20 min
facturer) of excitation may elapse before the heat be-
number of turns comes evident at the tooth bore surfaces. A fi-
3.14 nal heat run of 1 to 3 h should be made after
(see Eq 2) all repairs are completed .

• 23

You might also like