DATA SHEET FOR FOAM CHAMBERS FOR TANK

1.0 GENERAL

1.1 Location Kemari, Karachi

1.2 Quantity 5

2.0 CONSTRUCTION

2.1 Material Manufacturer Standard

2.2 Type Vertical

2.3 Rating Class 150

2.4 Body Size Vendor to Specify

2.5 Inlet Flange Size Vendor to Specify

2.6 Outlet Flange Size Vendor to Specify

3.0 OPERATING CONDITION

3.1 Flow Rate of Foam Solution 175 US Gallon Per Minute (per foam chamber)

3.2 Flow Medium Foam Solution

3.3 Composition 3%

3.4 Foam Type AFFF FOAM CONCENTRATE

3.5 Location Shell Mounted (Top)

4.0 WORKING PRESSURE

4.1 Normal 10 bar(g)

4.2 Minimum 5 bar(g)

4.3 Hydrostatic Test Pressure 15 bar(g)

5.0 OPTIONS

5.1 Painted Finish Manufacturer Standard

Underwriter laboratories, Lloyds Register or other equivalent international agencies


5.2 Approval / Certified
approved by the Owner.

Note:
1. All design & materials requirement should comply with NFPA Standard.