You are on page 1of 11

Indian Geotech J

DOI 10.1007/s40098-017-0230-1

TECHNICAL NOTE

Deep Excavation Supported by Diaphragm Wall: A Case Study


J. Jasmine Nisha1 • M. Muttharam1

Received: 6 July 2016 / Accepted: 2 March 2017


 Indian Geotechnical Society 2017

Abstract Space scarcity and demand for us to build Introduction


skyscrapers as well as deeper basements are increasing in
the present scenario. Excavations are commonly carried out Due to cost concern and scarcity of land, there has been
in congested areas to increase underground usable spaces. number of projects requiring multi storied office buildings
Hence a case study is made on shoring system for exca- with basements having large floor area. Such buildings are
vation depth of 14.2 m for an office block located in Noida. situated at strategic points with structures and congested
The office blocks which consist of 14 stories with 3 levels roads around the site. The excavation alters the stresses and
of combined basement are surrounded by existing struc- disturbs the existing equilibrium and become unstable.
tures and service lines. Subsoil of the study area mainly Hence executions of deep excavations become one of the
consists of two strata, silty sand with occasional gravel and important tasks of a geotechnical engineer in the modern
sand with traces of silt at deeper depth. Diaphragm wall is times.
supported by soil anchors during excavation and after As construction space is generally limited and control of
basement construction is over, the diaphragm wall will ground movement is important, the involvement of spe-
derive horizontal support from the floor slabs and the cialized foundation technologies, sophisticated equip-
basement raft. Hence analyses of diaphragm wall are ment’s, new methods in underground construction, safety
divided into two phases and are carried out using PLAXIS and monitoring systems are necessary to prevent the failure
2D and STAAD Pro software. Inclinometers are used to of excavations. Therefore, in order to improve the stability,
monitor the diaphragm wall deflection and a similar trend support systems are used to prevent the failure of excava-
of displacement pattern is observed between the predicted tions. Although various supporting systems are available,
and the measured lateral deflection of the wall. Cross-hole economical design of supporting system without compro-
sonic logging and Koden test were also carried out to check mising on the safety is of paramount importance. Choice of
the quality of concrete and verticality of the drilled hole a suitable method for support system of excavation
respectively. depends on several factors such as the depth of excavation,
soil profile, sensitivity of the adjacent structure, water
Keywords Excavation  Diaphragm wall  Anchor  table, duration of protection in case of temporary protec-
Plaxis  Inclinometer tion etc.
The performance of tied-back walls and braced walls
using finite element analysis is compared and examined the
effects of pre-stressing, anchor stiffness, anchor spacing,
& J. Jasmine Nisha wall rigidity and excavation depth on tied-back walls with
j_nisha2k@yahoo.co.in
parametric finite element studies [1]. A parametric study
M. Muttharam using finite element method is performed to assess the
muttharam@annauniv.edu
effects of the wall properties, depth of competent soil,
1
Soil Mechanics and Foundation Engineering, CEG, Anna excavation width and wall embedment on deep excavation
University, Chennai, India stability in clay [2].

123
Indian Geotech J

Fig. 1 Site plan

Fig. 2 Observed N values

Table 1 Subsoil profile Settlements and lateral deflections measured at three


Stratum Depth below NGL Soil classification
deep excavation sites of South Korea constructed in mixed
(m) ground profiles are analysed with respect to the construc-
tion process [3], categorized as (1) pre excavation i.e.,
I 0.5–1.0 Filled up soil preliminary site work and wall installation (2) main exca-
II 1.0–4.0 Silty sand vation to final subgrade for basement construction and (3)
III [4.0 Sand post excavation i.e., removal of bracing and basement
construction and concluded that deep excavations made
through mixed soil and rock profiles exhibited smaller

123
Indian Geotech J

Fig. 3 Support of excavation system

Table 2 Details of diaphragm walls


Thickness of the Top level of the Depth of open Level of anchors Embedment Maximum depth of
D-wall D-Wall excavation depth of excavation
(mm) (m) (m) D-wall (m)
(m)

800 200.58 (FRL) 0 3 levels (3, 7 and 11 m from 7 14.2 from FRL
FRL)
600 4 m below FRL 4 2 levels (7 and 11 m from 6 14.2 from FRL
(196.58) FRL)

lateral wall movements than similar excavations made in present study aims to discuss a case study on deep exca-
homogeneous soil profiles. vation supported by diaphragm wall.
The application of a generalized effective stress soil
model, for predicting the performance of 22 m deep
excavations in the M1 pit near the Lehrter Bahnhof in Site Descriptions
central Berlin is described [4]. The behaviour of a 16-18 m
deep excavation for a metro station using cut-and-cover The site for the case study considered in the research work
technique in soft clay in the Shanghai metropolitan area is is located along Noida (India). The plot area of the pro-
studied [5] and concluded that the magnitudes of wall posed building is approximately 24,000 m2. The project
deflections, ground settlements and settlements of the includes the construction of Block 1 (G ? 13 floors) with
adjacent buildings and utilities were relatively small and three basements, Block 2 (G ? 13 floors) with three
less than the specified protection levels due to quick basements and Substation. Block 1 and 2 consists com-
excavation and rapid cast of rigid concrete floor slabs right bined basement of 3 levels. The three basement floors will
after the completion of excavation. be used as car parking and remaining all floors are to be
Though several researchers are working on various used as office space. The site investigation comprised of a
aspects of support system for deep excavation as men- series of 23 nos. deep borings in and around the footprint of
tioned in references [6–13], the reported work of case study the proposed building which extends to a depth of 30 m.
on support system for deep excavation is limited. Hence The site plan, along with boreholes and building location,

123
Indian Geotech J

diaphragm walls, and nearby existing structures of the stratigraphy at the site may be divided into three general-
present case study is shown in Fig. 1. Ground water ized strata as given in Table 1.
table was found to be around 6 m below the natural ground
level. The site is almost plain in topography with surface
elevation of 200.58 m. Detail study is made on all the 23 Support System for Deep Excavation
borelog data sheets and their respective laboratory test
results to prepare the generalised soil profile. During the excavation for the basement construction, the
Earlier the site was being used for agricultural purposes. diaphragm wall has been proposed to be supported by soil
The deposits at the site are alluvial in nature. The variation anchors (installed at two or three levels depending on the
of SPT N with depth for typical boreholes is shown in design requirement) as shown in Fig. 3. Initially the anal-
Fig. 2 and it reveals that SPT N values increases with ysis has been carried out by considering 600 mm thick
increase in depth irrespective of the type of soil. The diaphragm wall, two level of anchors and depth of
Table 3 Design soil parameters
Layers (m) Soil description Unit weight of soil Observed SPT ‘N’ value Young’s modulus Poissons ratio, l Friction angle, /
(kN/m3) (kN/m2) (degrees)
Top Bottom

0 4 Silty sand (SM) 15 8 22,900 0.25 27


4 8 Sand (S) 16 14 35,900 0.25 29
8 11 Sand (S) 18 20 47,500 0.25 29
11 17 Sand (S) 19 32 64,400 0.25 30
17 22 Sand (S) 19 46 78,400 0.35 30
22 28 Sand (S) 19 52 80,000 0.35 30
[28 Sand (S) 20 60 85,000 0.35 31

Fig. 4 Schematic
representation of soil anchors
with failure plane

123
Indian Geotech J

embedment as 5 m below the excavation level and found wall based on the comparison between predicted and
that system is not safe. Then different options were anal- measured wall displacements during construction.
ysed by changing the thickness of diaphragm wall, number,
level and spacing of anchors, depth of embedment etc. and Analysis of Diaphragm Wall
finally adopted the safe and economical solution. The
details of diaphragm wall considered for execution are The analysis of diaphragm wall is divided into two phases.
summarised in Table 2. Embedment depth mentioned in The analysis of diaphragm wall supported by soil anchors
Table 2 is the depth of D-wall inserted into the ground in till the final excavation level is said to be Phase 1. Analysis
addition to the excavation depth. Though diaphragm wall of diaphragm wall by considering all the floor slabs in
of thickness 800 mm and 600 mm are adopted in the site, position is termed as Phase 2. Analysis of Phase 1 and 2
the design and performance of 800 mm thick diaphragm were carried out using PLAXIS 2D and STAAD Pro
wall is described in this paper. The main purpose of this software respectively. However, the diaphragm wall is
paper has been to assess the performance of the diaphragm designed as a flexural member for the worst case forces

Horizontal Displacement Bending Moment Shear Force


(mm) (kNm/m) (kN/m)
0 20 40 -250 -50 150 350 550 -200 -100 0 100
0 0 0

2 2 2

4 4 4

6 6 6
Depth (m)

8 8 8

10 10 10

12 12 12

14 14 14

16 16 16

18 18 18

20 20 20

22 22 22
Towards Excavation Towards Excavation

Fig. 5 Analysis results of PLAXIS 2D

123
Indian Geotech J

obtained from both the analysis. Brief description of basement area for lowering the ground water table to 1 m
analysis carried out using these two phases are described in below the bottom of excavation. Therefore no water pres-
Sects. 3.1.1 and 3.1.2. sure is considered for diaphragm wall analysis in this
phase. The excavation was carried out using three levels of
Phase 1: Analysis Using PLAXIS 2D soil anchor system for supporting 800 mm thick diaphragm
wall during the basement construction.
The soil parameters considered for PLAXIS analysis in Soil anchors are designed as pre-stressed anchors and
Phase 1 is shown in Table 3. the design is in accordance to BS 8081:1989 [16], IS:
A surcharge load of 20 kPa [14] is considered in addi- 10270 [17] and IS: 14268 [18] and The anchors are
tion to the earth pressure acting on the diaphragm wall. The designed for a design life of 2 years since the soil anchors
excavation has to be carried out in dry condition for the are designed to support the diaphragm wall till the final
construction activity and hence deep well dewatering sys- excavation level. Type C anchorage is adopted in the
tem [15] is proposed on both outside and inside the design. All the anchors shall be water tight and no leakage

Fig. 6 STAAD model for


800 mm thick diaphragm wall

123
Indian Geotech J

shall be allowed into the diaphragm wall. For the 800 mm Phase 2: Analysis Using STAAD Pro
thick diaphragm wall three levels of anchors are proposed
(viz. 3, 7 and 11 m from the NGL) at a horizontal spacing In Phase 2 analysis, the loads include self-weights and the
of 1.66 m c/c. Detailed design of soil anchors, determina- other downward load calculated based on the tributary area
tion of anchor lengths with failure wedge were carried out of the basement slabs depending upon the support system
for the present study. Refer Fig. 4 for the schematic rep- at the corresponding levels. At-rest earth pressure condition
resentation of soil anchors with failure plane. is considered behind the diaphragm wall along with the
Phase 1 analysis is carried out using PLAXIS 2D soft- surcharge of 20 kPa. The design water table level is con-
ware as a plane strain problem. In this analysis, the dia- sidered at ground level on soil side in this analysis.
phragm wall is modelled as plate element, soil anchors are In Phase 2 analysis, the diaphragm wall is modelled as a
modelled as node-to-node anchors and geo-grid elements 2D beam element of unit meter width on the out of plane
for free length and fixed length portion respectively. The direction. The soil resistance in the embedded portion of
soil behavior is modelled using Mohr–Coulomb model. the wall is modelled in the form of lateral springs up to the
The maximum total displacement of 50 mm occurs near embedment depth and with vertical spring support at the
the top of diaphragm wall and below the area of surcharge end. The earth pressure from the soil side is applied as
application. Stage wise analysis results of PLAXIS 2D horizontal loading with corresponding load intensity,
such as horizontal deflection, bending moment and shear including the lateral thrust due to vehicular loading and
force is shown in Fig. 5. As the excavation proceeded to ground water pressure. The diaphragm wall acts as a
lower levels, the diaphragm walls began to develop deep retaining wall and is restrained by basement slabs and
seated movements towards the excavation side. The values hence the diaphragm wall is not free to tilt. Therefore earth
of bending moment and shear force are reduced at the pressure at rest condition is considered in the design.
location of soil anchors. However maximum bending STAAD model for 800 mm thick diaphragm is shown in
moment and shear force occurs at the final excavation Fig. 6. Detailed load calculations, earth pressure calcula-
stage. tion for at rest condition and dynamic increment,

Shear Force (kN/m) & Bending Moment (kN-m/m)


-650 -550 -450 -350 -250 -150 -50 50 150 250

-1

-3 Basement slab
at -4.5m
-5

-7
Basement slab Diaphragm Wall
-9
at -9.0m
Depth (m)

-11

-13
Raft slab at
-15 -12.7m

-17

-19 Max. Shear force

-21 Min. Shear force


Max. Bending moment
-23
Min. Bending moment
-25

Fig. 7 Maximum and minimum bending moments and shear force for 800 mm thick diaphragm wall

123
Indian Geotech J

calculation of spring values, STAAD analysis and struc- Ks ¼ K0s =B ð4Þ


tural design of diaphragm wall were carried out for the
present study. Earth pressure calculation with dynamic Where, K0s 4
= 1.3 9 [Es 9 B /(Ep 9 Ip)]^(1/12) 9 Es/(1-
increment is calculated based on IS 1893-1984. The total l2); Es: young’s modulus of the soil, kPa; l: poison’s ratio;
earth pressure of at-rest and with dynamic increment con- B: width of diaphragm wall; Ip: moment of inertia of dia-
ditions linearly increases with depth, whereas the values of phragm wall; fck: grade of concrete, M30; Ep: young’s
earth pressure with dynamic increment is little higher than modulus of the diaphragm wall.
the at-rest earth pressure.
The spring values are obtained using Newmark Eqs. (1), Analysis Results
(2) and (3).
Figure 7 summarises the maximum and minimum values
K1 ¼ ðBL=24Þ  ð7ks1 þ 6ks2  ks3 Þ ð1Þ of Bending Moment (BM) and Shear Force (SF) obtained
 
Ki ¼ ðBL=12Þ  ksði1Þ þ 10ksi þ ksðiþ1Þ ð2Þ from the analysis for 800 mm thick diaphragm wall. It is
  noted from figure that the maximum shear force and
Kn ¼ ðBL=24Þ  7ksn þ 6ksðn1Þ ksðn2Þ ð3Þ bending moment are ?283 and ?106 respectively. Simi-
where, K1, Ki, Kn: are spring stiffness values for the first, larly, minimum shear force and bending moment are -306
ith and last layer respectively; L: depth of interval between and -559 respectively. In the chart, maximum and mini-
the springs; Ks1, ksi, ksn: are soil modulus for the first, ith mum values are shown with respect to positive or negative
and last layer respectively. Soil modulus is determined sign. However in the design, maximum value of shear force
using Eq. (4).

Horizontal Displacement of 800 mm thick Diaphragm Wall (mm)


-40 -30 -20 -10 0 10 20 30 40 50
0
1st level support
2

4
2nd level support
6
Depth below ground level (m)

10 3rd level support

12

Excavation level
14

16 E-79
Towards Excavation
N-52
18
N-21
20
Analysis Result

22

Fig. 8 Comparative plot for numerical versus measured lateral deflection

123
Indian Geotech J

and bending moment were considered irrespective of pos- responses are checked by field monitoring during the works
itive or negative sign. and contingency measures are implemented as and when
necessary. The deflections of the 800 mm thick diaphragm
walls were monitored using three inclinometers. Cross hole
Instrumentation sonic logging test is carried out to check the homogeneity
and integrity of concrete and Koden test is carried out to
As the deep excavation is made very close to buildings and accurately measure and record the shape of a drilled hole of
services, which require safeguarding against damage it was greater depth.
decided to adopt observational method where predicted

W-05 1-2 W-05 1-2


L = 21.27 meters L = 21.27 meters
Spacing = 1.72m Spacing = 1.72m
Gain = 19686 (x16) Gain = 19686 (x16)
02/12/2013 12:45 02/12/2013 12:45

Fig. 9 CSL test graph for diaphragm wall panel number W-05 between tubes 1-2

123
Indian Geotech J

Inclinometer cage. The detailed test graphs received for diaphragm wall
panel number W-05 between tubes 1-2 is presented in
Digital inclinometer with portable and traversing probe Fig. 9.
system is used in the present study for monitoring lateral The following points can be concluded from cross hole
deformation. The predicted behavior of 800 mm thick sonic logging tests conducted on the diaphragm wall panel
diaphragm wall is compared with actual measured behavior no. W-05 based on data, diaphragm wall location and site
using three inclinometers. Figure 8 shows the comparison conditions at the time of testing.
plot between the predicted and actual horizontal displace-
• Diaphragm wall number W-05 shows minor defect for
ment profiles for 800 mm thick diaphragm walls after final
tube corridors 2-3 and 3-5.
level of excavation has reached. By the end of excavation
• The minor defect also seems likely to be reflection from
works for inclinometer E-79, the maximum deflection was
anchors as the locations match with the anchor
about 7 mm. Displacements observed in inclinometer N-52
locations.
was more, with a maximum of about 15 mm. Maximum
horizontal displacement in the other inclinometer N-21 was
still of greater magnitude (27 mm). Koden Test
The curves presented indicate that the numerical
behavior of the wall has a trend similar to that of the actual The Drilling Monitor system has been developed in com-
behavior measured using inclinometers. However, the pliance with the user’s needs arisen from the recent con-
actual realized movements are consequently below the struction environment to accurately measure and record the
predicted values this may be because of various reasons shape of a drilled hole of greater depth. It can be easily
like non homogeneity of soil, assumed design surcharge positioned and set up for measurement to provide quick
was not actually experienced in the site by the walls and so and accurate recordings of excavations. This monitoring is
on. done for every bite of all panels.
With the help of Koden ultrasonic echometer, both the
Cross Hole Sonic Logging Test three dimensional orientations and the actual dimensions of
a panel can be continuously checked. A typical log of panel
The field test of Cross-hole Sonic Logging (CSL) is number N-61 for the present case study is presented in
conducted in accordance with ASTM D6760-08 [19]. For Fig. 10 The vertical line ‘0’ bordered by two strips (X–X0 ),
conducting the sonic logging test five steel tubes of represents the vertical descent path of the probe. The trench
50 mm internal diameter were installed throughout the wall profile is shown by the inner borders of the dark strips.
length of the shaft by tying them to the reinforcement It is inferred that the vertical deviation of diaphragm wall

Fig. 10 Log for panel number


N-61

Panel No. – N 61 Excavation Face Soil Face


Scale X Axis Scale Y Axis
1Division = 50 mm 1Division = 1 m

123
Indian Geotech J

panel number N-61 is 90 mm which is within the permis- geotechnical services team of L&T (B&F) for the help rendered in
sible limit 1 in 80 m. performing the analysis and for their great suggestions which sub-
stantially improved the presentation of this paper.

Conclusion References
This study focuses on the study of deep basement using 1. Clough G, Tsui Y (1974) Performance of tied-back walls in clay.
diaphragm wall. The 800 mm thick diaphragm wall was J Geotech Eng Div 10(12):1259–1273
monitored during the works using three digital inclinome- 2. Goh A (1990) Assessment of basal stability for braced excavation
system using finite element method. Comput Geotech
ters. The results from the observations have been used to 10(4):325–338
analyse the diaphragm wall response to various construc- 3. Gandhi SR, Suresh PK, Raju VS (1998) Lateral load tests on
tion and excavation activities. Observations from the large diameter bored pile and analysis. Indian Geotech Conf
monitoring results and the deduced diaphragm wall 1:373–377
4. Seo M, Olson SM, Yang KS, Kim M (2010) Sequential analysis
responses can be summarised as follows. of ground movements at three deep excavation sites with mixed
ground profiles. J Geotech Geoenviron Eng 136(5):656–668
1. Inclinometer measurements within the diaphragm 5. Nikolinakou MA, Whittle AJ, Savidis S, Schran U (2011) Pre-
walls indicated deep-seated inward horizontal move- diction and interpretation of the performance of a deep excava-
ments due to stress relief during excavation. tion in Berlin sand. J Geotech Geoenviron Eng
2. The predicted behaviour of the diaphragm wall has a 137(11):1047–1061
6. Tan Y, Wei B (2012) Observed behaviors of a long and deep
trend similar to that of the actual behaviour. Overall, excavation constructed by cut-and-cover technique in Shanghai
the predicted displacement trend of diaphragm wall is soft clay. J Geotech Geoenviron Eng 138(1):69–88
similar to the measured lateral deflection of the wall. 7. Konstantakos DC (2008) Online database of deep excavation
3. Inclinometer data indicated that the maximum mea- performance and prediction. In: 6th international conference on
case histories in geotechnical engineering, Arlington, pp 1–12
sured horizontal wall displacements varied from 17.5 8. Fekado T (2010) Analysis and parametric study of deep exca-
to 67.5% of the numerical results. vation supported by diaphragm walls. M.S. Thesis in Geotechnics
4. Cross-hole sonic logging test shows that there is no submitted to Addis Ababa University, Addis Ababa
major defect in the homogeneity and integrity of 9. Leung EHY, Ng CWW (2007) Wall and ground movements
associated with deep excavations supported by cast in situ wall in
concrete. mixed ground conditions. J Geotech Geoenviron Eng
5. Koden tests were carried out and found that the 133(2):129–143
verticality of the drilled hole is within allowable limit. 10. Ou C, Hsieh P, Lin Y (2011) Performance of excavations with
6. The tie-backed retaining wall system proved a suc- cross walls. J Geotech Geoenviron Eng 137(1):94–104
11. Konstantakos DC, Regalado AJWC, Scharner B (2004) Control
cessful method of constructing deep excavations, with of ground movements for a multi-level-anchored diaphragm wall
the major advantage of having no temporary struts during excavation. In: 5th international conference on case his-
obstructing the work site, thus allowing restriction-free tories in geotechnical engineering, New York, pp 1–7
basement construction from raft level. 12. Sen KK, Alostaz Y, Pellegrino G, Hagh A (2004) Support of deep
excavation in soft clay: a case history study. In: 5th international
Extensive monitoring carried out during the construction conference on case histories in geotechnical engineering, New
has given valuable insight into the performance of the York, pp 1–8
13. Wang JH, Xu ZH, Wang WD (2010) Wall and ground move-
diaphragm walls and the behaviour of the soil strata. ments due to deep excavations in Shanghai soft soils. J Geotech
However the final product was an effective design solution Eng ASCE 136(7):985–994
which took advantage of both analysis and project specific 14. Puller M (2003) Deep excavations a practical manual, 2nd edn.,
opportunities along with good workmanship, proper London, Thomas Telford
15. Control of groundwater for temporary works, CIRIA Report 113
installation of the support system and limited construction 16. BS 8081 (1989) British standard code of practice for ground
induced movements. Thus, this paper provides useful anchorages
guidance to practising engineers on the design of deep 17. IS 10270 (1982) Guidelines for design and construction of pre-
basements using diaphragm walls. stressed rock anchors
18. IS 14268 (1995) Uncoated stress relieved low relaxation seven-
ply strand for prestressed concrete-specification
Acknowledgements Authors are thankful to all the staff of Larsen 19. ASTM D6760-08 Standard test method for integrity testing of
and Toubro, Construction for granting the permission to use the concrete deep foundations by ultrasonic crosshole testing
experimental data to reach the conclusions. Special thanks to

123

You might also like