Calculo de ampacidad

1. AAAC 240 mm2, 32.9 MVA

IEEE Std. 738-2006 method of calculation

Air temperature is 25.00 (deg C)


Wind speed is 0.61 (m/s)
Angle between wind and conductor is 90 (deg)
Conductor elevation above sea level is 3470 (m)
Conductor bearing is 90 (deg) (user specified bearing, may not be value
producing maximum solar heating)
Sun time is 12 hours (solar altitude is 90 deg. and solar azimuth is 180
deg.)
Conductor latitude is -12.0 (deg)
Atmosphere is CLEAR
Day of year is 50 (corresponds to febrero 19 in year 2017) (day of the
year with most solar heating)

Conductor description: AAAC 240 mm2 Aleacion de Aluminio T-6201 (ASTM)


Conductor diameter is 2.060 (cm)
Conductor resistance is 0.1354 (Ohm/km) at 25.0 (deg C)
and 0.1581 (Ohm/km) at 50.0 (deg C)
Emissivity is 0.5 and solar absorptivity is 0.5

Solar heat input is 13.520 (Watt/m)


Radiation cooling is 12.448 (Watt/m)
Convective cooling is 47.009 (Watt/m)

Given a maximum conductor temperature of 75.0 (deg C),


The steady-state thermal rating is 504.1 amperes