You are on page 1of 13

COOLING TECHNOLOGY INSTITUTE

CTI CODE TOWER


Standard Specifications

For the Design of Cooling Towers


With Redwood Lumber

October 2014 STD-103 (14)

This document was developed using the consensus procedure outlined in the CTI Operating Procedure 304
and has been approved for publication by the CTI Board of Directors
Foreword
This Cooling Technology Institute (CTI) publication is published as an aid to cooling tower purchasers and designers. It may be
used by anyone desiring to do so, and efforts have been made by CTI to assure the accuracy and reliability of the data contained
herein. However, CTI makes no warranty of fitness for particular purpose or merchantability nor any other warranty expressed,
implied or statutory. In no event shall CTI be liable or responsible for Incidental, Consequential or Commercial losses or damage
of any kind resulting from this publication's use; or violation of any federal, state, or municipal regulation with which this
publication may conflict or for the infringement of any patent resulting from the use of this publication.

All CTI codes and standards are copyrighted with all rights reserved to CTI. The reproduction of any part of this or any other CTI
code or standard is a violation of Federal Law. One must recognize and appreciate commitment by a number of volunteer
members who donate their time to develop and update CTI codes and standards. The monies spent for code development,
administrative staff support and publication are essential and constitute a substantial drain on CTI. The purchase price of these
documents helps to offset these costs. Reproduction and distribution by others, in addition to being unethical, undermines this
system and constitutes a further financial drain on CTI. When copies are needed, you are requested to call or write the Cooling
Technology Institute, P.O. Box 73383, Houston, Texas 77273, (281) 583-4087. Please request that your associates buy the
required codes and standards rather than copy them. Your cooperation in this matter is greatly appreciated.

Nothing contained herein is to be construed as granting any right for the manufacture, sale or use in connection with any method,
apparatus, or product covered by letters patent, nor as insuring anyone against liability for infringement of letters patent.

This guideline document summarizes the best current state of knowledge regarding the specific subject. This document
represents a consensus of those individual members who have reviewed this document, its scope and provisions. It is intended to
aid all users or potential users of cooling towers.

Approved by the CTI Executive Board.

This document has been reviewed and approved


as part of CTI’s Five Year Review Cycle. This
document is again subject to review in 2019.

Copyright 2014
Approved by the by Cooling Technology Institute CTI - Bulletin
CTI Executive Board Printed in U.S.A. STD-103
TABLE OF CONTENT

Page

Part I Scope, Abbreviations, Other Standards and Definitions

1.0 Scope ........................................................................................................................................................ 5

2.0 Abbreviations ........................................................................................................................................... 5

3.0 Other Standards and Specifications .......................................................................................................... 5

4.0 Definitions of Members............................................................................................................................ 5

Part II Grades of Redwood Lumber

5.0 Purpose ..................................................................................................................................................... 6

6.0 Application of RIS Specifications ............................................................................................................ 6

7.0 Definitions of Grades and Treating Requirements for Framework Members .......................................... 6

8.0 Definitions of Grades for Non-Framework Members .............................................................................. 6

9.0 Definition of Fill....................................................................................................................................... 6

Part III Design Considerations

10.0 Scope ........................................................................................................................................................ 6

11.0 Design Criteria and Allowable Design Values ......................................................................................... 6

12.0 Design Data .............................................................................................................................................. 8

Tables

Table 103-A Reference Design Values for Visually Graded Dimension Lumber ..................................................... 9

Table 103-B Applicability of Adjustment Factors ................................................................................................... 10

Table 103-C Load Duration and Time Effect Factors ............................................................................................. 10

Table 103-D Size Adjustment Factor Cf .................................................................................................................. 11

Table 103-E Temperature Adjustment Factor Ct ..................................................................................................... 11

Table 103-F Moisture Adjustment Factor, Cm ........................................................................................................ 12

Table 103-G Incising Adjustment Factor Ci ............................................................................................................ 12

Table 103-H Flat Use Adjustment Factor Cfu .......................................................................................................... 12

3
4
For the Design of Cooling Towers with Redwood Lumber

Part I
Scope, Abbreviations, Other Standards and Definitions

1.0 Scope
1.1 This standard sets forth recommended timber design 4.0 Definitions of Members
parameters, the recommended grades, and the Framework Members:
specifications and grading rules for redwood lumber to
4.1 Water cooling tower framework members are those
be used in construction of water cooling towers.
members which must be capable of supporting
applicable loads and have published design values (or
2.0 Abbreviations sufficient testing verifying structural integrity) and
include the following:
Columns: Vertical or inclined supporting members in
ICC International Code Council, (www.iccsafe.org)
the tower framework, used to resist axial compression
NDS National Design Specification for Wood or tension stresses in combination with flexural or shear
Construction, (www.awc.org) stresses that may exist.
AWC American Wood Council, (www.awc.org) Horizontal Ties and Struts: The main horizontal
RIS Redwood Inspection Service Bureau, members interconnecting columns or bracing elements.
(www.redwoodinspection.com) Braces: Members in the framework whose primary
IBC International Building Code, latest edition, by ICC function is to provide lateral stability to the structure or
(www.iccsafe.org) individual members. These usually consist of diagonal
ASLC American Softwood Lumber Standard, latest members between columns or beams.
edition, (www.alsc.org). Standard is published by Joists and Beams: Horizontal members used to support
NIST gravity loads such as supports for fan deck flooring, fill,
NIST National Institute of Standards and Technology, drift eliminators, cold and hot water collection and
(www.nist.gov/) distribution basins, flumes, piping and mechanical
equipment. Also included are beam-type members that
resist wind or seismic forces.
3.0 Other Standards and Specifications Decking
3.1 Other standards or specifications as listed below are 4.2 Horizontal planking, typically 50.8mm x 152.4mm (2
referenced in the body of this standard. inches x 6 inches) tongue and groove material or
 ASCE 7 (latest edition) American Society of plywood per CTI-STD-134 (Plywood For Use In
Civil Engineers Standard Minimum Design Cooling Towers) used for fan deck or hot water basin
Loads in Buildings and other Structures. flooring must be capable of sustaining as appropriate,
 National Design Specifications for Wood water loads, live loads, construction and maintenance
Construction. Latest edition, by AWC with loads, environmental loads, concentrated loads and any
accompanying supplement, Design Values for applicable dynamic loads due to equipment.
Wood Construction. Non-Framework Members:
 Standard Specifications for Grades of California 4.3 Non-framework members of water cooling towers are
Redwood Lumber, latest edition by RIS. all parts of subassemblies not included in paragraph 4.1
above.

5
PART II
Grades of Redwood Lumber

5.0 Purpose 7.2 Clear Structural: Paragraph 507 for dimensions and
5.1 Structural grades of lumber defined in this standard are timbers 50.8 mm (2 inches) and thicker.
applicable for all structural framework members of the 7.3 Select Structural: Paragraph 605 for lumber 50.8 mm
tower. Proper application of principles of design as to 101.6 mm (2 inches to 4 inches) thickness, and
outlined herein may be used for structural grades other paragraph 509 for timbers 127 mm (five inches) and
than those indicated in this document, provided the thicker.
adjustment factors for either ASD (Allowable Stress 7.4 No 1 Structural: Paragraph 606 for lumber 50.8 mm to
Design) or LRFD (Load Resistance Factor Design) are 101.6 mm (two inches to four inches) thickness and
made in accordance with the NDS and this standard. paragraph 510 for timbers 127 mm (five inches) and
5.2 General purpose grades of the RIS specifications are thicker.
intended for the non-framework members of the tower.
7.5 For treating requirements of framework members, see
6.0 Application of RIS Specifications CTI-STD-112. Non-treated material shall conform to
6.1 Grades of redwood to be used for framework members requirements for All-Heart Redwood, RIS
in cooling tower construction shall be in accordance Specifications, paragraph 501.
with the "RIS Specifications: sections 7 & 8, 8.0 Definitions of Grades for
specifications for structural grades of California Non-Framework Members
Redwood Lumber, except that boxed heart shall not be
8.1 Grades for non-framework members shall be in
permitted.
accordance with one or more of the grades described in
7.0 Definitions of Grades and Treating paragraphs 103 through 128, excluding 114 and 122, of
Requirements for Framework Members the RIS Specification, 2000 edition.
7.1 Definitions of grades for framework members shall be 9.0 Definition of Fill
as described in RIS Specifications paragraphs for each
9.1 Definition of fill grades shall be as described in RIS
particular grade description as listed below in
Specifications, Paragraph 406 for "Heart Fill Redwood"
accordance with the General Provisions for Structural
and paragraph 407 for "A Fill Redwood."
Grades, paragraph 504, and knots, paragraph 505.
Thickness and width references indicated are nominal
dimensions.

PART III
Design Considerations

10.0 Scope
11.0 Design Criteria and
10.1 This part establishes design values for structural Design Values for ASD and LRFD
framework members and design criteria. Connections
to structural framework are addressed in CTI-STD 11.1 Except where more restrictive design requirements
119 are indicated herein, or by the final user, timber
design shall be in accordance with provisions of the
10.2 Structural grades of lumber shall conform to the National Design Specification for Wood Construction
definitions of grades as set forth in paragraphs 7.1 (NDS), latest edition, by the American Wood Council
through 7.4 of this standard. (AWC).

6
11.2 Unadjusted design values for the structural grades of increased by the difference between the design wet
Redwood described paragraphs 7.1 thru 7.4 above, bulb and the 2% summer design data wet bulb for
are shown in Table 103-A of this standard, as listed structural calculation purposes.
in Table 4A of the NDS Supplement. These values 11.7 Values in table 103-A must be multiplied by the
are based on an accumulated load duration of appropriate size adjustment factor, (CF) provided in
approximately 10 years. table 103-D, depending on the thickness and width of
11.3 The Design Values in Table 103-A are to be adjusted each piece of lumber. Stresses provided in table 103-
for conditions of use, including load duration A are considered Base Values (base value is defined
moisture, and temperature. Applicable adjustment as the allowable unit working stress for a reference
Factors for these and other conditions for both ASD size of lumber). The reference size is set at nominal
and LRFD are indicated in Table 103-B. 50.8 mm by 304.8 mm (2 inches by 12 inches) in
11.4 Cooling towers should be designed to provide for a lumber for grades of Structural Light framing and
50-year duration of operational loads in structural Structural Joist and Plank. CF factors are applicable
framework members Consequently the stresses in to both ASD and LRFD.
Table 103-A for Bending, Tension, Shear and 11.8 Values in table 103-A must be multiplied by the
Compression parallel to grain, need to be multiplied appropriate moisture adjustment factor, (Cm)
by appropriate load duration (or time effect) factors provided in table 103-F. When dimension lumber is
for both ASD (CD) and LRFD (λ). These factors do used where moisture content will exceed 19% for an
NOT apply to Modulus of Elasticity nor extended period of time, design values shall be
Compression perpendicular to grain. The CD and λ multiplied by the appropriate wet service factors from
factors are shown in Table 103-C. (See NDS Figure the table. This includes all cooling tower members
B1 Appendix B for load duration factors appropriate and members used in an unenclosed stair. CM factors
to ASD for durations not indicated). are applicable to both ASD and LRFD.
11.5 When loads of different durations are applied 11.9 Values in Table 103-A shall be multiplied by the
simultaneously, the design of structural members Format Conversion Factor (Kr) and Resistance Factor
shall be based on the critical load combinations as (Φ), which are included in Table 103-B for LRFD
defined by ASCE 7 for ASD or LRFD or the only. These factors are not to be applied to the
requirements of the local building code and per the Modulus of Elasticity.
National Design Specification. 11.10 Compression members such as columns or bracing to
11.6 For members in cooling towers which are subjected resist axial loads shall be restrained from buckling by
to extended periods of operation at temperatures ties, struts, or other suitable bracing. Such bracing
greater than 20° C (68° F), the design values of shall be capable of resisting at least three percent of
Table103-A shall include reduction factors due to the the compression member axial load in addition to any
higher temperatures. These reduced design values, forces resulting from induced flexural stresses.
applicable to both ASD and LRFD, shall be obtained 11.11 Design of axially loaded members shall take into
by multiplying the Table 103-A stresses by the account the stresses and the long-term deflection
temperature correction factors, (Ct) listed in Table effects resulting from eccentricity of load application.
103-E. Prolonged exposure to temperatures over 150° Bow and crook permitted by RIS Specification for
F can cause permanent loss in strength for wood and the grade used shall be included in determining such
the use of lumber for cooling tower framing for such eccentricity except that smaller bow and crook than
applications should be avoided. The temperature to limited by RIS Specifications may be used if such
be used is the actual temperature to which the smaller bow or crook is assured by cooling tower
member under consideration is exposed when the manufacturer's quality control.
tower is at design heat load at design wet-bulb
11.12 Design of axially loaded members shall take into
temperature. An acceptable option is to use the
account flexure resulting from the eccentricity of
design hot-water temperature in the top half of the
axial load application from bolted or other kinds of
flooded portion of the tower and the average of the
connection-joined shear connectors, where shear
design hot water and cold-water temperature in the
transfer to another member is accomplished by
lower half. A statement indicating the design
connections on only one side of the member
temperature distribution shall be included as part of
considered. Such eccentricity shall be taken as not
the manufacturers proposal. If the design wet bulb is
less than one-sixth the member cross sectional
lower than 2% summer design data wet bulb, the
design hot water and cold water temperatures shall be

7
dimension along the bolt axis and perpendicular to take into account wind loads occurring at an angle to
the load direction for bolted connections or, for other the longitudinal and transverse directions (i.e. all
kinds of connections, from the center of gravity of stacks assume either full wind load in both
the shear connector bearing area within the longitudinal and transverse direction or worst case
considered member to the neutral axis of such loading due to the angle the wind load is designed
member parallel to the side connected. Shear for). Design shall take into account the various
connector, as use herein, shall mean shear plate geometric shapes with corresponding shape factors to
timber connector, split ring timber connector, or be applied for wind force calculations. Load
toothed ring. Nails or spikes shall not be used for calculations for all structural members due to wind
connecting structural framework members. Specifics loads must be provided upon request. The dry weight
regarding timber cooling tower connection of the tower shall be used in determining uplift
requirements are further defined in CTI STD-119. forces. Adequate anchorage to foundations or the
11.13 The designer shall take into account the effects of any supporting structure shall be provided in accordance
lack of end restraint on effective column length (le); with the specified or local building code.
the effect of the location of column splices; the effect 12.2 Seismic: Design for seismic forces should be in
of eccentricity due to framing and material accordance with ASCE 7, latest edition unless
tolerances; and the effect of field construction specified otherwise. The specified seismic loading
tolerances on the overall column performance. and the wind load shall be considered separately and
11.14 The slenderness ratio for solid columns, le/d (where d design of the structure and its components shall
is the least cross-sectional dimension) shall not provide for the maximum forces resulting from
exceed 50. The column stability factor, Cp, shall be either. Load calculations for all structural members
calculated per NDS requirements and applied to the due to seismic loads must be provided upon request.
compression stress parallel to grain from Table 103- 12.3 Gravity Loads:
A for both ASD and LRFD. 12.3.1 Such loads used for design of tower,
11.15 The designer shall take into account the effects of framing, cold water basin, and foundations shall
simple, continuous and cantilevered beams, beam include wet weight of lumber; operating weight of
splice locations, concentrated loads, beam stability tower including water in the distribution system;
(depth of a bending member compared to is breadth snow and ice loads; and an allowance for
as for intermediate fill joists) and deflection of construction loads on the horizontal floor or deck
bending members. The beam stability factor, CL, surfaces. Load calculations for all structural
shall be developed per NDS procedures and applied members due to gravity loads must be provided upon
as required. request.
11.16 If mechanical incising is performed, the stresses in 12.3.2 Unless otherwise specified by the Purchaser,
Table 103-A shall be adjusted per the factors in Table the water weight load in the hot water distribution
103-G. Details for incising (length, depth, density of basin shall be based on the overflow depth of the
incision) are specified in the current edition of CTI- basin. The water weight load in distribution troughs
STD-112 “Pressure Preservative Treatment of shall be based on the overflow depth of the troughs.
Lumber”, applicable to both ASD and LRFD. All piping water weight loads shall be based on pipes
11.17 When loads are applied to the wide face of bending completely full.
members, the design value for bending, Fb, shall be 12.3.3 For design, the wet operating weight of
multiplied by the flat use factor, Cfu, as indicated in redwood lumber shall be calculated on the basis of
Table 103-H; applicable to both ASD and LRFD. 720kg/m3 (45 pounds per cubic foot) for both close
grain material and open grain material (G=.44 and
M.C. =175%). Dry weight to be used for uplift force
12.0 Design Data calculations shall not be greater than 416 kg/m3 (26
12.1 Wind: Unless otherwise specified, wind pressure pounds per cubic foot) for both close grain material
design shall be in accordance with ASCE 7 latest as well as open grain material. (G=.37 and M.C.
edition. In design of the component portions of the =15%)
structure, consideration of positive and negative 12.3.4 Unless greater design snow loads are specified
pressures on windward and leeward surfaces shall be by Purchaser or required by codes or regulations
taken into account. Design shall provide for the applicable to the cooling tower site, the basic snow
maximum forces that would result from any wind load on the fan deck or other similar exposed areas
direction. There shall be no reduction of wind force shall be per ASCE 7 latest edition for a 100 year
taken for the possible shielding effect of structures mean recurrence interval with no reduction. For
adjacent to the cooling tower. Any reduction of wind areas where snow loads are not indicated per ASCE 7
force taken for shielding effects at the fan stacks shall latest edition or specified by the Purchaser or local
8
code, the design snow loads shall be determined by has been reviewed and designed to accommodate a
research and analysis of the effect of local climate higher loading for longer durations. Design loads
and topography. The design shall provide for loading shall consider necessity for removing tower
requirements per ASCE 7 latest edition as applied to components such as motors and gearboxes across the
roofs of buildings except that the roof slope factor, fan deck or other surface, with resultant local
Cs, shall not be less than 1.0. concentrated loads, during maintenance or repair.
12.4 Construction and Maintenance Loads: Design During construction and or maintenance of the
shall account for construction and maintenance cooling tower, adequate design of the framework
requirements which necessitate loading of fan deck or members must be taken into account for the safety of
other areas with equipment, materials, or personnel workers and maintenance crews. Load calculations
during initial construction or for maintenance for all structural members including tie lines, due to
operations. Unless otherwise approved by the construction or maintenance loads must be provided
Purchaser, the minimum design load for such upon request.
construction or maintenance loads on the fan deck 12.5 Member Sizes
shall be taken as 2.87kPa (60 pounds per square foot) 12.5.1 Calculations to determine required member
over the whole fan deck area, or as approved by the properties shall be based on net dimensions (actual
Purchaser on those areas to be clearly defined on the size) and not on nominal dimensions.
manufacturer's design drawings. Unless otherwise
specified by the Purchaser, such construction or 12.5.2 Sizes of dressed boards, strips, and dimension
maintenance load need not be combined with snow lumber identified by nominal sizes shall not be less
load, and the cumulative duration of such than the dressed dimension in inches shown in the
construction or maintenance load shall not be less RIS Specifications, section 2, paragraph 15.
than two months. Permanently stored materials on 12.5.3 Manufacturing tolerances for nominal rough
the fandeck, such as scaffold planks, oil drums, etc, and dressed sizes shall be in accordance with the RIS
should not exceed 50 psf, unless the fandeck framing Specification.

TABLE 103-A
REDWOOD STRESS (1)

Grade Units Fb Ft Fv Fc┴ Fc E (2) Emin


Kpa 12066 6895 1103 4482 12755 9.6 x 106 3.5 x 106
Clear Structural
psi 1750 1000 160 650 1850 1.4 x 106 0.51 x 106
Select Structural Kpa 9308 5516 1103 4482 10342 9.6 x 106 3.5 x 106
(close grain) psi 1350 800 160 650 1500 1.4 x 106 0.51 x 106
Select Structural Kpa 7584 4309 1103 2930 7584 7.5 x 106 2.76 x 106
open grain psi 1100 625 160 425 1100 1.1 x 10 6
0.4 x 106
No. 1 Structural Kpa 6722 3964 1103 4482 8274 8.9 x 106 3.24 x 106
(close grain) psi 975 575 160 650 1200 1.3 x 106 0.47 x 106
No. 1 Structural Kpa 5343 3103 1103 2930 6205 7.5 x 106 2.76 x 106
open grain psi 775 450 160 425 900 1.1 x 106 0.4 x 106
1) Values must be multiplied by additional factors for condition of use. See Table 103-B for adjustment factors
for both ASD and LRFD.
2) Actual MOE values of visually graded redwood vary widely. Mechanical measurement of MOE for individual
members is recommended

9
TABLE 103 - B
Applicability of Adjustment Factors for SAWN LUMBER
ASD LRFD
ASD and LRFD
only only

Repetitive Member Factor


Table 103-G, Sec. 11.16
Table 103-H, Sec. 11.17
Table 1103-E, Sec. 11.6

Format Conversion
Factor Sec. 11.9
Column Stability Factor
Table 103-C, Sec. 11.4

Table 103-D, Sec. 11.7


Table 103-F, Sec. 11.8

Resistance Factor
Beam Stability Factor
Load Duration Factor

Temperature Factor
Wet Service Factor

Time Effect Factor


Flat Use Factor

Incising Factor

Sec. 11.9

Table 114-C
Size Factor
Sec. 11.15

Sec. 11.14
Mechanical

(1)
Property

KF Φ
Fb' = Fb x CD CM Ct CL CF Cfu Ci Cr - 2.54 0.85 λ
F t ' = Ft x CD CM Ct - CF Ci - - 2.70 0.8 λ
Fv' = Fv x CD CM Ct - - Ci - - 2.88 0.75 λ
Fc' = Fc x CD CM Ct - CF Ci - CP 2.40 0.9 λ
Fc┴' = Fc┴ x - CM Ct - - Ci - - 1.67 0.9 -
E' = E x - CM Ct - - Ci - - - - -
Emin' = Emin x - CM Ct - - Ci - - 1.76 0.85 -
(1) Members that are in contact or spaced no more than 24” on center, not less than 3 in number and are joined
by decking, flooring or other load distributing elements are considered repetitive where Cr = 1.15.

Table 103 – C
ASD Only LRFD only
Duration of Load Factor - CD Time Effects Factor, λ

Duration Load Case CD Load Combination (3) λ


Permanent (50 year) Dead Load 0.95 1.4D 0.6
Snow (also construction
Two months and maintenance per 1.15 1.2D + 1.6L + 0.5(Lr or S or R)
Section 12.4)
Seven Days Construction 1.25 when L is from storage 0.7
Ten minutes Wind / Earthquake 1.6 when L is from occupancy 0.8
(1)
Impact 1.6 when L is from impact (1) 1.0
(1)
Factors for Impact Loading are reduced for both ASD 1.2D + 1.6(Lr or S or R) + (L or 0.8W) (2) 0.8
and LRFD as it is assumed that the cooling tower
lumber is pressure treated with water borne 1.2D + 1.0 W + L + 0.5(Lr or S or R) (2) 1.0
preservatives.
(2)
The 1.0 factor for live load, L, can be reduced to 0.5 1.2D + 1.0E + L +0.2S (2) 1.0
if the considered uniform live load is 100 psf or less. 0.9D + 1.0W 1.0
(3)
These NDS load combinations are per ASCE 7-10. 0.9D + 1.0E 1.0

10
TABLE 103-D: Size Adjustment Factor CF
Fb
THICKNESS
GRADES WIDTH 101.6 Ft Fc
50.8 mm & 76.2 mm
mm
(2" & 3") (4")
Select Structural 50.8, 76.2 & 101.6 mm
No. 1 and Better 1.5 1.5 1.5 1.15
(2, 3 & 4 inches)
No. 1 127 mm
No. 2. 1.4 1.4 1.4 1.1
(5")
152.4 mm
1.3 1.3 1.3 1.1
(6")
203.3 mm
1.2 1.3 1.2 1.05
(8")
254 mm
1.1 1.2 1.1 1
(10")
304.8 mm
1 1.1 1 1
(12")
355.6 mm
0.9 1 0.9 0.9
(14") & UP

TABLE 103-E: Temperature Adjustment Factor, Ct


Ct
In Service
Design
Moisture
Values
Conditions 68° F T≤100ºF 100ºF<T≤125ºF 125ºF<T≤150ºF

Dry 1 n/a 1 0.9 0.9


Ft E
2
Wet 1 – [0.0015 x ∆T above 68°F up to (max) 150°F]

Fb, Fv ,Fc, Dry 1 n/a 1 0.8 0.7


and Fc┴
Wet 2 1 – [0.0057 x ∆T above 68°F up to (max) 150°F]

1. Temperature reductions for dry use as 'simplified' in 1991 NDS and unchanged in 2012 NDS.
Interpolation between values is acceptable.

2. Temperature reductions for wet use are NDS specifications prior to the 1991 simplification.

11
Table 103-F: Moisture Adjustment Factor CM
WET SERVICE FACTORS, CM

Fb Ft Fv Fc┴ Fc E

.85* 1 0.97 0.67 .8** 0.9

* When (Fb)(Cf) ≤ 7,931kPa (1150psi), CM= 1.0

** When (Fc)(Cf) ≤ 5172kPa (750psi), CM= 1.0

Table 103-G Incising Adjustment Factor Ci


Design Value Ci
E Emin 0.95
Fb Ft Fv Fc 0.80
Fc┴ 1.00

TABLE 103 - H Flat Use Factor Cfu


Lumber Size Cfu
2x4, 3x4 1.1
2x6, 2x8, 3x6, 3x8 1.15
2x10, 3x10 (and wider) 1.2
4x6, 4x8 1.05

4x10 (and wider) 1.1

12
Cooling Technology Institute
PO Box 681807 Houston, Texas 77268
281.583.4087 – Fax: 281.537.1721 – www.cti.org

You might also like