Professional Documents
Culture Documents
DIAGNOSTICS
Table 2: Cases with the same CO2/CO ratio where Meaning of the CO2/CO ratio also de- If the paper is degrading due to the local
its meaning can vary pends on the CO2 and CO historical valu- overheating, other gases (H2, C2H2, C2H4)
es (in IEC 60599 clause 6.1 and 9). have to be present in higher concentra-
CO2 / ppm CO / ppm CO2/CO tions. The paper is impregnated with oil
The CO2/CO ratio becomes signifi- so the oil is also in contact with hot place
150 60 2.5 cant when individual gases are above and combustible gases should be formed.
5000/500 ppm. A ratio below 3 indicates
2500 1000 2.5 ageing of insulation by arcing. A ratio If this ratio is less than 3 and higher than
above 10 indicates cellulose ageing from 10, one should consider other gases, like
thermal heating. H2, CH4, C2H2, C2H4, etc.
Case studies
Case 1 The CO2/CO ratio becomes significant when
In the reported case showed in Table 3, individual gases are above 5000/500 ppm. A
it was concluded that “paper is degra-
ding and the transformer has a hot spot
ratio below 3 indicates ageing of insulation
of about 730 °C.” It is not clear whether by arcing. A ratio above 10 indicates cellulose
the conclusion in the reported case was
made solely on the basis of DGA or
ageing from thermal heating
whether some other measurements also
supported the diagnosis.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 31
TRENDS
DIAGNOSTICS
Case 2
oil was not able to penetrate so deep. Pa- transformers has not been performed yet What could be the reason for high con-
per near the lead was slightly burnt. Com- but it is planned. centrations of CO and CO2 and high
bustible gases were not formed because CO2/CO ratio, when all other gas con-
the affected deep layers of paper were not Table 6 provides a list of such transfor- centrations are normal, and does it re-
well impregnated by the oil. mers where CO, CO2 and CO/CO2 are quire any action? This question is es-
high and other gasses have low values. sential because a significant number of
Furan analysis was performed and in all transformers (394 units i.e. around 8 % of
Case 3 cases it was below 0.02 ppm. The samples the population) are affected by this trend,
Analysing transformers from a data- were taken at low load (<20 % of capa- which cannot be ignored.
base including approximately 4100 city) during winter with oil temperature
transformers, 9.7 % (401 units) of the of around 40 °C. The transformers tend The advice to be taken in the case above
transformers were with CO>500 ppm, to get fully loaded in the summer (from is that along with concentrations of car-
CO2>5000 ppm, and CO2/CO>15. Only May to September) with higher ambient bon monoxide and carbon dioxide, the
1.7 % (7 units) of those transformers temperature (45÷50 °C in Qatar). trending is also to be looked into and that
were also confirmed by high Furan va-
lues >0.2 ppm, indicating cellulose de-
gradation. For the remaining 8 % (394 A database containing DGA data of appro-
units) Furan values were normal. DGA ximately 4100 transformers was analysed
(gases other than CO and CO2) results
for the transformers with high CO2/CO regarding the levels of carbon monoxide
ratio were analysed and it was observed and carbon dioxide
that only 0.7 % (29 out of 401 units) had
abnormal gas values. All the rest were
found normal. Gas trending for those
the oxygen content will also indicate a Gas generation rate DGA. Nowadays with the technology
problem, which is more likely to happen development, online DGA is available.
in sealed conservator type transformers. As per IEEE std C57.104-2008, gas ge- Many different monitoring units have
neration rate should be determined and been introduced to the market. Using
As stated above, CO2/CO ratio is sig- Table 3 of the standard provides recom- fully automated process sampling fre-
nificant when CO2 is above 5000 ppm mended actions. quency has been significantly increased
and CO is above 500 ppm. Below these to hourly sampling instead of daily or
values, the ratio will not result in cor- As already mentioned, the rate of gas gene- monthly sampling. The formula for cal-
rect situation awareness. Accordingly, ration is much more important than a sin- culation of a gas generation rate can also
all transformers from Table 6, except gle gas value or a ratio of gases. Therefore, a be used with such systems.
two transformers (Transformers 2 and follow-up of history values is a must to cal-
3) fulfil this criterion. Even in these ca- culate gas generation rate which is a central
ses the CO2/CO ratio is greater than 10, key for decision making. The formula for Interpretation
concentrations of other gases are normal calculation of gas generation rate is:
and the situation does not appear to be Referring back to the eight transformers
worrying. GGR = 1 x (S2 - S1) x 100 (1) mentioned in the paragraph Case 3, all
T S1 are fairly new and individual or total com-
Analysis of data from the other data- where: bustible gases are well below the caution
base with approximately 22500 DGA GGR stands for gas generation rate, level. Transformers 1, 2 and 7 have CO
results collected since 1980 show that S1 stands for the first sample value, level between 350 and 570 ppm which
the limit of 5000 ppm for CO 2 could S2 stands for the second sample value, may indicate that the sampling rate needs
be too high. According to this study, and T stands for the time between sam- to be increased, unless the gas values were
more realistic limit for CO2 would be ples in days. caused by a previous event. If CO level
2000 ppm, while the limit of 500 ppm rises above 570 ppm and the growth rate
for CO is in agreement with commonly This formula was developed for use in is greater than 0.5 %, it indicates a severe
accepted level. traditional lab analysis, i.e. for offline problem which requires immediate inter-
w w w . t ra n sfo r m e r s - m a g a z i n e . co m
TRENDS
DIAGNOSTICS
P Ramachandran started his career in Pavel Justiz holds an Eng. of Power Elect
transformer industry in 1966 at a Hitachi rical Engineering degree from the Czech
Joint venture in India-TELK, Kerala. He Technical University in Prague, Czech Re-
has been with ABB India since 1999 and public. He worked in testing laboratory in
currently works as Technical Advisor with ORGREZ for most of his professional life,
Power Products Division of ABB. He re- i.e. for almost 20 years. ORGREZ laborato-
ceived his BSc in Electrical Engineering ry provides tests for power and instrument
from the University of Kerala, India and MBA from Cochin transformers, HV rotating machines, surge arresters, insulation
University, India. He is a Fellow of Institution of Engineers (In- liquids, SF6, etc. Pavel is the head of the Department of Diag-
dia) and represented India in CIGRE Study Committee A2 for nostics and HV Testing. He takes part in research projects solving
Transformers between 2002 and 2010. failures and expert systems development.