MONITORING REPORT EQUIPMENT PERFORMANCE

UNIT WATER TREATMENT PLANT PT. REKIND DAYA MAMUJU


PLTU 2 X 25 MW SULAWESI BARAT, MAMUJU
DATE : 13 Oktober 2021

UNIT #1 UNIT #2
PERSONAL CHECK PERSONAL CHECK
MAXIMUM MAXIMUM
TIME STANDARD CONDITION RESULT VALUE OF TIME STANDARD CONDITION RESULT VALUE OF
WATER SAMPLE RESULT WATER SAMPLE RESULT
PREATREATMENT SYSTEM PREATREATMENT SYSTEM
FLOCCULATION SETTLING TANK FLOCCULATION SETTLING TANK
Outlet Turbidity Value ≤ 20 NTU 0.252 0.252 Outlet Turbidity Value ≤ 20 NTU 0.252 0.252
FINE SAND FILTER FINE SAND FILTER
Outlet Turbidity Value ≤ 3 NTU Unit Standby 0 Outlet Turbidity Value ≤ 3 NTU 0.269 0.269
ULTRA FILTRATION ULTRA FILTRATION
Inlet Residual Chlorine Content ≤ 2 mg/l Unit Standby 0 Inlet Residual Chlorine Content ≤ 2 mg/l 0.03 0.03
Outlet Turbidity Value ≤ 0.4 NTU Unit Standby 0 Outlet Turbidity Value ≤ 0.4 NTU 0.079 0.079
DESALINATION SYSTEM DESALINATION SYSTEM
SALT WATER REVERSE OSMOSIS SALT WATER REVERSE OSMOSIS
Silt Density Index 3 Unit Standby 0 Silt Density Index 3 1.41 1.41
Inlet Residual Chlorine Content ≤ 0.1 mg/l Unit Standby 0 Inlet Residual Chlorine Content ≤ 0.1 mg/l 0.05 0.05
Conductivity Vessel #1 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #1 ≤ 2000 µs/cm 950 950
Conductivity Vessel #2 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #2 ≤ 2000 µs/cm 825 825
Conductivity Vessel #3 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #3 ≤ 2000 µs/cm 680 680
Conductivity Vessel #4 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #4 ≤ 2000 µs/cm 985 985
Conductivity Vessel #5 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #5 ≤ 2000 µs/cm 747 747
Conductivity Vessel #6 ≤ 2000 µs/cm Unit Standby 0 Conductivity Vessel #6 ≤ 2000 µs/cm 931 931
Outlet Conductivity ≤ 2000 µs/cm #DIV/0! #DIV/0! Outlet Conductivity ≤ 2000 µs/cm 853 853
BRACKISH WATER REVERSE OSMOSIS BRACKISH WATER REVERSE OSMOSIS
Conductivity Vessel #1 ≤ 50 µs/cm Unit Standby 0 Conductivity Vessel #1 ≤ 50 µs/cm 30.1 30
Conductivity Vessel #2 ≤ 50 µs/cm Unit Standby 0 Conductivity Vessel #2 ≤ 50 µs/cm 7.39 7
Conductivity Vessel #3 ≤ 50 µs/cm Unit Standby 0 Conductivity Vessel #3 ≤ 50 µs/cm 7.29 7
Outlet Conductivity ≤ 50 µs/cm #DIV/0! #DIV/0! Outlet Conductivity ≤ 50 µs/cm 14.9 15
DEMINERALIZE SYSTEM DEMINERALIZE SYSTEM
MIXED BED MIXED BED
DD ≤ 0.2 µs/cm #DIV/0! #DIV/0! DD ≤ 0.2 µs/cm #DIV/0! #DIV/0!
SiO2 ≤ 20 µg/l #DIV/0! #DIV/0! SiO2 ≤ 20 µg/l #DIV/0! #DIV/0!